Catalogs > Industrial Controls Catalog > Push Buttons > 22 mm IEC > Bulletin 800MB Push Buttons
Bulletin 800MB Push Buttons
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
Specifications¬
| Electrical Ratings | ||
| Contact Ratings | Refer to the Contact Ratings tables below. | |
| Dielectric Strength | 1600V for one minute | |
| 1300V for one minute (Logic Reed) | ||
| Electrical Design Life Cycles | 750 000 at maximum rated load | |
| 200 000 at maximum rated load (Logic Reed) | ||
| Mechanical Ratings | ||
| Vibration | 10…2000 Hz 1.52 mm displacement (peak-to-peak) max./10 G max. (except Logic Reed) | |
| Shock | 1/2 cycle sine wave for 11 ms ³ 25 G (contact fragility) and no damage at 100 G | |
| Degree of Protection | Type 13; IEC 144 IP65 Oiltight | |
| Contact Operation | Contact blocks with bifurcated spanner: Slow, make and break, simple break. | |
| Logic Reed contact blocks: Snap-action | ||
| Typical Operating Forces | 2.45 lb (10.8 N) | |
| Operators without Contact Blocks | ||
| Contact Blocks | Standard | 1.5 lb (6.7 N) 0.62 lb (2.6 N) |
| Logic Reed | ||
| Environment | ||
| Temperature Range | Operating | +32…+131 °F (0…+55 °C) |
| Storage | 40…+185 °F (40…+85 °C) | |
| Note:Operating temperatures at +32 °F (0 °C) are based on the absence of freezing moisture and liquids. | ||
| Humidity | 50% at +104 °F (+40 °C) | |
| Panel Thickness Requirements | 1/16…1/4 in. (1.6…6.4 mm) | |
| ¬ Performance Data — See Performance Data. | ||
Standard Contact Ratings
(IEC 337-1) (NEMA ICS 2-125) Maximum continuous current Ith 10 A. Bulletin 800MB units have control circuit ratings with 800M contact blocks as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-II | A300 | 120…300 72…120 24…72 T |
7200 VA 60 A 60 A |
720 VA 720 VA 10 A |
| T For applications below 24V and 24 mA, Logic Reed contacts are recommended. | |||||
Logic Reed Contact Ratings
Maximum: 150V AC, 0.15 A, 8VA, and 30V DC, 0.06 A, 1.8VA. Should only be used with resistive loads.
Wire Capacity
Small screw contact blocks —
Accept 1 (one) #14 or 2 (two) #16 AWG solid or stranded wires.
Large screw contact blocks —
Accept 2 (two) #12 AWG wires.
Push-on connectors —
Accept 2 (two) 0.110 in x 0.032 in connectors or 1 (one) 0.250 in x 0.032 in connector.