Push Buttons

Catalogs > Industrial Controls Catalog > Push Buttons > 30 mm NEMA

30 mm NEMA

Introduction Standards Compliance and Certifications Specifications Product Selection Accessories Approximate Dimensions
Specifications

Specifications¬ 

Electrical Ratings
Contact ratings Refer to the contact ratings tables on Standard Contact Ratings.
Dielectric strength 2200V for one minute, 1300V for one minute (Logic Reed)
Electrical design life cycles 1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed)
Mechanical Ratings
Vibration 10…2000 Hz, 1.52 mm displacement (peak-to-peak) max./
10 G max. (except Logic Reed)
Shock 1/2 cycle sine wave for 11 ms ³ 25 G (contact fragility) and no damage at 100 G
Degree of protection Type 1/4/12/13 (800T); Type 1/4/4X/12/13 (800H); EN/IEC 60529 IP66/65
Mechanical design life cycles  
Push buttons (Momentary, non-illuminated) 10 000 000 min.
(Momentary, illuminated) 250 000 min.
(Push-pull/twist-to-release) 250 000 min.
Selector switches (Non-illuminated) 1 000 000 min.
(Illuminated, key-operated) 200 000 min.
Potentiometers 25 000 min.
All other devices 200 000 min.
Contact operation Shallow, mini, and low-voltage contact blocks: Slow, double make and break
Logic Reed and sealed switch contact blocks: Single break magnetic
Wire gauge/Terminal screw torque #18…14 AWG (#18…10 Max Duty) / 6…8 lbin.
Typical operating forces  
Operators without contact blocks Flush, extended button, standard mushroom, jumbo plastic mushroom: 2 lbs max.
Jumbo and extended aluminum mushroom head: 3.95 lbs max.
Maintained selector switch: 3.6 inlb max.
Spring return selector switches 3.6 in•lb to stop, 0.2 inlb to return
Illuminated push buttons and push-to-test pilot lights 5 lb max.
2-position push-pull 8.0 lb max. push or pull
3-position push-pull 8 lb max. push to in position or pull to center position (15 lb max. pull to out position)
Twist-to-release or push-pull 9 lbs max. push or pull 30 in•oz max. twist, 6 in•oz minimum return
Potentiometer Rotational torque 3…12 in•oz; stopping torque 12 in•lb (minimum)
Contact blocks Standard 1 lb
Logic Reed 1 lb max.
Sealed switch 3 lb max. at 0.205 in. plunger travel
Stackable sealed switch 1 lb max.
MaxDuty 1.4 lb max.
PenTUFF 1.4 lb max.
Self Monitoring 1.6 lb
Environment
Temperature range Operating –40…+131 °F (–40…+55 °C)
Storage –40…+185 °F (–40…+85 °C)
Note:Operating temperatures below freezing are based on the absence of moisture and liquids. Consult your local Rockwell Automation sales office or Allen-Bradley distributor for use in lower temperature applications.  
Humidity 50…95% RH from 77…140 °F (25…60 °C) per Procedure IV of MIL-STD-810C,
Method 507.1 cycling test
  
¬ Performance Data — See Performance Data.

Standard Contact Ratings

Minimum: 24V, 24 mA

Maximum thermal continuous current Ith 10 A AC/2.5 A DC. Bulletin 800T units with 800T-XA contacts have ratings as follows:


Max. Opertnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 600 AC-15 A600 120…600
72…120
24…72
7200VA
60 A
60 A
720VA
720VA
10 A
DC 600 DC-13 Q600 28…600
24…28¬ 
69VA
2.5 A
  
¬ For applications below 24V/24 mA, PenTUFF™ or Logic Reed contacts are recommended.

Sealed Switch Contact Ratings

Minimum: 5V, 1 mA

Maximum continuous current Ith 5 A. Bulletin 800T units have control circuit ratings with sealed switch contact blocks as follows:


Max. Opertnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 600 AC-15 B600 120…600
0…120
3600VA
30 A
360VA
3 A
DC 300 DC-13 P300 24…300
0…24
138VA
5.0 A
  

Stackable Sealed Switch Contact Ratings

Minimum: 5V, 10 mA (digital); 24V, 1 mA (analog)

Maximum continuous current Ith 2.5 A. Bulletin 800T untis have control circuit ratings with sealed switch contact blocks as follows:


Max. Opertnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 300 AC-15 C300 120…300
0…120
1800VA
15 A
180VA
1.5 A
DC 150 DC-13 Q150 24…150
0…24
69VA
2.5 A
  

Logic Reed Contact Ratings

Minimum — DC: 5V, 1 mA
Maximum — DC: 30V, 0.06 A, AC: 150V, 0.15 A
Should only be used with resistive loads.


Materials Used in 800H Type 4X Operators
Thermoplastic Polyester (Fiberglass Reinforced)



Thermoplastic Polyester


Transparent Amorphous Nylon


Glass Filled Crystalline Nylon


Mineral Filled Nylon


Nitrile (Synthetic Rubber)


PenTUFF™ (Low Voltage) Contact Ratings

Minimum DC: 5V, 1 mA
Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC. Bulletin 800T units with 800T-XAV contacts have ratings as follows:


Max. Opertnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 300 AC-15 C300 120…300
0…120
1800VA
15 A
180VA
1.5 A
DC 150 DC-13 R150 24…150
0…24
28VA
1.0 A
  

Snap Action Contact Ratings

Max. Opertnl.
Volts Ue
Contact Rating
Designation
Rated Operational Currents
Volts Ue Make Break
AC 300 A300 120…300
24…72
7200VA
60 A
720VA
10 A
DC 250 230…250
115…125
0.2 A
0.4 A
  

MaxDuty Contact Rating

Maximum thermal continuous current Ith 24 A.
Pilot Duty — 120V AC, 12 A; 24V DC, 10 A
Motor Ratings — 120V AC, 1.5 Hp; 240V AC, 3 Hp; 24V DC,
10 A FLA/60 A LRA


Time Delay Contacts

Max. Opertnl.
Volts Ue
Contact Rating
Designation
Rated Operational Currents
Volts Ue Make Break
AC 120 B150 120 3600VA 360VA
  
Note:This device is not rated for DC applications.

Adjustment range: 0.5…15 s ± 25% Ith = 5 A