Condition Sensing Switches and Controls

Catalogs > Industrial Controls Catalog > Condition Sensing Switches and Controls > Temperature, Mechanical

Temperature, Mechanical

Introduction Standards Compliance and Certifications Introduction Technical Data Ordering Information Catalog Number Explanation
Product Selection Modifications Accessories Renewal Parts Factory Options Approximate Dimensions
Accessories

Ordering Accessories

Accessories are ordered as separate catalog numbers. Select the required accessories from the accessories table below.

Angle Mounting Brackets

Description Bracket Type Cat. No.
For mounting one or two open type Bulletin 836 Style A Pressure Controls or Bulletin 837 Temperature Controls on an enclosure mounting plate. Single bracket 836-N11
Dual mounting bracket 836-N12
  

Hardware Kits for Mounting Open Type Controls in Special Enclosures

Description Kit Contents Material Cat. No.
Style A Controls
For mounting open type controls in special enclosures by user. Allows ease of running a capillary external to the enclosure. For use with Type 1 and 4 & 13 enclosures with wall thickness up to 0.25 in. (6.35 mm). Bulb and capillary with armored capillary Brass 837-N17
  

Thermostat Wells¬ 

Description Material Type of Control Control Bulb Size
[in. (mm)]
Cat. No.
Thermostat wells are used when inserting the sensing bulb into a pressurized system. This allows removal of the sensing bulb for recalibration or inspection without having to discharge the system Brass Remote standard capillary 3-3/4 (95) 837-N1
8-1/2 (216) 837-N6
Remote armored capillary 3-3/4 (95) 837-N3
8-1/2 (216) 837-N7
Direct immersion 3-1/2 (89) 837-N2
Type 316
Stainless steel
Remote standard capillary 3-3/4 (95) 837-N12
8-1/2 (216) 837-N13
Remote armored capillary 3-3/4 (95) 837-N14
8-1/2 (216) 837-N15
Direct immersion 3-1/2 (89) 837-N16
  
¬ External pressure rating — 1000 psi at 600˚F maximum.

Packing GlandsT 

Description Material Type of Control Cat. No.
Packing glands form a seal around any desired position of the capillary, allowing any length of capillary to be inserted into the vessel where temperature is to be sensed. Brass Remote standard capillary 837-N5
Remote armored capillary 837-N4
  
T Maximum sealing pressure — 50 psi.

Figure 6
Thermostat Wells


Click to enlarge - 837-17-5-2


Packing Glands

Click to enlarge - 837-17-5-3


¬ External pressure rating — 1000 psi at 600°F maximum.
T Maximum sealing pressure — 50 psi.