Control Tower Stack Lights

Catalogs > Industrial Controls Catalog > Signaling > Control Tower Stack Lights > Bulletin 855E 50 mm Control Tower™ Stack Lights

Bulletin 855E 50 mm Control Tower™ Stack Lights

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Specifications

Mechanical Ratings
Shock and Vibration Based on the weight and style of mounting; tower lights are subject to damage from shock and vibration. Listed below are reference guidelines for maximum acceptable conditions.
1 Module Stack 3 Module Stack 5 Module Stack
Standard Bases Surface Mount Base or
10 cm Aluminum Pole Base
150 G Shock
5 G Vibration
45 G Shock
1.5 G Vibration
35 G Shock
0.75 G Vibration
Vertical Base or
25 cm Aluminum Pole Base
95 G Shock
3.5 G Vibration
30 G Shock
1.25 G Vibration
20 G Shock
0.5 G Vibration
Recommended Wire Sizes 0.5…1.5 mm2 (22…16 AWG)
Recommended Terminal Torque 0.87 N•m (7 lb•in)
Environmental Ratings
Ingress Ratings Light Modules with Cap UL Type 4/4X/13, IP65
Sound Modules UL Type 4/4X/13, IP65
Surface, Vertical, Tube Mount Bases UL Type 4/4X/13, IP65
Pole Mount Bases UL Type 4/4X/13, IP65
Temperature Ratings — All Products Operating Temperature -25…+50 °C (-13…+122 °F)
Storage Temperature -40…+85 °C (-40…+185 °F)
Materials
Bases, Caps, Lens Covers, Sound Module Housings, Lenses Polycarbonate
Lamp Socket Polycarbonate
Rubber Seals and Gaskets Nitrile Rubber
Pole (for aluminum pole assembly) Aluminum
Pole Base Footing (for aluminum pole base) Polycarbonate
Insulation Sleeve (for pole insulation) Polyolefin
Mounting Screw Washers Polypropylene
  

Performance Ratings
Description 12V AC/DC 24V AC/DC 120V AC 240V AC
Light Output Steady Incandescent 0.5 MSCP
6.3 Lumens
2.5 MSCP
31.4 Lumens
3.0 MSCP
37.7 Lumens
0.49 MSCP
6.2 Lumens
Flashing Incandescent 0.5 MSCP
6.3 Lumens
2.5 MSCP
31.4 Lumens
3.0 MSCP
37.7 Lumens
0.49 MSCP
6.2 Lumens
Strobe 1 Joule per lamp
Steady, Flashing Socket Mount LED Red 900…2240 mcd
Steady, Flashing Socket Mount LED Green 900…1800 mcd
Steady, Flashing Socket Mount LED Amber 1400…3550 mcd
Steady, Flashing Socket Mount LED Blue 224…560 mcd
Steady, Flashing Socket Mount LED
White and Yellow
900…1800 mcd
Operating Voltage
Description 12V AC/DC 24V AC/DC 120V AC 240V AC
Light Modules and Sound Modules 12V AC/DC (± 10%) 24V AC/DC (± 10%) 110V AC 50Hz (± 10%)
120V AC 60Hz (± 10%)
230V AC 50 Hz (± 10%)
240V AC 60 Hz (± 10%)
Lamp Life Ratings (Design Life)
Average Life Under Static, No Vibration, Conditions
Description 12V AC/DC 24V AC/DC 120V AC 240V AC
Incandescent ModulesT ‡  8 000 hrs 7 000 hrs 3 000 hrs 1 600 hrs
LED Modules 100 000 hrs
Strobe Modules 15 000 hrs
Sound Modules 20 000 hrs
  
T First failures at about 35% of average life. Severe vibration may reduce life to 44% of average life.
‡ Flashing applications may reduce life to 50% of average life.

Current Consumption
Description 12V AC/DC 24V AC/DC 120V AC 240V AC
Light Only Modules Steady Incandescent 208 mA 271 mA 58 mA 23 mA
Flashing Incandescent 208 mA 271 mA 58 mA 23 mA
Steady or Flashing LED 42 mA 29 mA 21 mA 20 mA
Strobe 95 mA 60 mA 55 mA 30 mA
Sound Modules Single-Tone Sound Module 12 mA 25 mA 33 mA 33 mA
Two-Tone Sound Module
Flashing Frequency (Light Only Modules)
Flashing Incandescent Modules 12V module approximately 1.5 Hz
24V, 120V, and 240V modules approximately 2 Hz
Time ON/Time OFF = 1:1
Flashing LED Modules Flashing frequency approximately 1.5 Hz
Time On/Time OFF = 1:1
Strobe Modules Flashing frequency appoxrimately 2 Hz (flash duration 1/50,000 secound)
Flashing and Tone frequency (Light Modules/with Sound Set at Continuous Tone)
Tone Frequency Tone frequency is preset at 2800 Hz
Flashing and Tone Pulsing Frequencies (Light Modules/with Sound Set at Pulsing Tone)
Tone Frequency Tone Frequency is preset at 2800 Hz
dB Rating (Sound Modules)
All dB(A) ratings determined at a distance of 1 meter from sound module
Single Tone Sound Module (SA3) Maximum volume ranges from 88 or 103 dB(A) (volume adjustable by dipswitch)
Two Tone Sound Module (TA3)
Leakage Current Impact
All light modules and sound modules are capable of absorbing up to 3 mA of leakage from solid-state outputs without module activation