Bulletin 800H Type 7&9 Hazardous Location Push Buttons
| Product Overview |
|
Bulletin 800H/Hazardous Location Push Buttons
Build a Catalog Number
- Hazardous locations push buttons and stations
- Classes I, II & III Divisions 1 & 2
- 3/4 in. - 14 NPSM barrel
- Type 7 & 9
- Explosion-proof operators
Description
Application
When properly mounted in a Type 7 & 9 enclosure, Bulletin 800H Type 7 & 9 operators are designed to meet the requirements of the National Electrical Code for Class I, Divisions 1 & 2, Groups B, C & D Hazardous Gas; Class II, Divisions 1 & 2, Groups E, F and G Hazardous Dust; and, Class III Hazardous Fiber Locations. In addition, the single gang shallow base, Cat. No. 800H-IHZX7, meets Class I, Group B requirements. This Type 7 & 9 equipment is listed by Underwriters Laboratories, Inc.
Per National Electrical Code:
Zone 1. In Class I, Zone 1 locations, all wiring methods permitted for Class I, Division 1 locations and Class I, Zone 0 or Zone 1 locations, including requirements for sealing, shall be permitted.
Zone 2. In Class I, Zone 2 locations, all wiring methods permitted for Class I, Division 2, Class I, Division 1 or Division 2, and Class I, Zone 0 or Zone 1 locations, including requirements for sealing, shall be permitted.
Operator Construction
The Allen-Bradley line of hazardous location devices features copper-free (less than 0.4 of 1% copper content) die cast aluminum bushings and mounting rings, Type #316 stainless steel operating shafts and an O-ring seal for added corrosion resistance. These components mount into a threaded hole (3/4 in.-14 NPSM) in a suitable enclosure.
Bulletin 800H Type 7 & 9 components are available in two basic formats: standard barrel (Bulletin 800H) and long barrel (Bulletin 800HL). Standard barrel devices are suitable for mounting in panel thickness up to 1 in.; Long barrel devices are suitable for mounting in panel thickness greater than 1 in. and no thicker than 2-1/2 in. Both style operators offer a unique locking bracket which provides an anti-turn feature to guard against loosening. The mounting rings in front of the panel are knurled to provide a second means of tightening each unit into the panel.
Outdoor Use
Bulletin 800H Type 7 & 9 stations and enclosures are not configured for outdoor use as standard. A Type 3 rating is available, while maintaining Type 7 & 9 integrity of the enclosure, by the addition of a Type 3 sealing flange and an approved drain. The sealing flange shown below may be purchased as an option or as an accessory. A Type 4 rating can be achieved by using sealing nuts to seal the push button operators in addition to using the sealing flange. Sealing nuts are available as accessories (see Miscellaneous.)
Elimination of Conduit Seal Off Requirement
Bulletin 800H Type 7 & 9 units may be installed with a variety of sealing options. By utilizing either a sealing well or flanged sealing well, these stations may be installed without a conduit seal off in most applications (subject to applicable codes and laws). The sealing wells shown below may be purchased as an option or as an accessory. Sealing wells are also available with an integral Type 3 flange seal for outdoor applications.
Sealed switch contact blocks are another way to eliminate the need for conduit seal fittings in most applications (subject to applicable codes and laws). Sealed switch contact blocks may be purchased as an option on assembled stations by changing the Bulletin No. from 800H to 800R. Sealed switch contact blocks can be ordered as an accessory (see Contact Blocks∆ ). A push button station with a sealed switch contact block is shown below.
|
|
|
||
| Type 3 Flange Seal | Sealing Wells | Sealed Switch Contact Blocks |
Standards Compliance and Certifications
Standards Compliance
UL698, UL1604
CSA 22.2, No. 14
Certifications
Enclosures:
UL Listed (File No. E71673
Guide No. NNNY)
Devices:
UL Listed (File No. E10314
Guide No. NOIV)
Stations:
CSA (File No. LR11924)
Product Selection
Complete Assembled Stations (Supplied with 3/4 in. Dead End Conduit Entry — Cat. No. 800H‑1HZX7)
Momentary Contact Push Button Units, Non-Illuminated
|
|
|
||
| Flush Head Unit Cat. No. 800H-AP1A |
Extended Head Unit Cat. No. 800H-BP6B |
Mushroom Head Unit Cat. No. 800H-DP6A |
Dual Momentary Contact Push Button Units
|
Momentary Contact Push Button Units, Non-Illuminated
| 800 | H | | AP | 1 | A | |||||
| a | b | c | d | e |
|
| a | b | c | |||||
| Barrel Type | Operator Type | Color Cap | |||||
| Code | Description | Code | Description | Code | Description | ||
| H | Standard barrel length | AP | Flush head | Blank | Used only when ordering operator type DPX (Table b) | ||
| HL | Long barrel | BP | Extended head | 1 | Green | ||
| DP | Mushroom head | 2 | Black | ||||
| DPX | Mushroom head less color cap | 3 | Orange | ||||
| 4 | Grey | ||||||
| 6 | Red | ||||||
| 7 | Blue | ||||||
| 9 | Yellow | ||||||
| d | e | |||
| Special Mushroom Head | Contact Block(s)⋆ | |||
| Code | Description | Standard | ||
| Blank | No special head | Code | Description | |
| J | Jumbo mushroom head — plastic | Blank | No contacts | |
| L | Jumbo mushroom head — metal | D1 | 1 N.O. | |
| Note: Special mushroom head options only apply to mushroom head operator type DP (Table b). | D2 | 1 N.C. | ||
| D5 | 1 N.O. (Mini) | |||
| D6 | 1 N.C. (Mini) | |||
| A2 | 2 N.O. | |||
| A4 | 2 N.C. | |||
| A | 1 N.O. - 1 N.C. | |||
| B | 2 N.O. - 2 N.C. | |||
| H | 3 N.O. - 3 N.C. | |||
| C | 4 N.O. - 4 N.C. | |||
| PenTUFF (Low Voltage) | ||||
| D1V | 1 N.O. | |||
| D2V | 1 N.C. | |||
| AV | 1 N.O. - 1 N.C. | |||
| BV | 2 N.O. - 2 N.C. | |||
| HV | 3 N.O. - 3 N.C. | |||
| CV | 4 N.O. - 4 N.C. | |||
Note:Special mushroom head options only apply to mushroom head operator type DP (Table b).
Dual Push Button Units
| 800 | H | | DP | H | 16 | AAXX | 64 | |||||
| a | b | c | d | e | f |
|
| a | b | c | d | |||||||
| Barrel Type | Operator Type | Mounting | Color of Button | |||||||
| Code | Description | Code | Description | Code | Description | Code | Description | |||
| H | Standard barrel | DP | Dual push button | H | Horizontal | 16 | Left green flush/right red extended | |||
| HL | Long barrel | B | Vertical | 22 | Left black flush/right black flush | |||||
| e | f | |||||
| Contact Block(s)⋆ | Marking | |||||
| Code | Contact Arrangement | Code | Description | |||
| Left button for horizontal Top button for vertical |
Right button for horizontal Bottom button for vertical |
Left button for horizontal Top button for vertical |
Right button for horizontal Bottom button for vertical |
|||
| AAXX | 1 N.O. - 1 N.C. | 1 N.O. - 1 N.C. | Blank | No mark specified | No mark specified | |
| AAAA | 2 N.O. - 2 N.C. | 2 N.O. - 2 N.C. | 64 | START | STOP | |
| 50 | ON | OFF | ||||
| 51 | FORWARD | REVERSE | ||||
| 57 | OPEN | CLOSE | ||||
| 66 | UP | DOWN | ||||
| 99 | Marking specified | Marking specified | ||||
⋆ For sealed switch and Logic Reed contact blocks, see Modifications and Accessories.
To order with special marking, specify marking; seven characters maximum per button, single line only.
Momentary Contact Push Button Units, Illuminated
|
| Type | Lamp | Supply Voltage | Lens Color∆ | Extended Head with Guard |
| Cat. No.♣ & | ||||
| Operator only♦ | 800H-QPB00XX | |||
| Full Voltage | Incandescent | 24V AC/DC | Multi-color kit | 800H-QPB24M |
| 120V AC/DC | 800H-QPB10M | |||
| No lamp | 0…250V AC/DC | No lens | 800H-QPBN25 | |
| Universal | LED | 12…130V AC/DC | Multi-color kit | 800H-QPBH2M |
| Transformer | Incandescent | 120V AC 50/60 Hz |
Multi-color kit | 800H-PPB16M |
| LED | 800H-PPBH16M | |||
| No lamp | No lens | 800H-PPBN16 | ||
| ∆ Units ship with multi-color insert packet including amber, blue, green, red, and white. | ||||
| ♣ For long barrel versions, add an L to the cat. no. Example: Cat. No. 800HL-QPB2M. | ||||
| & Includes as standard one Cat. No. 800T-XA (1 N.O./1 N.C.) contact block. | ||||
| ♦ Operator only supplied without power module, lamp, lens cap, or contact blocks. | ||||
Potentiometer Units§
|
| Resistance | Potentiometer⋆ | Resistance | Potentiometer⋆ |
| Cat. No.♠ | Cat. No.♠ | ||
| Operator Only (without Resistive Element) |
800H-NP37 | 2.5 kW | 800H-UP19 |
| 5 kW | 800H-UP24 | ||
| 1 kW | 800H-UP13 | 10 kW | 800H-UP29 |
| ⋆ Rated for 300V AC/DC, 2W maximum. | |||
| For use with Type J potentiometers having a shaft length of 7/8 in. (22.2 mm) and a shaft diameter of 1/4 in. (6.3 mm). | |||
| § Single-turn operation with 312° rotation. | |||
| ♠ For long barrel versions, add an L to the cat. no. Example: Cat. No. 800HL-UP13. | |||
Momentary Contact Push Button Units, llluminated
| 800 | H | | PPB | H | 16 | M | ||||||
| a | b | c | d | e | f |
|
| a | b | |||
| Operator Type | Power Module Type | |||
| Code | Description | Code | Description | |
| H | Standard barrel length | PPB | Transformer (or dual input) | |
| HL | Long barrel | QPB | Full voltage/Universal | |
| c | d | |||
| Illumination Options | Voltage | |||
| Transformer | ||||
| Code | Description | Code | Description | |
| Blank | Incandescent | 16 | 120V AC 50/60 Hz | |
| H | LED | 26 | 240V AC 50/60 Hz | |
| Dual Input | 46 | 480V AC 50/60 Hz | ||
| D | Diode type, incandescent♣ | 56 | 600V AC 50/60 Hz | |
| T | Transformer — relay type, incandescent |
Full Voltage — Incandescent | ||
| TH | Transformer — relay type, LED |
24 | 24V AC/DC | |
| 10 | 120V AC/DC | |||
| 20 | 240V AC/DC | |||
| Universal — LED | ||||
| 2 | 12…130V AC/DC | |||
| Dual Input | ||||
| 16 | 120V AC | |||
| 24 | 24V AC/DC♠ | |||
| e | f | |||
| Lens Color | Contact Block(s)∇ | |||
| Code | Color | Standard | ||
| Blank | No lens, with standard contacts 1 N.O. - 1 N.C. | Code | Description | |
| X | No lens if ordering any contacts other than standard 1 N.O. - 1 N.C. | Blank | 1 N.O. - 1 N.C. | |
| M | Multi-color⋆ | X | No contacts | |
| D1 | 1 N.O. | |||
| D2 | 1 N.C. | |||
| A2 | 2 N.O. | |||
| A4 | 2 N.C. | |||
| PenTUFF (Low Voltage) | ||||
| D1V | 1 N.O. | |||
| D2V | 1 N.C. | |||
| AV | 1 N.O. - 1 N.C. | |||
♣ Diode type dual input provides circuit isolation via opposing diodes. Not recommended for use with solid-state outputs and neon indicators.
♠ Dual input diode only.
⋆ Multi-color insert packet includes amber, blue, green, red, and white.
∇ For sealed switch and Logic Reed contact blocks, see Modifications and Accessories.
2-Position Push-Pull Units, Non-Illuminated
|
3-Position Push-Pull Units, Non-Illuminated
|
2-Position Push-Pull Units, Non-Illuminated
| 800 | H | | FPX | 1 | A1 | |||||
| a | b | c | d | e |
|
| a | b | c | d | |||||||
| Barrel Type | Operator Type | Head Type | Color Cap | |||||||
| Code | Description | Code | Description | Code | Description | Code | Color | |||
| H | Standard barrel length | FPX | Push-pull unit | Blank | Mushroom head | Blank | No cap | |||
| HL | Long barrel | J | Jumbo mushroom head⋆ | 1 | Green | |||||
| 2 | Black | |||||||||
| 4 | Grey (silver) | |||||||||
| 6 | Red | |||||||||
| 7 | Blue | |||||||||
| 9 | Yellow (gold) | |||||||||
⋆ Normally closed late break contact. When button is pushed from the OUT to the IN position, the mechanical detent action of the operator occurs before electrical contacts change state. When the button is pulled from the IN to the OUT position, the electrical contacts change state before the mechanical detent occurs.
3-Position Push-Pull Units, Non-Illuminated
| 800 | H | | FPX | M | 1 | A7 | ||||||
| a | b | c | d | e | f |
|
| a | b | c | |||||
| Barrel Type | Operator Type | Head Type | |||||
| Code | Description | Code | Description | Code | Description | ||
| H | Standard barrel length | FPX | Push-pull unit | Blank | Mushroom head | ||
| HL | Long barrel | J | Jumbo mushroom head | ||||
Not valid with color cap option Blank (no cap).
2-Position Push-Pull Units, Illuminated
|
3-Position Push-Pull Units, Illuminated
|
| Type | Lamp Type | Supply Voltage | Lens Color⋆ | Cat. No. | Cat. No. |
| Operator only§ | 800H-FPXMQ00 | 800H-FPXNQ00 | |||
| Full voltage | Incandescent | 24V AC/DC | Multi-color kit | 800H-FPXMQ24MA7 | 800H-FPXNQ24MA7 |
| 120V AC/DC | 800H-FPXMQ10MA7 | 800H-FPXNQ10MA7 | |||
| No lamp | 0…250V AC/DC | No lens | 800H-FPXMQN25 | 800H-FPXNQN25 | |
| Universal | LED | 12…130V AC/DC | Multi-color kit | 800H-FPXMQH2MA7 | 800H-FPXNQH2MA7 |
| Transformer | Incandescent | 120V AC, 50/60 Hz | Multi-color kit | 800H-FPXMP16MA7 | 800H-FPXNP16MA7 |
| LED | 800H-FPXMPH16MA7 | 800H-FPXNPH16MA7 | |||
| No lamp | No lens | 800H-FPXMPN16 | 800H-FPXNPN16 | ||
| Note:X = Closed/O = Open | |||||
| ⋆ Units ship with multi-color insert packet including amber, blue, green, red, and white. | |||||
| For long barrel versions, add an L to the cat. no. Example: Cat. No. 800HL-FPXQH2MA1. | |||||
| § Operator only supplied without power module, lamp, lens cap, or contact blocks. | |||||
2- and 3-Position Push-Pull Units, Illuminated
| 800 | H | | FPX | PH | 16 | M | A1 | |||||||
| a | b | c | d | e | f | g |
|
| a | b | |||
| Barrel Type | Operator Type | |||
| Code | Description | Code | Description | |
| H | Standard barrel length | FPX | Push-pull unit | |
| HL | Long barrel | |||
| e | e (cont'd) | f | g | g (cont'd) | |||||||||
| Voltage | Voltage | Color Cap | Contact Blocks | Contact Blocks | |||||||||
| Transformer | Universal — LED | Standard | PenTUFF (Low Voltage) | ||||||||||
| Code | Description | Code | Description | Code | Color | Code | Color | Code | Description | ||||
| 16 | 120V AC 50/60 Hz | 2 | 12…130V AC/DC | Blank | No lens with no contacts | Blank | No contacts | D1V | 1 N.O. | ||||
| 26 | 240V AC 50/60 Hz | Dual Input | X | No lens with contacts | D1 | 1 N.O. | D2V | 1 N.C. | |||||
| 46 | 480V AC 50/60 Hz | 16 | 120V AC | M | Multi-color⋆ | D4 | 1 N.C.L.B.♠ | AV | 1 N.O. - 1 N.C. | ||||
| 56 | 600V AC 50/60 Hz | 24 | 24V AC/DC∇ | A | 1 N.O. - 1 N.C. | Logic Reed | |||||||
| Full Voltage — Incandescent | A1 | 1 N.O. - 1 N.C.L.B.♠ |
D1R | 1 N.O. | |||||||||
| 24 | 24V AC/DC | A2 | 2 N.O. | D2R | 1 N.C. | ||||||||
| 10 | 120V AC/DC | A5 | 2 N.C.L.B. | AR | 1 N.O. - 1 N.C. | ||||||||
| 20 | 240V AC/DC | A7 | 1 N.C. - 1 N.C.L.B.♠ |
A2R | 2 N.O. | ||||||||
| A4R | 2 N.C. | ||||||||||||
Note:Mom. - Momentary
Main. - Maintained
Table 1. Target Selection
⋆ Multi-color insert packet includes amber, blue, green, red, and white.
♣ Diode type dual input provides circuit isolation via opposing diodes. Not recommended for use with solid-state outputs and neon indicators.
♠ Normally closed late break contact. When button is pushed from the OUT to the IN position, the mechanical detent action of the operator occurs before electrical contacts change state. When the button is pulled from the IN to the OUT position, the electrical contacts change state before the mechanical detent occurs.
∇ Dual input diode only.
2-Position Selector Switch Units, Non-Illuminated
|
|
|
||
| Standard Knob Operator Cat. No. 800H-HP2KB6AXXX |
Knob Lever Operator Cat. No. 800H-HP17KB6AXXX |
Metal Wing Lever Operator Cat. No. 800H-HP11KBAXXX |
|
2-Position Selector Switch Units, Non-Illuminated
| 800 | H | | HP | A | 2 | KB6 | AXXX | |||||
| a | b | c | d | e | f |
(Knob/Wing Lever)
| 800 | H | | HP | 31 | KB6 | AXXX | ||||||
| a | b | c1 | d1 | e | f |
(Cylinder Lock)
|
| a | b | c | |||||
| Barrel Type | Number of Positions | Knob Insert Colors⋆ | |||||
| Code | Description | Code | Description | Code | Color | ||
| H | Standard barrel length | HP | 2-position | Blank | White | ||
| HL | Long barrel | X | Packet of colored inserts | ||||
| Metal Wing Lever Colors | |||||||
| Code | Color | ||||||
| A | Red | ||||||
| Blank | Grey | ||||||
| c1 | d | |||
| Key Removal Position | Operator Type and Function | |||
| Maintained | Standard Knob | |||
| Code | Operator Function | Code | Operator Function | |
| 31 | Key removal — left | 2 | Maintained | |
| 32 | Key removal — right | 4 | Spring return from left§ | |
| 33 | Key removal — both | 5 | Spring return from right | |
| Spring Return From Left | Knob Lever | |||
| Code | Operator Function | Code | Operator Function | |
| 42 | Key removal — right§ | 17 | Maintained | |
| Spring Return From Right | 18 | Spring return from left§ | ||
| Code | Operator Function | 19 | Spring return from right | |
| 48 | Key removal — left | Metal Wing Lever | ||
| Code | Operator Function | |||
| 11 | Maintained | |||
| 15 | Spring return from left§ | |||
| 16 | Spring return from right | |||
| d1 | e | |||||
| Optional Keys | Cam Option | |||||
| Code | D Series Key No. |
Code | T Series Key No. |
Code | Description | |
| Blank | D018 (std. key) |
15 | T112 | KB6 | Cam for maintained operators | |
| 03 | D020 | 16 | T115 | KL8 | Cam for spring return operators | |
| 04 | D025 | 17 | T324 | |||
| 05 | D335 | 18 | T382 | |||
| 06 | D429 | 19 | T404 | |||
| 07 | D461 | 20 | T171 | |||
| 08 | D111 | 21 | T484 | |||
| 09 | D587 | 22 | T547 | |||
| 10 | D682 | 23 | T569 | |||
| 11 | D713 | 24 | T692 | |||
| 12 | D900 | 25 | T752 | |||
| 13 | D992 | 26 | T178 | |||
| 14 | D118 | — | — | |||
⋆ Each standard and knob lever operator is factory assembled with a white insert. Other colors are available, factory assembled, if ordered in quantities of 10 or more.
One insert of each color (blue, green, orange, red, and yellow).
§ Target tables are reversed from those shown.
3-Position Selector Switch Units, Non-Illuminated
|
|
|
||
| Standard Knob Operator Cat. No. 800H-JP2KB7AXXX |
Knob Lever Operator Cat. No. 800H-JP17KB7AXXX |
Metal Wing Lever Operator Cat. No. 800H-JP11KB7AXXX |
|
3-Position Selector Switch Units, Non-Illuminated
| 800 | H | | JP | 2 | KB7 | AAXX | ||||||
| a | b | c | d | e | f |
(Knob/Wing Lever)
| 800 | H | | JP | 41 | KB7 | AAXX | ||||||
| a | b | c1 | d1 | e | f |
(Cylinder Lock)
|
| a | b | c | |||||
| Barrel Type | Number of Positions | Knob Insert Colors⋆ | |||||
| Code | Description | Code | Description | Code | Color | ||
| H | Standard barrel length | JP | 3-position | Blank | White knob insert or cylinder lock operator | ||
| HL | Long barrel | X | Packet of colored inserts | ||||
| Metal Wing Lever Colors | |||||||
| Code | Color | ||||||
| A | Red | ||||||
| Blank | Grey | ||||||
| c1 | d | |||
| Cylinder Lock Operators | Knob/Lever Type Operators | |||
| Maintained Position | Standard Knob | |||
| Code | Locking Position | Code | Operator Function | |
| 41 | Left | 2 | Maintained | |
| 42 | Center | 4 | Spring return from left | |
| 43 | Right | 5 | Spring return from right | |
| 44 | All | 91 | Spring return from both | |
| 45 | Left and center | Knob Lever | ||
| 46 | Right and left | Code | Operator Function | |
| 47 | Right and center | 17 | Maintained | |
| Spring Return from Left | 18 | Spring return from left | ||
| Code | Locking Position | 19 | Spring return from right | |
| 50 | Center | 20 | Spring return from both | |
| 52 | Right | Metal Wing Lever♣ | ||
| 51 | Right and center | Code | Operator Function | |
| Spring Return from Right | 11 | Maintained | ||
| Code | Locking Position | 15 | Spring return from left | |
| 69 | Left | 16 | Spring return from right | |
| 38 | Center | 141 | Spring return from both | |
| 73 | Left and center | |||
| Spring Return from Both | ||||
| Code | Locking Position | |||
| 631 | Center | |||
| d1 | |
| Operator Type/Function§ | |
| Standard Knob | |
| Code | Key No. |
| Blank | D018 (standard key) |
| Note: Refer to 2-Position Selector Switch Units, Non-Illuminated for additional key option codes. | |
| e | f | |||
| Cam Option | Contact Block Option | |||
| Code | Description | Code | Description | |
| KB7 | Standard cam KB7 | Blank | No contacts | |
| KA1 | Cam KA1 | AXXX | 2 contact targets for a given cam as shown in the W (white side) column of Table 5. | |
| KA7 | Cam KA7 | AAXX | 2 contact targets for a given cam as shown in the W (white side) column of Table 1 and 2 contact targets for the same cam as shown in the B (black side) column of Table 5. (1-800T-XA Contact Block per side. 2 Contact Blocks total.) | |
| Note: For additional Cam descriptions, see Table 5. | AAAA | 4 contact targets for a given cam as shown in the W (white side) column of Table 5 and 4 contact targets for the same cam as shown in the B (black side) column of Table 5. (2-800T-XA Contact Blocks per side. 4 Contact Blocks total.) | ||
Table 5. Cam and Contact Block Functionality Table
Note:X = Closed/O = Open
⋆ Each standard and knob lever operator is factory assembled with a white insert. Other colors available, factory assembled, if ordered in quantities of 10 or more.
One insert of each color (blue, green, orange, red, and yellow).
§ For additional keys, see 2-Position Selector Switch Units, Non-Illuminated.
♣ Wing levers are not suitable with KE7 cam code.
4-Position Selector Switch Units, Non-Illuminated
|
|
|
||
| Standard Knob Operator Cat. No. 800H-NP2KF4AAXX |
Knob Lever Operator Cat. No. 800H-NP17KF4AAXX |
Metal Wing Lever Operator Cat. No. 800H-NP11KF4AAXX |
|
4-Position Selector Switch Units, Non-Illuminated
| 800 | H | | NP | 2 | KF4 | AAXX | ||||||
| a | b | c | d | e | f |
(Knob/Wing Lever)
| 800 | H | | NP | 31 | KF4 | AAXX | ||||||
| a | b | c1 | d1 | e | f |
(Cylinder Lock)
|
| a | b | c | |||||
| Barrel Type | Number of Positions | Knob Insert Colors⋆ | |||||
| Code | Description | Code | Description | Code | Color | ||
| H | Standard barrel length | NP | 4-position | Blank | White | ||
| HL | Long barrel | X | Packet of colored inserts | ||||
| Metal Wing Lever Colors | |||||||
| Code | Color | ||||||
| A | Red | ||||||
| Blank | Grey | ||||||
| c1 | d | |||
| Key Removal Position and Operator Function |
Operator Function and Knob Type |
|||
| Maintained | Standard Knob | |||
| Code | Operator Function | Code | Operator Function | |
| 31 | Key removal position 1 | 2 | Maintained | |
| 32 | Key removal position 2 | 3 | Spring return from position 1 to position 2 | |
| 33 | Key removal position 3 | 9 | Spring return from position 4 to position 3 | |
| 34 | Key removal position 4 | Knob Lever | ||
| 61 | Key removal all positions | Code | Operator Function | |
| Spring Return From Position 1 to Position 2 |
17 | Maintained | ||
| Code | Operator Function | 29 | Spring return from position 1 to position 2 | |
| 132 | Key removal position 2 | 30 | Spring return from position 4 to position 3 | |
| 133 | Key removal position 3 | Metal Wing Lever | ||
| 134 | Key removal position 4 | Code | Operator Function | |
| 154 | Key removal positions 2, 3, and 4 | 11 | Maintained | |
| Spring Return From Position 1 to Position 2 |
13 | Spring return from position 1 to position 2 | ||
| Code | Operator Function | 14 | Spring return from position 4 to position 3 | |
| 231 | Key removal position 1 | |||
| 232 | Key removal position 2 | |||
| 233 | Key removal position 3 | |||
| 251 | Key removal positions 1, 2, and 3 | |||
| d1 | e | f | |||||
| Optional Keys♣ | Cam Option | Contact Block Option | |||||
| D Series | Code | Description | Code | Description | |||
| Code | Description | KF4 | F cam (standard) | Blank | No contacts | ||
| Blank | D018 (standard key) | KG4 | G cam | AAXX | Two contact targets for a given cam as shown in the W (white side) column of Table 1 and 2 contact targets for the same cam as shown in the B (black side) column of Table 1. (One Cat. No. 800T-XA contact block per side. Two contact blocks total) | ||
| KK4 | K cam | AAAA | Four contact targets for a given cam as shown in the W (white side) column of Table 1 and 4 contact targets for the same cam as shown in the B (black side) column of Table 1. (Two Cat. No. 800T-XA contact blocks per side. Four contact blocks total.) | ||||
| KM4 | M cam | PenTUFF (Low Voltage) | |||||
| KP4 | P cam | FFXX | Two contact targets for a given cam as shown in the W (white side) column of Table 1 and 2 contact targets for the same cam as shown in the B (black side) column of Table 1. (One Cat. No. 800T-XAV contact block per side. Two contact blocks total) | ||||
| KH4 | Overlapping cam | FFFF | Four contact targets for a given cam as shown in the W (white side) column of Table 1 and 4 contact targets for the same cam as shown in the B (black side) column of Table 1. (Two Cat. No. 800T-XAV contact blocks per side. Four contact blocks total.) | ||||
Table 1. Selector Switch Cam Targets
Pilot Light Units
|
|
|
||
| Transformer Type Pilot Light Cat. No. 800H-PP16M |
Push-to-Test Pilot Light Cat. No. 800H-PPT16M |
Pigtail Pilot Light Cat. No. 800H-LP24M |
| Type | Lamp Type | Supply Voltage | Lens Color⋆ | Pilot Light | Push-to-Test | Pigtail |
| Cat. No. | Cat. No. § | Cat. No. ♣ | ||||
| Operator only∆ | 800H-QPN00 | 800H-QPB00XX | — | |||
| Full voltage | Incandescent | 24V AC/DC | Multi-color kit | 800H-QP24M | 800H-QPT24M | 800H-LP24M |
| 120V AC/DC | 800H-QP10M | 800H-QPT10M | 800H-LP10M | |||
| No lamp | 0…250V AC/DC | No lens | 800H-QPN25 | 800H-QPTN25 | 800H-LPN25 | |
| LED | 24V AC/DC | Multi-color kit | — | — | 800H-LPH24M | |
| 120V AC | — | — | 800H-LPH10M | |||
| Universal | LED | 12…130V AC/DC | Multi-color kit | 800H-QPH2M | 800H-QPTH2M | — |
| Transformer | Incandescent | 120V AC, 50/60 Hz | Multi-color kit | 800H-PP16M | 800H-PPT16M | — |
| LED | 800H-PPH16M | 800H-PPTH16M | — | |||
| ⋆ Units ship with multi-color insert packet including amber, blue, green, red, and white. | ||||||
| For long barrel versions, add an L to the cat. no. Example: Cat. No. 800HL-QPH2M | ||||||
| § Includes one standard Cat. No. 800T-XA (1 N.O./1 N.C.) contact block. | ||||||
| ♣ Pigtail length is 7 in. | ||||||
| ∆ Operator only supplied without power module, lamp, lens cap, or contact blocks. | ||||||
Pilot Light Units
| 800 | H | | PP | T | 16 | M | ||||||
| a | b | c | d | e | f |
|
| a | b | c | |||||
| Barrel Type | Power Module Type | Lamp Test Options | |||||
| Code | Description | Code | Description | Code | Description | ||
| H | Standard barrel length | PP | Transformer (or dual input) |
Blank | No test option | ||
| HL | Long barrel | QP | Full voltage/Universal | T | Push-to-test | ||
| LP | Pigtail — Full voltage | D | Dual input — diode§ | ||||
| LPK | Pigtail — full voltage (for dual push buttons) |
DT | Dual input — transformer relay§ |
||||
| d | e | e (cont'd) | f | |||||||
| Illumination Option | Voltage | Voltage | Lens Color | |||||||
| Code | Description | Transformer | Full Voltage — LED | |||||||
| Blank | Incandescent | Code | Description | 2 | 12…130V AC/DC | Code | Color | |||
| H | LED∆ | 16 | 120V AC, 50/60 Hz | Dual Input | Blank | No lens with no contacts | ||||
| 26 | 240V AC, 50/60 Hz | 16 | 120V AC | M | Multi-color⋆ | |||||
| 46 | 480V AC, 50/60 Hz | 24 | 24V AC/DC∇ | |||||||
| 56 | 600V AC, 50/60 Hz | Pigtail | ||||||||
| Full Voltage — Incandescent | 24 | 24V AC/DC | ||||||||
| 24 | 24V AC/DC | 10 | 120V AC/DC | |||||||
| 10 | 120V AC/DC | 20 | 240V AC/DC | |||||||
| 20 | 240V AC/DC | |||||||||
Note: Push-to-test pilot light is supplied with a factory jumpered Cat. No. 800T-XA, 1 N.O/1 N.C contact block.
⋆ Multi-color insert packet includes amber, blue, green, red, and white
Lamp test options is not available with pigtail.
§ Only available with power module type code PP.
∆ LED illumination option is not available with diode type dual input lamp test options.
∇ Dual input diode only.
Product Selection for Stations
Ordering Information for Stations
Stations
Bulletin 800H Type 7 & 9 stations are available as factory assembled or as components for field assembly.
Factory-Assembled Stations
Bulletin 800H Type 7 & 9 control stations are designed to meet the requirements of the National Electrical Code. These stations are listed by Underwriters Laboratories, Inc. for Class I, Divisions 1 & 2, Groups C & D Hazardous Gases or Vapors, Class II, Divisions 1 & 2, Groups E, F & G Hazardous Dust and Class III Hazardous Fiber Locations. In addition the single gang shallow base, Cat. No. 800H‑IHZX7, meets Class I, Group B requirements as defined in the National Electrical Code.
Factory-assembled stations may be ordered in three ways:
- Standard, factory-assembled stations listed on Complete Assembled Stations (Supplied with 3/4 in. Dead End Conduit Entry — Cat. No. 800H‑1HZX7).
- Custom, factory-assembled stations can be ordered by following the instructions listed on this page.
Components for Field Assembled Stations
Eight-gang maximum⋆ . These 2- and 3-gang modules may be assembled into the multi-gang stations by installing a coupler kit between the enclosures. These separate bases, covers, or bases with covers are Underwriters Laboratories, Inc. listed when properly assembled. These enclosures meet the requirements of Class I, Division 1 & 2, Groups C & D, Class II, Divisions 1 & 2, Groups E, F & G, and Class III hazardous locations as defined in the National Electrical Code. Bulletin 800H Type 7 & 9 components are designed for these modular enclosures and are UL Listed for this purpose.
Note: Components may be assembled as multi-gang units up to an eight-gang maximum⋆ .
To select components for field assembly, follow the instructions for ordering a custom-built station.
Instructions for Ordering Custom-Built Stations
1. Select operators required from Complete Assembled Stations (Supplied with 3/4 in. Dead End Conduit Entry — Cat. No. 800H‑1HZX7). (If lever type, select covers from Covers, Lever Type Actuator and go to Step 3).
2. Select covers based on mounting requirements on Covers, Lever Type Actuator.
3. Select an assembled base from Assembled Bases (for Field Assembly and Custom Stations) in accordance with the number of covers selected in Step 2.
4. Select legend plates from Legend Plates…Legend Plates, Continued (and accessories, if required, from pages Modifications and Accessories…Locking Attachments).
5. If a particular sequence of operators or mounting orientation (vertical versus horizontal) is required, include a rough sketch.
Station Design Guidelines
(Also see Applicable Codes and Standards)
1. Push-to-test pilot lights, illuminated push buttons, push-to-pull units, 4-position selector switches, and all operators with two contact blocks fastened along side one another or with a power module and contact block along side one another must be installed in a single hole cover.
2. Dual push button units may only be installed in a single-hole cover or the specially designed two-hole cover (Cat. No. 800H-NP33), which can accommodate the dual push button and the special pigtail pilot light (Cat. No. 800H-LPK10R).
3. When two components are installed in one cover, contact blocks are restricted to one side of the operator. Contact blocks of each operator must face each other.
4. One level of contact blocks is maximum in a shallow base or deep base when used with a sealing well. Contact blocks, except sealed switch type, may be mounted two deep in other bases.
5. If sealed switch contact blocks or a sealing well are used, a deep enclosure is required.
6. a. START push buttons should be green or black flush, installed to the left or above STOP push buttons.
b. EMERGENCY STOP push buttons should be a red mushroom.
c. STOP push buttons should be red extended, installed to the right or below START push button.
d. STOP push buttons should be installed in the last position (bottom or right) of each unit when required.
e. Pilot lights should be installed in the first position (top or left side) of each unit when required.
|
Design Guideline #1
Push-to-test pilot lights, illuminated push buttons, push-pull units, 4-position selector switches, all operators with two contact blocks fastened along side one another or with a power module and contact block along side one another must be installed in a single hole cover.
|
Design Guideline #2
Dual push button units may only be installed in a single hole cover or the specially designed two hole cover (Cat. No. 800H‑NP33), which can accommodate the dual push button and the special pigtail pilot light (Cat. No. 800H‑LPK10R).
|
Design Guideline #3
When two components are installed in one cover, contact blocks are restricted to one side of the operator. Contact blocks of each operator must face each other.
Design Guideline #4
One level of contact blocks is maximum in a shallow base or deep base when used with a sealing well. Contact blocks, except sealed switch type, may be mounted two deep in other bases.
⋆ Flange width is designed to comply with Underwriters Laboratories standards to enclosures with an internal free volume of up to 300 cubic inches (a maximum 8-gang assembly).
Product Selection
Covers, Lever Type Actuator
Note:Lever type covers are furnished without contact blocks. Legend plate for half lever is STOP; full lever momentary and maintained is a START-STOP. To order without legend plate, add suffix X to the cat. no.
|
|
|
| Half Lever | Double Lever Momentary |
| Half Lever | Double Lever Momentary | Double Lever Maintained | Double Lever Momentary/Maintained⋆ |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. |
| 800H-NP14 | 800H-NP15 | 800H-NP16 | 800H-NP34 |
| ⋆ A normally open circuit configuration is recommended for use behind this momentary lever and a late break normally closed circuit configuration is required for use behind the maintained lever to achieve proper functioning of the device. | |||
Covers, Component Type Button
|
|
|
|
| Blank | One Hole | Two Hole§ | Two Hole Special♣ |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. |
| 800H-NP32 | 800H-NP30 | 800H-NP31 | 800H-NP33 |
One-hole covers use a jumbo legend plate only.
§ Two-hole covers use a standard legend plate only.
♣ This special two-hole cover can accommodate the pigtail pilot light (Bulletin 800H-LPK10 series), the dual push button or any non-illuminated unit. Legend plates (Cat. No. 800H-Y140J green and red split-field) and (Cat. No. 800H-Y141J grey full field), are the only legend plates suitable for use with this cover.
Assembled Bases (for Field Assembly and Custom Stations)
Enclosure Covers — See enclosure cover tables for a complete listing of covers for these bases.
Special Conduit Entries — For conduit entries not listed, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
|
|
|
||
| 1-Gang Shallow⋆ | 1-Gang Deep | 2-Gang Horizontal |
| Conduit Entry | Cat. No. | Cat. No. | Cat. No. |
| 3/4 in. Dead End | 800H-1HZX7 | 800H-1HVX7 | — |
| 3/4 in. Feed Through | — | 800H-1HVX7M1 | — |
| 1 in. Dead End | — | 800H-1HVX7M2 | 800H-2HHX7 |
| 1 in. Feed Through | — | 800H-1HVX7M3 | — |
| ⋆ Shallow base cannot accommodate sealing well, sealed switched contact blocks, or stacked contact blocks. Shallow base rated for Group B. | |||
| Deep base can accommodate sealing well, sealed switch contact blocks, or up to 2 deep standard contact blocks. | |||
|
|
|
||
| 2-Gang Vertical | 3-Gang Vertical | 4-Gang |
| Conduit Entry | Cat. No. | Cat. No. | Cat. No. |
| 1 in. Feed Through | 800H-2HYX7 | 800H-3HYX7 | 800H-4HVX7 |
| Deep base can accommodate sealing well, sealed switch contact blocks, or up to 2 deep standard contact blocks. | |||
|
|
|
| 6-Gang | 8-Gang |
| Conduit Entry | Cat. No. | Cat. No. |
| 1 in. Feed Through | 800H-6HVX7 | 800H-8HVX7 |
| Deep base can accommodate sealing well, sealed switch contact blocks, or up to 2 deep standard contact blocks. | ||
Bases for Multi-Gang Stations
|
|
|
| Conduit Sizes | Cat. No. | Cat. No. | Cat. No. |
| 3/4 in. Feed Through | 800H-NP40C | 800H-NP41C | — |
| 1 in. Feed Through | 800H-NP40D | 800H-NP41D | — |
| 3/4 in. Dead End | — | — | 800H-NP42A |
| 1 in. Dead End | — | — | 800H-NP42B |
|
|
|
|
| Conduit Sizes | Cat. No. | Cat. No. | Cat. No. | Cat. No. |
| 3/4 in. Dead End | 800H-NP43A | 800H-NP44A | — | 800H-NP46A |
| 1 in. Dead End | 800H-NP43B | 800H-NP44B | — | 800H-NP46B |
| None | — | — | 800H-NP45 | — |
Example:
7-gang base with 1 in. through-feed conduit consists of:
3-Cat. No. 800H-NP42B
1-Cat. No. 800H-NP43B
1-Cat. No. 800H-NP44B
1-Cat. No. 800H-NP45
1-Cat. No. 800H-NP46B
6-Cat. No. 800H-NP7
Plus up to four 1 in. plugs (Cat. No. 800H-NP11) to close unused conduit openings.
Caution: Do not assemble more than eight enclosure gangs together, to avoid exceeding the internal volume for which the flame path of these enclosures is designed.
|
⋆ When coupling modular enclosures together, a coupler kit (Cat. No. 800H-NP7) is required between enclosures.
§ 1 in. conduit through-feed (all gangs).
Modifications and Accessories
Contact Blocks∆
Packaged in kit form for field installation. All necessary mounting hardware is provided with each contact block kit. Contact ratings are listed on Specifications⋆ .
Note:It is not recommended to mount more than four contact blocks on any one unit (maximum two blocks deep). Sealed switch contact blocks are limited to two blocks per unit maximum.
|
|
|
||
| Shallow Block | Mini Block | PenTUFF (Low Voltage) Contact Block |
| Contact Type | Shallow Block⋆ § | Mini Block⋆ § | PenTUFF (Low Voltage) Block⋆ § |
| Cat. No. | Cat. No. | Cat. No. | |
| 1 N.O. | 800T-XD1 | 800T-XD5 | 800T-XD1V |
| 1 N.C. | 800T-XD2 | 800T-XD6 | 800T-XD2V |
| 1 N.O.E.M. | 800T-XD3 | — | 800T-XD3V |
| 1 N.C.L.B. | 800T-XD4 | — | 800T-XD4V |
| 1 N.O. - N.C. | 800T-XA | — | 800T-XAV |
| 2 N.O. | 800T-XA2 | — | — |
| 2 N.C. | 800T-XA4 | — | — |
| 1 N.C.L.B. - 1 N.O. | 800T-XA1 | — | — |
| 1 N.C.L.B. - 1 N.C. | 800T-XA7 | — | — |
| ⋆ To determine if a conduit seal-off is necessary, see Miscellaneous for sealing well information. | |||
| Specify Bulletin 800TC for finger-safe contact blocks. Example: Cat. No. 800TC-XA. | |||
| § Contact blocks with normally closed contacts meet direct drive positive opening standard requirements. | |||
|
|
|
||
| Logic Reed Block | Sealed Switch Block | Stackable Sealed Switch Block |
| Contact Type | Logic Reed Block♣ | Sealed Switch Block♣ | Stackable Sealed Switch Block♣ |
| Cat. No. | Cat. No. | Cat. No. | |
| 1 N.O. | 800T-XD1R | 800T-XD1P | 800T-XD1Y |
| 1 N.C. | 800T-XD2R | 800T-XD2P | 800T-XD2Y |
| 1 N.O. - 1 N.C. | 800T-XAR | 800T-XAP | 800T-XAY |
| 2 N.O. | 800T-XA2R | — | 800T-XA2Y |
| 2 N.C. | 800T-XA4R | — | 800T-XA4Y |
| ♣ To determine if a conduit seal-off is necessary, see Miscellaneous for sealing well information. | |||
| ∆ Refer to 800T/H section, Contact Blocks, for additional contact blocks and accessories. | |||
Replacement Color Caps (Illuminated)
|
|
|
|
|||
| Pilot Light Cat. No. 800H-N104M |
Push-to-Test Pilot Light Cat. No. 800H-N105M |
Illuminated Push Button Cat. No. 800H-N106M |
Illuminated Push-Pull Cat. No. 800H-NP50M |
| Color | Pilot Light | Push-to-Test Pilot Light | Illuminated Push Button | Illuminated Push-Pull |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| Multi-color kit | 800H-N104M | 800H-N105M | 800H-N106M | 800H-NP50M |
Replacement Color Caps (Non-Illuminated)
| Color | Momentary Mushroom — Standard (Plastic) |
Momentary Mushroom — Jumbo (Metal) ⋆ |
Push-Pull Standard (Metal) |
Push-Pull Jumbo (Metal) |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| Red | 800T-N246R | 800T-N248R | 800H-NP51A | 800H-NP52A |
| Green | 800T-N246G | 800T-N248G | 800H-NP51B | 800H-NP52B |
| Blue | 800T-N246BL | 800T-N248BL | 800H-NP51C | 800H-NP52C |
| Yellow | 800T-N246Y | 800T-N248Y | 800H-NP51E | 800H-NP52E |
| Black | 800T-N246B | 800T-N248B | 800H-NP51H | 800H-NP52H |
| Grey | 800T-N246GR | 800T-N248GR | 800H-NP51G | — |
| Natural | — | 800T-N248 | — | — |
| ⋆ To order plastic jumbo mushroom caps, replace 248 with 247. Plastic not available in natural color. Example: Cat. No. 800T-N248R becomes Cat. No. 800T-N247R. |
||||
Replacement Knobs and Dual Push Button Assembly
|
|
|
|
|||
| Standard Knob Cat. No. 800H-N130F |
Knob Lever Cat. No. 800H-131F |
Wing Lever Cat. No. 800H-N138 |
Dual Push Button Cat. No. 800H-NP39 |
| Color | Standard Knob | Knob Lever | Wing Lever | Dual Push Button |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| White | 800H-N130F | 800H-N131F | — | — |
| Kit (Complete)§ | 800H-N130 | 800H-N131 | — | — |
| Grey | — | — | 800H-N138 | — |
| Red | — | — | 800H-N138A | — |
| Green Red | — | — | — | 800H-NP39 |
| Standard finish is grey. | ||||
| § Kit includes knob and packet of inserts (Cat. No. 800T-N123). Refer to color insert kits on Miscellaneous. | ||||
Boots—Non-Illuminated Momentary Contact Push Buttons Units
Note:For Bul. 800H/HL Type 7&9 operators, order one adapter and one boot per operator.
Adapters
| Push Button Type | Cat. No. |
| Flush head | 800H-NPAF |
| Extended head | 800H-NPAE |
Boots
Boots supplied with control stations and components are made of a chlorosulfonated polyethylene material with stainless steel insert ring. To order boots with silicone, urethane, or ethylene propylene material, see the table below. Material application information shown below.
|
| Insert Material | Boot Color | Material | |||
| Chlorosulfonated Polyethylene§ | Silicone § | Urethane § | Ethylene Propylene § |
||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||
| Stainless steel♣ | Red | 800H-N5A | 800H-N101R | 800H-N100R | 800H-N103R |
| Green | 800H-N5B | 800H-N101G | 800H-N100G | 800H-N103G | |
| Black | 800H-N5H | 800H-N101B | 800H-N100B | 800H-N103B | |
| Yellow | 800H-N5E | 800H-N101Y | 800H-N100Y | — | |
| Blue | 800H-N5C | 800H-N101BL | 800H-N100BL | — | |
| May be added to flush or extended head push button units to protect against foreign materials reaching the opening between the button and the locking ring. | |||||
| ♣ Series B boots incorporate a stainless steel insert as standard. | |||||
| § Dots printed on the inside of the boot identify the boot material. | |||||
Booted Knobs
|
|
|
| Booted Standard Knob Selector Switch Cat. No. 800H-NP5 |
Booted Knob Lever Selector Switch Cat. No. 800H-NPE5 |
| Switch Type | Boot Material⋆ | |||
| Chlorosulfonated Polyethylene | Silicone | Urethane | Ethylene Propylene |
|
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| Standard Knob Selector Switch | 800H-NP5 | 800H-NP101 | 800H-NP100 | 800H-NP103 |
| Knob Lever Selector Switch | 800H-NPE5 | 800H-NPE101 | 800H-NPE100 | 800H-NPE103 |
| ⋆ Dots printed on the inside of the boot identify the boot material. | ||||
| Includes color insert kit. | ||||
Push Button Guards and Mushroom Push Button Guards
|
|
|
|
|||
| Cat. No. 800H-NP19 | Cat. No. 800H-NP13 | Cat. No. 800H-NP9 | Cat. No. 800H-NP12 |
| Push Buttons, Pilot Lights and Push-to-Test |
Extra Long Guard (1 in.) for Push Button |
Mushroom | Jumbo Mushroom |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. |
| 800H-NP19 | 800H-NP13 | 800H-NP9 | 800H-NP12 |
Protective Rings
|
|
|
| Protective Ring for 2-Position Push-Pull Cat. No. 800H-NP40 |
Jumbo Protective Ring for 2-Position Push-Pull Cat. No. 800H-NP40J |
| Protective Ring for Push-Pull Devices | ||
| Description | Type | Cat. No. |
| Protective ring for Bul. 800H 2-position non-illuminated push-pull operators. Often used to avoid unintentional tripping of E-stop operators. Available for standard size button (40 mm) or for jumbo button (60 mm). | For standard size button | 800H-NP40 |
| For jumbo size button | 800H-NP40J | |
General Accessories
Plugs
Locking Attachments
Locking Attachments
Miscellaneous
| Description | Style | No. of Wires | Cat. No. | ||
|
|
Sealing Well with or without Integral Type 3 Flange Seal These sealing wells can only be used with bases having 1 in. conduit entries. They reduce costs usually necessary with other conduit seal fittings for most installations (subject to applicable codes and laws) while maintaining Type 7 and 9 integrity. When using a sealing well with integral flange seal for Type 3 outdoor applications, an approved drain fitting must be provided. (Refer to National Electrical Code.) |
With Integral Flange Seal, Type 3, 7, and 9 | 2 | 800H-NPRD90 |
| 4 | 800H-NPRD91 | ||||
| 6 | 800H-NPRD92 | ||||
| 8 | 800H-NPRD93 | ||||
| Without Integral Flange Seal, Type 7 and 9 | 2 | 800H-NPD90 | |||
| 4 | 800H-NPD91 | ||||
| Cat. No. 800H‑NPRD91 | Cat. No. 800H‑NPD93 | 6 | 800H-NPD92 | ||
| 8 | 800H-NPD93 | ||||
| Description | Style | Cat. No. | |||
|
|
Type 3 Flange Seal This seal provides a Type 3 rating while maintaining Type 7 and 9 integrity. An approved drain (see listing) is required for condensation when using this option (refer to National Electrical Code). For a Type 4 rating, use sealing nuts to seal the push button operators in addition to using the flange seal. Sealing kit is comprised of flange seal and sealing nut. They are used with the Allen-Bradley enclosures listed on Complete Assembled Stations (Supplied with 3/4 in. Dead End Conduit Entry — Cat. No. 800H‑1HZX7) for outdoor applications. |
Flange Seal | 800H-NP20 | ||
| Drain for 3/4 in. Conduit Opening | 800H-NP21 | ||||
| Cat. No. 800H-NP20 | Drain for 1 in. Conduit Opening | 800H-NP22 | |||
|
|
Type 4 Sealing Nut | 800H-N479 | |||
| Cat. No. 800H-NP21 | Type 4 Sealing Kit | 800H-N479F | |||
| Description | Color | Cat. No. | |||
|
Color Insert Kit These color insert kits are used with illuminated push buttons, pilot lights, push-pull, and push-to-test push buttons (order quantity of 1 to receive kit of 5 inserts). |
Red | 800H-NP23R | ||
| Green | 800H-NP23G | ||||
| Amber | 800H-NP23A | ||||
| Blue | 800H-NP23B | ||||
| White | 800H-NP23W | ||||
| Cat. No. 800H-NP23R | One of each color | 800H-NP23 | |||
Replacement Lamps
Pilot Lights, Illuminated Push Buttons, Illuminated Push-Pull, Illuminated Push-Pull/Twist to Release, and Illuminated Selector Switches
Legacy LED Lamps∆
Legend Plates
|
|
|
|
|
Blank Legend Plates
| Legend Plate Color | Lever Style | Standard Size | Jumbo Size | Special Jumbo Size |
| Use 1 lever style legend with each lever type cover (Cat. Nos. 800H-NP14, -NP15, -NP16 or -NP34) |
Use 2 standard size legends with each standard 2 hole cover (Cat. No. 800H-NP31) |
Use 1 jumbo size legend with each standard 1 hole cover (Cat. No. 800H-NP30) |
Use 1 special jumbo legend with each special 2 hole cover (Cat. No. 800H-NP33) Ex: Dual Push Button/ Pigtail Pilot Light |
|
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| Grey | — | 800H-Y59 | 800H-Y59J | 800H-Y141J |
| Red | — | 800H-Y121 | 800H-Y121J | — |
| Green | — | 800H-Y136 | 800H-Y136J | — |
| Yellow | — | 800H-Y700 | 800H-Y700J | — |
| Top Grey — Bottom Grey | 800H-Y222 | — | — | — |
| Top Grey — Bottom Red | 800H-Y223 | — | — | — |
| Left Green — Right Red | — | — | — | 800H-Y140J |
| Grey with Potentiometer Graduations | — | 800H-Y109 | 800H-Y109J | — |
Custom Legend Plates
| Legend Plate Color | Lever Style | Standard Size | Jumbo Size | Special Jumbo Size | ||||
| Use 1 lever style legend with each lever type cover (Cat. Nos. 800H-NP14, -NP15, -NP16 or -NP34) |
Use 2 standard size legends with each standard 2 hole cover (Cat. No. 800H-NP31) |
Use 1 jumbo size legend with each standard 1 hole cover (Cat. No. 800H-NP30) |
Use 1 special jumbo legend with each special 2 hole cover (Cat. No. 800H-NP33) Ex: Dual Push Button/ Pigtail Pilot Light |
|||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |||||
| Grey | — | ⋆ | 800H-Y59E | ⋆ | 800H-Y59JE | ⋆ | 800H-Y141JE | |
| Red | — | ⋆ | 800H-Y121E | ⋆ | 800H-Y121JE | — | ||
| Green | — | ⋆ | 800H-Y136E | ⋆ | 800H-Y136JE | — | ||
| Yellow | — | 800H-Y700E | 800H-Y700JE | — | ||||
| Top Grey — Bottom Grey | ⋆ | 800H-Y222E | — | — | — | |||
| Top Grey — Bottom Red | ⋆ | 800H-Y223E | — | — | — | |||
| Left Green — Right Red | — | — | — | ⋆ | 800H-Y140JE | |||
| Grey with Potentiometer Graduations | — | ⋆ | 800H-Y109E | ⋆ | 800H-Y109JE | — | ||
| ⋆ Horizontally mounted engraved legend plates (with standard or custom marking) are available. Add the letter H after the Y in the cat. no. Example: Cat. No. 800H-Y222E becomes 800H-YH222E. |
||||||||
Lever Style Legend Plates with Standard Markings
|
| Legend Marking | Cat. No. | Legend Marking | Cat. No. |
| Upper/Lower | Upper/Lower | ||
| HAND AUTO |
800H-Y228 | OPEN CLOSE |
800H-Y205 |
| JOG RUN |
800H-Y227 | RUN STOP (Red) |
800H-Y226 |
| JOG STOP (Red) |
800H-Y206 | START STOP (Red) |
800H-Y200 |
| ON OFF |
800H-Y225 | — | — |
Legend Plates, Continued
Legend Plates with Standard Markings
|
|
|
| Legend Marking | Standard Size | Jumbo Size | Legend Marking | Standard Size | Jumbo Size |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||
| AUTO-OFF-HAND | 800H-Y1 | 800H-Y1J | ON | 800H-Y30 | 800H-Y30J |
| AUTO-MAN-HAND | 800H-Y125 | 800H-Y125J | OPEN | 800H-Y31 | 800H-Y31J |
| CLOSE | 800H-Y2 | 800H-Y2J | OPEN-CLOSE | 800H-Y32 | 800H-Y32J |
| CYCLE START | 800H-Y62 | 800H-Y62J | OPEN-OFF-CLOSE | 800H-Y33 | 800H-Y33J |
| DOWN | 800H-Y3 | 800H-Y3J | OUT | 800H-Y34 | — |
| EMERG. STOP (Red) | 800H-Y4 | 800H-Y4J | PUSH TO STOP-PULL TO START | 800H-Y118 | 800H-Y118J |
| FAST | 800H-Y5 | 800H-Y5J | POWER ON | 800H-Y139 | 800H-Y139J |
| FEED START | 800H-Y66 | 800H-Y66J | RAISE | 800H-Y35 | 800H-Y35J |
| FEED STOP | 800H-Y67 | 800H-Y67J | RAISE-LOWER | 800H-Y36 | 800H-Y36J |
| FOR.-REV. | 800H-Y6 | 800H-Y6J | RAISE-OFF-LOWER | 800H-Y37 | 800H-Y37J |
| FOR.-OFF-REV. | 800H-Y7 | 800H-Y7J | RESET | 800H-Y38 | 800H-Y38J |
| FORWARD | 800H-Y8 | 800H-Y8J | REVERSE | 800H-Y39 | 800H-Y39J |
| FOURTH SPEED | 800H-Y124 | 800H-Y124J | RUN | 800H-Y40 | 800H-Y40J |
| FULL SPEED | 800H-Y9 | 800H-Y9J | RUN-INCH | 800H-Y134 | 800H-Y134J |
| HAND-AUTO | 800H-Y10 | 800H-Y10J | RUN-JOG | 800H-Y41 | 800H-Y41J |
| HAND-OFF-AUTO | 800H-Y11 | 800H-Y11J | SAFE-RUN | 800H-Y42 | 800H-Y42J |
| HIGH | 800H-Y12 | 800H-Y12J | SECOND SPEED | 800H-Y43 | 800H-Y43J |
| HIGH-LOW | 800H-Y13 | 800H-Y13J | SLOW | 800H-Y44 | 800H-Y44J |
| HIGH-OFF-LOW | 800H-Y14 | 800H-Y14J | SLOW-FAST | 800H-Y45 | 800H-Y45J |
| IN | 800H-Y15 | 800H-Y15J | SLOW-OFF-FAST | 800H-Y46 | 800H-Y46J |
| INCH | 800H-Y16 | 800H-Y16J | SPEED⋆ | 800H-Y108 | 800H-Y108J |
| JOG | 800H-Y17 | 800H-Y17J | START (Green) | 800H-Y47 | 800H-Y47J |
| JOG FORWARD | 800H-Y18 | 800H-Y18J | START-JOG | 800H-Y48 | 800H-Y48J |
| JOG REVERSE | 800H-Y19 | 800H-Y19J | START-STOP | 800H-Y49 | 800H-Y49J |
| JOG-RUN | 800H-Y20 | 800H-Y20J | STOP (Red) | 800H-Y50 | 800H-Y50J |
| JOG-SAFE-RUN | 800H-Y22 | 800H-Y22J | STOP-START | 800H-Y51 | 800H-Y51J |
| JOG-STOP-RUN | 800H-Y21 | 800H-Y21J | SUMMER-OFF-WINTER | 800H-Y53 | 800H-Y53J |
| LEFT-RIGHT | 800H-Y23 | 800H-Y23J | SUMMER-WINTER | 800H-Y52 | 800H-Y52J |
| LOW | 800H-Y24 | 800H-Y24J | TEST | 800H-Y54 | 800H-Y54J |
| LOW SPEED | 800H-Y25 | — | THIRD SPEED | 800H-Y55 | — |
| LOWER | 800H-Y26 | 800H-Y26J | UP | 800H-Y56 | 800H-Y56J |
| OFF | 800H-Y27 | 800H-Y27J | UP-DOWN | 800H-Y57 | 800H-Y57J |
| OFF-COOLANT-ON | 800H-Y28 | 800H-Y28J | UP-OFF-DOWN | 800H-Y58 | 800H-Y58J |
| OFF-ON | 800H-Y29 | 800H-Y29J | — | — | — |
| ⋆ Graduated potentiometer type. | |||||
Pilot Light Wiring Diagrams
Typical Pilot Light Wiring Diagrams
See applicable Codes and Laws.
| Push-to-Test Pilot Light Device Schematic | Dual Input Pilot Light Typical Application Wiring Diagram | |
|
|
|
| Dual Input Diode Pilot Device Schematic | Dual Input Pilot Light Transformer Type Device Schematic |
|
|
|
|
Specifications
Specifications⋆
| Electrical Ratings | ||
| Contact Ratings | Refer to the contact ratings tables below. | |
| Dielectric Strength | 2200V for one minute, 1300V for one minute (Logic Reed) | |
| Electrical Design Life Cycles | 1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed) | |
| Mechanical Ratings | ||
| Vibration | 10…2000 Hz 1.52 mm displacement (peak-to-peak) Max./10 G Max. (except Logic Reed) | |
| Shock | 1/2 cycle sine wave for 11 ms ³ 25 G (contact fragility) and no damage at 100 G | |
| Degree of Protection | Type 7 & 9 Explosion Proof (Type 3 and Type 4 ratings available with accessories) | |
| Mechanical Design Life Cycles | ||
| Push Buttons | 250 000 minimum | |
| Potentiometers | 100 000 minimum | |
| All other devices | 200 000 minimum | |
| Contact Operation | Shallow and mini contact blocks: slow double make and break Logic Reed & sealed switch contact blocks: snap-action |
|
| Wire Guage/Terminal Screw Torque | # 18…12 AWG/6…8 lbin | |
| Typical Operating Forces | ||
| Operators without contact blocks: | Flush, extended, standard mushroom, jumbo mushroom: 2.9 lb max. Jumbo and extended aluminum mushroom head: 3.95 lb maximum Maintained selector switch: 4.0 inlb maximum |
|
| Spring Return Selector Switches: | 5 inlb to stop, 0.2 inlb to return | |
| Illuminated Push Buttons and Push-to-Test Pilot Lights | 5.6 lb maximum | |
| 2-Position Push-Pull | 9 lb maximum push or pull | |
| 3-Position Push-Pull | 12 lb maximum push to in position or pull to center position (15 lb maximum pull to out position) |
|
| Contact Blocks: | 800T-XA | 1 lb |
| Logic Reed | 1 lb maximum | |
| Sealed Switch | 3 lb maximum at 0.205 in. plunger travel | |
| Stackable Sealed Switch | 1 lb maximum | |
| Environment | ||
| Temperature Range | Operating | 4…+13 °F (20…+55 °C) |
| Storage | 40…+185 °F (40…+85 °C) | |
| Note:Operating temperatures below freezing are based on the absence of freezing moisture and liquids. | ||
| Humidity | 50% at +104 °F (+40 °C) | |
| ⋆ Performance Data — See Performance Data. | ||
| External thread major diameter: 1.034 in. max., 1.024 in. min. Internal thread minor diameter: 0.958 in. min., 0.970 in. max. | ||
Standard Contact Ratings
Maximum thermal continuous current Ith 10 A AC/2.5 A DC. Bulletin 800H Type 7 & 9 units with 800T-XA contacts have ratings as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | A600 | 120…600 | 7200VA | 720VA |
| 72…120 | 60 A | 720VA | |||
| 24…28 | 60 A | 10 A | |||
| DC 600 | DC-13 | Q600 | 28…600 | 69VA | |
| 24…28 | 2.5 A | ||||
| For applications below 24V and 24 mA, PenTUFF™, Logic Reed or stackable sealed switch contacts are recommended. | |||||
Sealed Switch Contact Ratings
Maximum continuous current Ith 5 A.
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | B600 | 120…600 | 3600VA | 360VA |
| 0…120 | 30 A | 3 A | |||
| DC 300 | DC-13 | P300 | 24…300 | 138VA | |
| 0…24 | 5.0 A | ||||
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 3 A. Bulletin 800T units have control circuit ratings with sealed switch contact blocks as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 | 1800VA | 180VA |
| 0…120 | 15 A | 1.5 A | |||
| DC 150 | DC-13 | Q150 | 24…150 | 69VA | |
| 0…24 | 2.5 A | ||||
Logic Reed Contact Ratings
Maximum: 150V AC, 0.15 A, 8 VA and 30V DC, 0.06 A, 1.8 VA.
Should only be used with resistive loads.
PenTUFF™ (Low Voltage) Contact Ratings
Minimum DC: 5V, 1 mA
Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC. Bulletin 800H units with 800T-XAV contacts have ratings as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 | 1800VA | 180VA |
| 0…120 | 15 A | 1.5 A | |||
| DC 150 | DC-13 | R150 | 24…150 | 28VA | |
| 0…24 | 1.0 A | ||||
Approximate Dimensions
Approximate Dimensions and Shipping Weights
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
| Standard Legend Plate (used with two-hole cover) |
Jumbo Legend Plate (used with one-hole cover) |
|
|
|
Note: Mounting hole requirements for components — 3/4 in. - 14 NPSM.⋆
⋆ External thread major diameter: 1.034 in. max., 1.024 in. min.
Internal thread minor diameter: 0.958 in. min., 0.970 in. max.
Sketch illustrates the minimum distance between center lines when mounting Bulletin 800H units with legend plates either side by side or one above the other in non Allen‑Bradley enclosures. Minimum spacing without legend plate: When units are mounted so that the contact block terminals face each other, the 2‑1/4 in. (57.2 mm) dimension must be used in order to get proper electrical clearance. When control units are mounted so that the contact block terminals do not face each other, the 1‑27/32 in. (46.8 mm) dimension can be used.
Panel Thickness Requirements
| Standard Barrel [devices will fit panels up to 1 in. (25.4 mm)] |
Long Barrel [devices will fit panels up to 2-1/2 in. (63.5 mm)] |
|
|
|
When mounting in a panel thicker than 2-1/8 in. (54 mm) locking bracket not required.
§ This dimension for push buttons only.
Push Buttons
Dual Head
|
| Dim. | A | B | C | Ship. Wt. [oz (kg)] |
| Standard Barrel | 3-5/16 (84.1) |
4-3/16 (106.4) |
4-7/16 (112.7) |
10-3/8 (0.30) |
| Long Barrel | 4-19/32 (116.7) |
5-15/32 (138.9) |
5-23/32 (145.2) |
13 (0.37) |
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Push Buttons
| Mushroom Head | Push Button with Extra Long Guard | |
|
|
|
| Flush Head | Extended Head | |
|
|
|
| Type | Standard Barrel | Long Barrel | ||||||
| A ⋆ | B | C | Ship. Wt. [oz (kg)] |
A | B | C | Ship. Wt. [oz (kg)] |
|
| Mushroom, Flush and Extended Head | 3-3/16 (81) | 4-1/8 (105) | 4-3/8 (111) | 9-7/8 (0.28) | 5 (127) | 5-7/8 (149.2) | 6-1/8 (155.6) | 13-5/16 (0.38) |
| Extra Long Guard | 3-3/16 (81) | 4-1/8 (105) | 4-3/8 (111) | 10-7/8 (0.31) | 5 (127) | 5-7/8 (149.2) | 6-1/8 (155.6) | 14-5/16 (0.40) |
| ⋆ When using sealed switch contact block, this dimension is 4-1/16 in. (103 mm). | ||||||||
| When using sealed switch contact block, this dimension is 5-7/8 in. (149.2 mm). | ||||||||
Selector Switches
| Standard Operator | Knob Lever Operator | |
|
|
|
| Wing Lever Operator | Cylinder Lock Operator | |
|
|
|
| Type | Standard Barrel | Long Barrel | ||||||
| A ⋆ | B | C | Ship. Wt. [oz (kg)] |
A | B | C | Ship. Wt. [oz (kg)] |
|
| Standard and Knob Lever | 3-3/16 (81) | 4-1/8 (105) | 4-3/8 (111) | 9-1/2 (0.27) | 5 (127) | 5-7/8 (149.2) | 6-1/8 (155.6) | 14-3/8 (0.41) |
| Wing Lever | 3-3/16 (81) | 4-1/8 (105) | 4-3/8 (111) | 10-1/2 (0.30) | 5 (127) | 5-7/8 (149.2) | 6-1/8 (155.6) | 15 (0.42) |
| Cylinder Lock | 3-3/16 (81) | 4-1/8 (105) | 4-3/8 (111) | 11-1/4 (0.32) | 5 (127) | 5-7/8 (149.2) | 6-1/8 (155.6) | 16 (0.45) |
| ⋆ When using sealed switch contact block, this dimension is 4-1/16 in. (103 mm). | ||||||||
| When using sealed switch contact block, this dimension is 5-7/8 in. (149.2 mm). | ||||||||
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Illuminated Push Buttons or Push-to-Test Pilot Lights
| Transformer Type | Full Voltage, Dual Input or Neon Type | |
|
|
| Illuminated Push Buttons, Push-to-Test Pilot Lights | |||||
| Description | Style | A ⋆ | B | C | Ship. Wt. [oz (kg)] |
| Transformer Type | Standard Barrel | 3-5/32 (80.2) | 3-29/32 (99) | 4-1/8 (105) | 14 (0.40) |
| Long Barrel | 5-1/16 (128.6) | 5-13/16 (147.6) | 6-1/16 (154) | 16-3/16 (0.45) | |
| Full Voltage Dual Input or Neon Type | Standard Barrel | 3-1/32 (77) | 3-29/32 (99) | 4-1/8 (105) | 11-5/8 (0.33) |
| Long Barrel | 4-15/16 (125.4) | 5-13/16 (147.6) | 6-1/16 (154) | 13-7/16 (0.38) | |
Push-Pull Units
| Non-Illuminated | Illuminated | |
|
|
| Push-Pull Units | ||||||
| Description | Style | A ⋆ | B | C | D | Ship. Wt. [oz (kg)] |
| Illuminated Transformer Type | Standard Barrel | 3-9/16 (90.5) | 4-9/16 (115.9) | 4-5/8 (117.5) | 2-1/8 (54) | 15-1/2 (0.44) |
| Long Barrel | 4-21/32 (118.3) | 5-13/32 (137) | 5-21/32 (143.7) | 2-1/8 (54) | 17-7/16 (0.49) | |
| Illuminated Full Voltage Type | Standard Barrel | 3-7/16 (87.3) | 4-9/16 (115.9) | 4-5/8 (117.5) | 1-31/32 (50) | 12-13/16 (0.33) |
| Long Barrel | 4-17/32 (115.1) | 5-13/32 (137) | 5-21/32 (143.7) | 1-31/32 (50) | 14-3/4 (0.41) | |
| Non-Illuminated Push-Pull Units | Standard Barrel | 3-1/2 (88.9) | 4-3/8 (111.1) | 4-5/8 (117.5) | — | 11-1/8 (0.32) |
| Long Barrel | 4-17/32 (115.1) | 5-13/32 (137) | 5-21/32 (143.7) | — | 12-5/16 (0.34) | |
| ⋆ When using sealed switch contact block add 7/8 in. (22.2 mm) to the listed dimension. | ||||||
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
| Pilot Lights | Transformer Type | |
|
|
|
| Full Voltage, Pigtail Type | ||
|
||
| Description | Style | A | Ship. Wt. [oz (kg)] |
| Transformer type and dual input transformer type pilot lights | Standard Barrel | 3-5/32 (80) | 8-9/16 (0.24) |
| Long Barrel | 4-9/16 (115.9) | 30-1/4 (0.85) | |
| Full voltage, neon or dual input diode and resistor type pilot lights | Standard Barrel | 3-1/32 (77) | 5-13/16 (0.17) |
| Long Barrel | 4-7/16 (112.7) | 27-1/2 (0.77) | |
| Full voltage pigtail type pilot lights | Standard Barrel | 2-3/16 (55.5) | 5-5/8 (0.16) |
| Long Barrel | 3-43/64 (94) | 8-5/16 (0.24) | |
Potentiometer Units
|
| Style | A | Ship. Wt. [oz (kg)] |
| Standard barrel | 3-1/8 (79.5) | 5-3/8 (0.16) |
| Long barrel | 4-1/2 (114.3) | 8 (0.23) |
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Shallow Base Stations
| Figure 1 Shallow Base Station Lever Type |
Figure 2 Shallow Base Station Component Type 1-Gang (1 or 2 devices) |
|
|
|
|
| Shipping Wt. 3 lbs (1.36 kg) | Shipping Wt. 3-1/2 lbs (1.58 kg) |
Deep Base Stations
| Figure 3 Deep Base Station Lever Type 1-Gang |
Figure 4 Deep Base Component Lever Type 1-Gang (1 or 2 devices) |
|
|
|
|
| Shipping Wt. 4 lbs (1.81 kg) | Shipping Wt. 4-1/2 lbs (2.04 kg) |
⋆ When using a flange seal, an approved drain fitting must be provided (refer to National Electrical Code).
When used add the following to the max. depth: Flange seal add 3/16 in. (4.8 mm). Sealing well with or without integral flange seal add 1/2 in. (12.7 mm).
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Factory-Assembled Stations
For depth dimension refer to Figure 3 or 4 on Shallow Base Stations.
⋆ When using a large flange seal, an approved drain fitting must be provided (refer to National Electric Code).