Catalogs > Industrial Controls Catalog > Push Buttons > Hazardous Location > Bulletin 800R Hazardous Location Push Buttons
Bulletin 800R Hazardous Location Push Buttons
| Product Overview |
|
Bulletin 800R — 30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
- Hazardous location push button stations
- Classes I and II Division 2/Zone 2
- 30.5 mm mounting hole
- Types 4/13 and 4/4X/13
Control Stations
Bulletin 800R control stations are designed for Division 2/Zone 2 hazardous locations. They consist of Bulletin 800H (Type 4/4X/13) or Bulletin 800T (Type 4/13) operators with sealed contact blocks. Bulletin 800R units are available as factory assembled stations or as components for field assembly.
Hazardous Locations
Since the contacts are enclosed in a hermetically sealed chamber, the contact block is suitable for use in Class I and II, Division 2/Zone 2 Groups A, B, C, D, F and G hazardous locations and is listed by Underwriters Laboratories for this class of service. Complete stations as shown on page 2-23 can be used for Class I and II Division 2/Zone 2 applications. The individual components shown in the 800T and 800H sections are also suitable for Class I and II Division 2/Zone 2 locations providing they are suitably mounted by the customer in an enclosure as required for the application and by applicable codes and laws.
Class I Zone 2 protection method Ex nW IIc Temp. Code T3/T6, Demko 97.Y.122018 U applies to operators and contacts.
Per National Electrical Code: Zone 2. In Class I, Zone 2 locations, all wiring methods permitted for Class I, Division 2, Class I, Division 1 or Division 2, and Class I, Zone 0 or Zone 1 locations, including requirements for sealing, shall be permitted.
Note:Allen-Bradley Logic Reed contact blocks are also listed by Underwriters Laboratories for the Division 2/Zone 2 hazardous locations listed above.
Sealed Switch Contact Ratings
Maximum continuous current Ith 5 A. Bulletin 800T and 800H units have control circuit ratings with sealed switch contact blocks as follows:
| Max. Opertnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | B600 | 120…600 0…120 |
3600 VA 30 A |
360 VA 3 A |
| DC 300 | DC-13 | P300 | 24…300 0…24 |
138 VA 5.0 A |
|
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 2.5 A. Bulletin 800T and 800H units have control circuit ratings with sealed switch contact blocks as follows:
| Max. Opertnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 0…120 |
1800 VA 15 A |
180 VA 1.5 A |
| DC 150 | DC-13 | Q150 | 24…150 0…24 |
69 VA 2.5 A |
|
Logic Reed Contact Ratings
Maximum DC: 30V, 0.06 A Maximum AC: 150V, 0.15 A
Should only be used with resistive loads.