Catalogs > Industrial Controls Catalog > Power Supplies > Uninterruptible Power Supply > 1609-U
1609-U
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions and Shipping Weights |
| Electrical Ratings | 1609-U750N | 1609-U1000N | 1609-U1500N | |
| Input | V nom. | 120V | ||
| Voltage Range, default | 82…144V | |||
| Voltage Range, widest, on line | 75…154V | |||
| Capacity Frequency | 50/60 Hz +/- 3 Hz (auto sensing) | |||
| Output | V nom. | 120V | ||
| Capacity | 750VA (500 W) | 1000VA (670 W) | 1440VA (980 W) | |
| Frequency | 47…53 Hz for 50 Hz, nominal 57…63 Hz for 60 Hz, nominal |
|||
| THD | <5% at full load | |||
| Crest Factor | up to 5:1 | |||
| Output Connections | (6) NEMA 5-15R | (8) NEMA 5-15R | (8) NEMA 5-15R | |
| Protection | Surge Rating | 540 J | 459 J | 459 J |
| Filtering | Full time multi-pole noise filtering: 0.3% IEEE surge let-through, zero clamping response time, meets UL 1449 | |||
| Regulatory | UL 1778, CSA, BSMI, FCC Part 15 Class A, UL Listed, VCCI | UL 1778, CSA, BSMI, FCC Part 15 Class A | UL 1778, CSA, BSMI, FCC Part 15 Class A | |
| Battery Pack | Typical Run Time, full load | 4.6 minutes (500 W) | 6.1 minutes (670 W) | 6.7 minutes (980 W) |
| Typical Run Time, half load | 15.9 minutes (250 W) | 20.6 minutes (335 W) | 23.9 minutes (490 W) | |
| Type | Maintenance-free, sealed Lead Acid with suspended electrolyte, leakproof | |||
| Typical Recharge Time | 3 hours | |||
| Environment | Temperature | 0…40 °C (32…104 °F), operating -15…45 °C (5…113 °F), storage |
||
| Altitude | 0…3000 m (0…10 000 ft), operating | |||
| Humidity | 0…95%, operating | |||
| Heat Output | 90 BTU per hour | 100 BTU per hour | 135 BTU per hour | |
| Audible Noise | 55 dB @ 1 meter | 41 dB @ 1 meter | 45 dB @ 1 meter | |
| Communication | Interface Ports | DB9 RS-232, SmartSlot, USB | ||
| Control Panel | LED status display with load and battery bar graphs and On Line, On Battery, Replace Battery, and Overload indicators | |||
| EPO | optional | |||
| Audible Alarm | Alarm when: on battery, distinctive low battery, and configurable delays | |||