Catalogs > Industrial Controls Catalog > Push Buttons > Touch/Palm > Bulletin 800P Palm-Operated Push Buttons
Bulletin 800P Palm-Operated Push Buttons
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
Specifications⋆
| Electrical Ratings | ||
| Dielectric Strength | 2200V for one minute | |
| Electrical Design Life Cycles | 1 000 000 at maximum rated load 200 000 at maximum rated load (Logic Reed) |
|
| Mechanical Ratings | ||
| Vibration | 10…2000 Hz 1.52 mm displacement (peak-to-peak) 10 G max. | |
| Shock | Mechanical shock at 1/2 cycle sine wave for 11 ms | |
| Contact Fragility | 25 G 9 G 6 G |
800T-XA1, -XA2, -XD1, -XD4, -XD2R, contact blocks 800T-XA, -XA4, -XD2, -XD3, -XAR, -XAV contact blocks 800T-XD1R No damage at 100 G all contact blocks |
| Degree of Protection | Type 1, 12, 4/13; watertight/oiltight 529 IP65 | |
| Mechanical Design Life Cycles | Push Buttons | 1 000 000 minimum |
| Contact Operation | Shallow Contact Block Logic Reed |
Slow, double make and break Snap action |
| Typical Operating Forces | Articulated | 800T-XD1 and 800T-XD4 contact blocks 3.7 lb maximum at center of button, 2.7 lb at perimeter |
| Standard Drive | 3.7 lb | |
| Environmental | ||
| Temperature Range | Operating Storage |
+32…+131 °F (0…+55 °C) -40…+185 °F (-40…+85 °C) |
| Note: Operating temperatures at 0 °C (32 °F) are based on the absence of freezing moisture and liquids. | ||
| ⋆ Performance Data — See Performance Data. | ||
Standard Contact Ratings
(IEC 947-5-1) (NEMA ICS 2-125) Maximum continuous current Ith
10 A. Bulletin 800P units have control circuit ratings with 800T-XA1, -XD1, -XD4, -XA2, -XA, -XA4, -XD2, and -XD3 contact blocks as follows:
| Maximum Operational Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
|
|
|
||||
| AC 600 | AC-15 | A600 | 120…600 72…120 24…72 |
7200VA 60 A 60 A |
720VA 720VA 10 A |
| DC 600 | DC-13 | Q600 | 28…600 24…28 |
69VA 2.5 A |
|
| (See Contact Blocks for 800T-XAR, -XD1R, -XD2R data.) | |||||
PenTUFF™ (Low Voltage) Contact Ratings
Minimum DC: 5V, 1 mA. Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC. Bulletin 800P units with Cat. No. 800T‑XAV contacts have ratings as follows:
| Maximum Operational Volts Ue |
Utilization Category | Rated Operational Currents | |||
| IEC | NEMA | Volts Ue | Make | Break | |
|
|
|
||||
| AC 300 | AC-15 | C300 | 120…300 0…120 |
1800VA 15 A |
180VA 1.5 A |
| DC 150 | DC-13 | R150 | 24…150 0…24 |
28VA 1.0 A |
|