Catalogs > Industrial Controls Catalog > Push Buttons > 30 mm NEMA
30 mm NEMA
| Introduction | Standards Compliance and Certifications | Specifications | Product Selection | Accessories | Approximate Dimensions |
Specifications¬
| Electrical Ratings | ||
| Contact ratings | Refer to the contact ratings tables on Standard Contact Ratings. | |
| Dielectric strength | 2200V for one minute, 1300V for one minute (Logic Reed) | |
| Electrical design life cycles | 1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed) | |
| Mechanical Ratings | ||
| Vibration | 10…2000 Hz, 1.52 mm displacement (peak-to-peak) max./ 10 G max. (except Logic Reed) |
|
| Shock | 1/2 cycle sine wave for 11 ms ³ 25 G (contact fragility) and no damage at 100 G | |
| Degree of protection | Type 1/4/12/13 (800T); Type 1/4/4X/12/13 (800H); EN/IEC 60529 IP66/65 | |
| Mechanical design life cycles | ||
| Push buttons | (Momentary, non-illuminated) | 10 000 000 min. |
| (Momentary, illuminated) | 250 000 min. | |
| (Push-pull/twist-to-release) | 250 000 min. | |
| Selector switches | (Non-illuminated) | 1 000 000 min. |
| (Illuminated, key-operated) | 200 000 min. | |
| Potentiometers | 25 000 min. | |
| All other devices | 200 000 min. | |
| Contact operation | Shallow, mini, and low-voltage contact blocks: Slow, double make and break Logic Reed and sealed switch contact blocks: Single break magnetic |
|
| Wire gauge/Terminal screw torque | #18…14 AWG (#18…10 Max Duty) / 6…8 lbin. | |
| Typical operating forces | ||
| Operators without contact blocks | Flush, extended button, standard mushroom, jumbo plastic mushroom: 2 lbs max. Jumbo and extended aluminum mushroom head: 3.95 lbs max. Maintained selector switch: 3.6 inlb max. |
|
| Spring return selector switches | 3.6 inlb to stop, 0.2 inlb to return | |
| Illuminated push buttons and push-to-test pilot lights | 5 lb max. | |
| 2-position push-pull | 8.0 lb max. push or pull | |
| 3-position push-pull | 8 lb max. push to in position or pull to center position (15 lb max. pull to out position) | |
| Twist-to-release or push-pull | 9 lbs max. push or pull 30 inoz max. twist, 6 inoz minimum return | |
| Potentiometer | Rotational torque 3…12 inoz; stopping torque 12 inlb (minimum) | |
| Contact blocks | Standard | 1 lb |
| Logic Reed | 1 lb max. | |
| Sealed switch | 3 lb max. at 0.205 in. plunger travel | |
| Stackable sealed switch | 1 lb max. | |
| MaxDuty | 1.4 lb max. | |
| PenTUFF | 1.4 lb max. | |
| Self Monitoring | 1.6 lb | |
| Environment | ||
| Temperature range | Operating | 40…+131 °F (40…+55 °C) |
| Storage | 40…+185 °F (40…+85 °C) | |
| Note:Operating temperatures below freezing are based on the absence of moisture and liquids. Consult your local Rockwell Automation sales office or Allen-Bradley distributor for use in lower temperature applications. | ||
| Humidity | 50…95% RH from 77…140 °F (25…60 °C) per Procedure IV of MIL-STD-810C, Method 507.1 cycling test |
|
| ¬ Performance Data — See Performance Data. | ||
Standard Contact Ratings
Minimum: 24V, 24 mA
Maximum thermal continuous current Ith 10 A AC/2.5 A DC. Bulletin 800T units with 800T-XA contacts have ratings as follows:
| Max. Opertnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | A600 | 120…600 72…120 24…72 |
7200VA 60 A 60 A |
720VA 720VA 10 A |
| DC 600 | DC-13 | Q600 | 28…600 24…28¬ |
69VA 2.5 A |
|
| ¬ For applications below 24V/24 mA, PenTUFF™ or Logic Reed contacts are recommended. | |||||
Sealed Switch Contact Ratings
Minimum: 5V, 1 mA
Maximum continuous current Ith 5 A. Bulletin 800T units have control circuit ratings with sealed switch contact blocks as follows:
| Max. Opertnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | B600 | 120…600 0…120 |
3600VA 30 A |
360VA 3 A |
| DC 300 | DC-13 | P300 | 24…300 0…24 |
138VA 5.0 A |
|
Stackable Sealed Switch Contact Ratings
Minimum: 5V, 10 mA (digital); 24V, 1 mA (analog)
Maximum continuous current Ith 2.5 A. Bulletin 800T untis have control circuit ratings with sealed switch contact blocks as follows:
| Max. Opertnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 0…120 |
1800VA 15 A |
180VA 1.5 A |
| DC 150 | DC-13 | Q150 | 24…150 0…24 |
69VA 2.5 A |
|
Logic Reed Contact Ratings
Minimum — DC: 5V, 1 mA
Maximum — DC: 30V, 0.06 A, AC: 150V, 0.15 A
Should only be used with resistive loads.
Materials Used in 800H Type 4X Operators
Thermoplastic Polyester (Fiberglass Reinforced)
- Bushings
- Mounting Rings
- Sockets
Thermoplastic Polyester
- Non-illuminated button caps
Transparent Amorphous Nylon
- Pilot light lens cap
- Illuminated button caps
Glass Filled Crystalline Nylon
- Thrust washer
Mineral Filled Nylon
- Trim washer
Nitrile (Synthetic Rubber)
- Gaskets and internal seals
PenTUFF™ (Low Voltage) Contact Ratings
Minimum DC: 5V, 1 mA
Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC. Bulletin 800T units with 800T-XAV contacts have ratings as follows:
| Max. Opertnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 0…120 |
1800VA 15 A |
180VA 1.5 A |
| DC 150 | DC-13 | R150 | 24…150 0…24 |
28VA 1.0 A |
|
Snap Action Contact Ratings
| Max. Opertnl. Volts Ue |
Contact Rating Designation |
Rated Operational Currents | ||
| Volts Ue | Make | Break | ||
| AC 300 | A300 | 120…300 24…72 |
7200VA 60 A |
720VA 10 A |
| DC 250 | — | 230…250 115…125 |
0.2 A 0.4 A |
|
MaxDuty Contact Rating
Maximum thermal continuous current Ith 24 A.
Pilot Duty — 120V AC, 12 A; 24V DC, 10 A
Motor Ratings — 120V AC, 1.5 Hp; 240V AC, 3 Hp; 24V DC,
10 A FLA/60 A LRA
Time Delay Contacts
| Max. Opertnl. Volts Ue |
Contact Rating Designation |
Rated Operational Currents | ||
| Volts Ue | Make | Break | ||
| AC 120 | B150 | 120 | 3600VA | 360VA |
| Note:This device is not rated for DC applications. | ||||
Adjustment range: 0.5…15 s ± 25% Ith = 5 A