Catalogs > Industrial Controls Catalog > Push Buttons > Hazardous Location > Bulletin 800H Type 7&9 Hazardous Location Push Buttons
Bulletin 800H Type 7&9 Hazardous Location Push Buttons
| Introduction | Standards Compliance and Certifications | Product Selection | Product Selection for Stations |
| Modifications and Accessories | Pilot Light Wiring Diagrams | Specifications | Approximate Dimensions |
Specifications¬
| Electrical Ratings | ||
| Contact Ratings | Refer to the contact ratings tables below. | |
| Dielectric Strength | 2200V for one minute, 1300V for one minute (Logic Reed) | |
| Electrical Design Life Cycles | 1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed) | |
| Mechanical Ratings | ||
| Vibration | 10…2000 Hz 1.52 mm displacement (peak-to-peak) Max./10 G Max. (except Logic Reed) | |
| Shock | 1/2 cycle sine wave for 11 ms ³ 25 G (contact fragility) and no damage at 100 G | |
| Degree of Protection | Type 7 & 9 Explosion Proof (Type 3 and Type 4 ratings available with accessories) | |
| Mechanical Design Life Cycles | ||
| Push Buttons | 250 000 minimum | |
| Potentiometers | 100 000 minimum | |
| All other devices | 200 000 minimum | |
| Contact Operation | Shallow and mini contact blocks: slow double make and break Logic Reed & sealed switch contact blocks: snap-action |
|
| Wire Guage/Terminal Screw Torque | # 18…12 AWG/6…8 lbin | |
| Typical Operating Forces | ||
| Operators without contact blocks: | Flush, extended, standard mushroom, jumbo mushroom: 2.9 lb max. Jumbo and extended aluminum mushroom head: 3.95 lb maximum Maintained selector switch: 4.0 inlb maximum |
|
| Spring Return Selector Switches: | 5 inlb to stop, 0.2 inlb to return | |
| Illuminated Push Buttons and Push-to-Test Pilot Lights | 5.6 lb maximum | |
| 2-Position Push-Pull | 9 lb maximum push or pull | |
| 3-Position Push-Pull | 12 lb maximum push to in position or pull to center position (15 lb maximum pull to out position) |
|
| Contact Blocks: | 800T-XA | 1 lb |
| Logic Reed | 1 lb maximum | |
| Sealed Switch | 3 lb maximum at 0.205 in. plunger travel | |
| Stackable Sealed Switch | 1 lb maximum | |
| Environment | ||
| Temperature Range | Operating | 4…+13 °F (20…+55 °C) |
| Storage | 40…+185 °F (40…+85 °C) | |
| Note:Operating temperatures below freezing are based on the absence of freezing moisture and liquids. | ||
| Humidity | 50% at +104 °F (+40 °C) | |
| ¬ Performance Data — See Performance Data. | ||
| T External thread major diameter: 1.034 in. max., 1.024 in. min. Internal thread minor diameter: 0.958 in. min., 0.970 in. max. | ||
Standard Contact Ratings
Maximum thermal continuous current Ith 10 A AC/2.5 A DC. Bulletin 800H Type 7 & 9 units with 800T-XA contacts have ratings as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | A600 | 120…600 | 7200VA | 720VA |
| 72…120 | 60 A | 720VA | |||
| 24…28T | 60 A | 10 A | |||
| DC 600 | DC-13 | Q600 | 28…600 | 69VA | |
| 24…28T | 2.5 A | ||||
| T For applications below 24V and 24 mA, PenTUFF™, Logic Reed or stackable sealed switch contacts are recommended. | |||||
Sealed Switch Contact Ratings
Maximum continuous current Ith 5 A.
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 600 | AC-15 | B600 | 120…600 | 3600VA | 360VA |
| 0…120 | 30 A | 3 A | |||
| DC 300 | DC-13 | P300 | 24…300 | 138VA | |
| 0…24 | 5.0 A | ||||
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 3 A. Bulletin 800T units have control circuit ratings with sealed switch contact blocks as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 | 1800VA | 180VA |
| 0…120 | 15 A | 1.5 A | |||
| DC 150 | DC-13 | Q150 | 24…150 | 69VA | |
| 0…24 | 2.5 A | ||||
Logic Reed Contact Ratings
Maximum: 150V AC, 0.15 A, 8 VA and 30V DC, 0.06 A, 1.8 VA.
Should only be used with resistive loads.
PenTUFF™ (Low Voltage) Contact Ratings
Minimum DC: 5V, 1 mA
Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC. Bulletin 800H units with 800T-XAV contacts have ratings as follows:
| Max. Oprtnl. Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
| AC 300 | AC-15 | C300 | 120…300 | 1800VA | 180VA |
| 0…120 | 15 A | 1.5 A | |||
| DC 150 | DC-13 | R150 | 24…150 | 28VA | |
| 0…24 | 1.0 A | ||||