Hazardous Location

Catalogs > Industrial Controls Catalog > Push Buttons > Hazardous Location > Bulletin 800H Type 7&9 Hazardous Location Push Buttons

Bulletin 800H Type 7&9 Hazardous Location Push Buttons

Introduction Standards Compliance and Certifications Product Selection Product Selection for Stations
Modifications and Accessories Pilot Light Wiring Diagrams Specifications Approximate Dimensions
Specifications

Specifications¬ 

Electrical Ratings
Contact Ratings Refer to the contact ratings tables below.
Dielectric Strength 2200V for one minute, 1300V for one minute (Logic Reed)
Electrical Design Life Cycles 1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed)
Mechanical Ratings
Vibration 10…2000 Hz 1.52 mm displacement (peak-to-peak) Max./10 G Max. (except Logic Reed)
Shock 1/2 cycle sine wave for 11 ms ³ 25 G (contact fragility) and no damage at 100 G
Degree of Protection Type 7 & 9 Explosion Proof (Type 3 and Type 4 ratings available with accessories)
Mechanical Design Life Cycles  
    Push Buttons 250 000 minimum
    Potentiometers 100 000 minimum
    All other devices 200 000 minimum
Contact Operation Shallow and mini contact blocks: slow double make and break
Logic Reed & sealed switch contact blocks: snap-action
    Wire Guage/Terminal Screw Torque # 18…12 AWG/6…8 lbin
Typical Operating Forces  
    Operators without contact blocks: Flush, extended, standard mushroom, jumbo mushroom: 2.9 lb max.
Jumbo and extended aluminum mushroom head: 3.95 lb maximum
Maintained selector switch: 4.0 inlb maximum
    Spring Return Selector Switches: 5 in•lb to stop, 0.2 in•lb to return
    Illuminated Push Buttons and Push-to-Test Pilot Lights 5.6 lb maximum
    2-Position Push-Pull 9 lb maximum push or pull
    3-Position Push-Pull 12 lb maximum push to in position or pull to center position
(15 lb maximum pull to out position)
    Contact Blocks: 800T-XA 1 lb
Logic Reed 1 lb maximum
Sealed Switch 3 lb maximum at 0.205 in. plunger travel
Stackable Sealed Switch 1 lb maximum
Environment
Temperature Range Operating –4…+13 °F (–20…+55 °C)
Storage –40…+185 °F (–40…+85 °C)
Note:Operating temperatures below freezing are based on the absence of freezing moisture and liquids.
Humidity 50% at +104 °F (+40 °C)
  
¬ Performance Data — See Performance Data.
T External thread major diameter: 1.034 in. max., 1.024 in. min. Internal thread minor diameter: 0.958 in. min., 0.970 in. max.

Standard Contact Ratings

Maximum thermal continuous current Ith 10 A AC/2.5 A DC. Bulletin 800H Type 7 & 9 units with 800T-XA contacts have ratings as follows:

Max. Oprtnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 600 AC-15 A600 120…600 7200VA 720VA
72…120 60 A 720VA
24…28T  60 A 10 A
DC 600 DC-13 Q600 28…600 69VA
24…28T  2.5 A
  
T For applications below 24V and 24 mA, PenTUFF™, Logic Reed or stackable sealed switch contacts are recommended.

Sealed Switch Contact Ratings

Maximum continuous current Ith 5 A.

Max. Oprtnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 600 AC-15 B600 120…600 3600VA 360VA
0…120 30 A 3 A
DC 300 DC-13 P300 24…300 138VA
0…24 5.0 A
  

Stackable Sealed Switch Contact Ratings

Maximum continuous current Ith 3 A. Bulletin 800T units have control circuit ratings with sealed switch contact blocks as follows:

Max. Oprtnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 300 AC-15 C300 120…300 1800VA 180VA
0…120 15 A 1.5 A
DC 150 DC-13 Q150 24…150 69VA
0…24 2.5 A
  

Logic Reed Contact Ratings

Maximum: 150V AC, 0.15 A, 8 VA and 30V DC, 0.06 A, 1.8 VA.

Should only be used with resistive loads.


PenTUFF™ (Low Voltage) Contact Ratings

Minimum DC: 5V, 1 mA

Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC. Bulletin 800H units with 800T-XAV contacts have ratings as follows:

Max. Oprtnl.
Volts Ue
Utilization Category Rated Operational Currents
IEC NEMA Volts Ue Make Break
AC 300 AC-15 C300 120…300 1800VA 180VA
0…120 15 A 1.5 A
DC 150 DC-13 R150 24…150 28VA
0…24 1.0 A