Bulletin 800R Hazardous Location Push Buttons

Introduction Standards Compliance Product Selection Specifications¬  Approximate Dimensions
Product Overview


Click to enlarge - 800R-2_21-1


Bulletin 800R — 30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2


Control Stations

Bulletin 800R control stations are designed for Division 2/Zone 2 hazardous locations. They consist of Bulletin 800H (Type 4/4X/13) or Bulletin 800T (Type 4/13) operators with sealed contact blocks. Bulletin 800R units are available as factory assembled stations or as components for field assembly.

Hazardous Locations

Since the contacts are enclosed in a hermetically sealed chamber, the contact block is suitable for use in Class I and II, Division 2/Zone 2 Groups A, B, C, D, F and G hazardous locations and is listed by Underwriters Laboratories for this class of service. Complete stations as shown on page 2-23 can be used for Class I and II Division 2/Zone 2 applications. The individual components shown in the 800T and 800H sections are also suitable for Class I and II Division 2/Zone 2 locations providing they are suitably mounted by the customer in an enclosure as required for the application and by applicable codes and laws.
Class I Zone 2 protection method Ex nW IIc Temp. Code T3/T6, Demko 97.Y.122018 U applies to operators and contacts.
Per National Electrical Code: Zone 2. In Class I, Zone 2 locations, all wiring methods permitted for Class I, Division 2, Class I, Division 1 or Division 2, and Class I, Zone 0 or Zone 1 locations, including requirements for sealing, shall be permitted.
Note:Allen-Bradley Logic Reed contact blocks are also listed by Underwriters Laboratories for the Division 2/Zone 2 hazardous locations listed above.


Click to enlarge - 1492-213-1_GL CAUTION:
The complete stations and individual components listed herein are NOT suitable for use in Class I and II Division 1 hazardous locations. For Class I and II Division 1 hazardous locations, order Bulletin 800H Type 7 & 9 stations and units.
  

Sealed Switch Contact Ratings

Maximum continuous current Ith 5 A. Bulletin 800T and 800H units have control circuit ratings with sealed switch contact blocks as follows:

Max. Opertnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 600 AC-15 B600 120…600
0…120
3600 VA
30 A
360 VA
3 A
DC 300 DC-13 P300 24…300
0…24
138 VA
5.0 A
  

Stackable Sealed Switch Contact Ratings

Maximum continuous current Ith 2.5 A. Bulletin 800T and 800H units have control circuit ratings with sealed switch contact blocks as follows:

Max. Opertnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 300 AC-15 C300 120…300
0…120
1800 VA
15 A
180 VA
1.5 A
DC 150 DC-13 Q150 24…150
0…24
69 VA
2.5 A
  

Logic Reed Contact Ratings

Maximum DC: 30V, 0.06 A Maximum AC: 150V, 0.15 A
Should only be used with resistive loads.