Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Contactors, Starters, and Overload Relays > AC Contactors and Starters > Bulletin 500 Top Wiring For Motor Loads
Bulletin 500 Top Wiring For Motor Loads
| Introduction | Standards Compliance and Certifications | Cat. No. Explanation | Product Selection | Modifications for Non-Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
| Build a Catalog Number |
Product Selection of NEMA size 0…4 Modular Kits
Base Contactor
Includes a 120V AC coil and (1) N.O. auxiliary contactor as standard.
|
| NEMA Size |
Continuous Ampere Rating [A] |
Max. Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
|
|
|
|||||
| 1-Phase Motor Voltage | 3-Phase Motor Voltage | 600V AC Maximum 60 Hz | ||||||||
| 115V | 230V | 200V | 230V | 50 Hz | 460…575V | 3 Power Poles | 4 Power Poles | 5 Power Poles | ||
| 380…415V | Cat. No. | Cat. No. | Cat. No. | |||||||
| 00 | 9 | 1/3 | 1 | 1.5 | 1.5 | 2 | 2 | ∆ | ∆ | — |
| 0 | 18 | 1 | 2 | 3 | 3 | 5 | 5 | 500-AOÄ930 | 500-AOÄ940 | 500-AOÄ950 |
| 1 | 27 | 2 | 3 | 7.5 | 7.5 | 10 | 10 | 500-BOÄ930 | 500-BOÄ940 | 500-BOÄ950 |
| 2 | 45 | 3 | 7.5 | 10 | 15 | 25 | 25 | 500-COÄ930 | 500-COÄ940 | 500-COÄ950 |
| 3 | 90 | 7.5 | 15 | 25 | 30 | 50 | 50 | 500-DOÄ930 | 500-DOÄ940 | 500-DOÄ950 |
| 4 | 135 | — | — | 40 | 50 | 75 | 100 | 500-EOÄ930 | 500-EOÄ940 | 500-EOÄ950 |
| 5 | 270 | — | — | 75 | 100 | 150 | 200 | ∆ | ∆ | — |
| 6 | 540 | — | — | 150 | 200 | 300 | 400 | ∆ | — | — |
| 7 | 810 | — | — | — | 300 | 600 | 600 | ∆ | — | — |
| 8 | 1215 | — | — | — | 450 | 900 | 900 | ∆ | — | — |
| 9 | 2250 | — | — | — | 800 | 1600 | 1600 | ∆ | — | — |
| ∆ See Product Selection of NEMA sizes 00…9 as Factory Assembled for NEMA size 00, 5…9 open type contactors and NEMA size 00…9 enclosed contactors. | ||||||||||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 500-AOÄ940 becomes Cat. No. 500-AOD940.
| [V] | 24 | 110 | 120 | 125 | 208 | 220 | 240 | 250 | 277 | 380 | 415 | 440 | 480 | 550 | 600 |
| AC, 50 Hz | J | D | — | — | — | A | — | — | — | N | I | B | — | C | — |
| AC, 60 Hz | J | — | D | — | H | — | A | — | F | — | — | — | B | — | C |
| DC♦ | VL | — | — | VG | — | — | — | VG | — | — | — | — | — | — | — |
| ♦ DC voltage code is only available for NEMA sizes 0…3. When ordering a DC voltage code (VL or VG), add "DC" to the catalog number. Example: 500DC-BOVL930. | |||||||||||||||
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, a second coil will be included in the modular kit for field swap out.
Options for Modular Kit
| Options | |
| Code | Description |
| 17 | Surge Suppressor for 120 or 240V AC Coil |
| 90 | (1) N.O. Auxiliary Contact⋆ |
| 91 | (1) N.C. Auxiliary Contact⋆ |
⋆ Up to (6) combinations of auxiliary contacts can be selected. Example: Code 90011 indicates (2) N.O. and (2) N.C. contacts.
Example: Cat. No. 500-COD930-17-90 includes a NEMA size 2, 3-pole, contactor with a 120V AC coil, surge suppressor, and (1) N.O. auxiliary contact.
Product Selection of NEMA sizes 0…4 by Components
|
|
|
|
|
|
|
| Base Contactor | Coil | Auxiliary Contact Contactor |
Surge Suppressor | Power Pole | Top Wire Kit | Load -Side Terminal Shield |
| Base Contactor | ||
| NEMA Size | Continuous Ampere Rating [A] | Cat. No. |
| 0 | 18 | 500F-AOD930 |
| 1 | 27 | 500F-BOD930 |
| 2 | 45 | 500F-COD930 |
| 3 | 90 | 500F-DOD930 |
| 4 | 135 | 500F-EOD930 |
| Coils | ||||
| Description | NEMA Size | |||
| 0…1 | 2 | 3 | 4 | |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| 24V 50/60 Hz | CB013 | CC013 | CD013 | CE013 |
| 110V 50 Hz, 120V 60 Hz | CB236 | CC236 | CD236 | CE236 |
| 208V 60 Hz | CB249 | CC249 | CD249 | CE249 |
| 220V 50 Hz, 240V 60 Hz | CB254 | CC254 | CD254 | CE254 |
| 277V 60 Hz | CB260 | CC260 | CD260 | CE260 |
| 380V 50 Hz | CB354 | CC354 | CD354 | CE354 |
| 415V 50 Hz | CB357 | CC357 | CD357 | CE357 |
| 440V 50 Hz, 480V 60 Hz | CB273 | CC273 | CD273 | CE273 |
| 550V 50 Hz, 600V 60 Hz | CB278 | CC278 | CD278 | CE278 |
| 24V DC | 599-B24DC | 599-C24DC | 599-D24DC | — |
| 125…250V DC | 599-B250DC | 599-C250DC | 599-D250DC | — |
Note: The base contactor includes a 120V AC coil as standard. For all other voltages, select an alternate component coil for field installation.
| Auxiliary Contact — Contactors | ||
| Description | NEMA Size | Cat. No. |
| 1 N.O. | 0…5 | 595-A |
| 2 N.O. | 0…5 | 595-AA |
| 1 N.C. | 0…5 | 595-B |
| 2 N.C. | 0…5 | 595-BB |
| 1 N.O. and N.C. | 0…5 | 595-AB |
| Surge Suppressor | ||
| Description | NEMA Size | Cat. No. |
| 12…120V AC | 0…5 | 599-K04 |
| 240…264V AC Varistor | 599-KA04 | |
| Power Pole Adders | ||
| Description | NEMA Size | Cat. No. |
| 1 N.O. | 0…1 | 599-P01A |
| 1 N.O. | 2 | 599-P2A |
| 1 N.O. | 3 | 599-P3A |
| 1 N.O. | 4 | 599-P4A |
| Top Wiring Kit | |
| NEMA Size | Cat. No. |
| 0…1 | 599-TW01 |
| 2 | 599-TW2 |
| 3 | 599-TW3 |
| 4 | 599-TW4 |
| Terminal Shield Kit | |
| NEMA Size | Cat. No. |
| 0…2 | 599-TS02 |
| 3,4 | 599-TS34 |
Product Selection of NEMA sizes 00…9 as Factory Assembled
| NEMA Size |
Continuous Ampere Rating [A] |
Max. Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Open Type Without Enclosure | Type 1 General Purpose Enclosure |
Type 3R/4/12 Rainproof, Dusttight Industrial Use Enclosure |
Type 4/4X Watertight, Corrosion- Resistant Enclosures Stainless Steel⋆ |
|||
| Motor Voltage |
|
|
|||||||
| 200V | 230V | 50 Hz 380…415V |
460…575V | Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||
| 3-Phase 3 Power Poles 600V AC Maximum 60 Hz | |||||||||
| 00 | 9 | 1-1/2 | 1-1/2 | 2 | 2 | 500-TOÄ930 | 500-TAÄ930 | — | — |
| 0 | 18 | 3 | 3 | 5 | 5 | ∆ | 500-AAÄ930 | 500-AJÄ930 | 500-ACÄ930 |
| 1 | 27 | 7.5 | 7.5 | 10 | 10 | ∆ | 500-BAÄ930 | 500-BJÄ930 | 500-BCÄ930 |
| 2 | 45 | 10 | 15 | 25 | 25 | ∆ | 500-CAÄ930 | 500-CJÄ930 | 500-CCÄ930 |
| 3 | 90 | 25 | 30 | 50 | 50 | ∆ | 500-DAÄ930 | 500-DJÄ930 | 500-DCÄ930 |
| 4 | 135 | 40 | 50 | 75 | 100 | ∆ | 500-EAÄ930 | 500-EJÄ930 | 500-ECÄ930 |
| 5 | 270 | 75 | 100 | 150 | 200 | 500-FOÄ930 | 500-FAÄ930 | 500-FJÄ930 | 500-FCÄ930 |
| 6§ ♣ | 540 | 150 | 200 | 300 | 400 | 500-GOÄ930 | 500-GAÄ930 | 500-GJÄ930 | 500-GCÄ930 |
| 7§ | 810 | — | 300 | 600 | 600 | 500-HOÄ930 | 500-HAÄ930 | 500-HJÄ930 | 500-HCÄ930 |
| 8§ | 1215 | — | 450 | 900 | 900 | 500-JOÄ930 | 500-JAÄ930 | — | — |
| 9§ | 2250 | — | 800 | 1600 | 1600 | 500-KOÄ930 | 500-KAÄ930 | — | — |
| ⋆ Fiberglass-reinforced polyester hubs are included with each starter at no additional charge. | |||||||||
| On size 7 and larger, the auxiliary contact is located on the interposing relay. | |||||||||
| § Does not include line and load lugs, see for kits. | |||||||||
| ♣ Size 6 has feed through wiring. | |||||||||
| ∆ See Product Selection of NEMA size 0…4 Modular Kits for NEMA size 0…4 open type contactors. | |||||||||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 500-AOÄ940 becomes Cat. No. 500-AOD940.
| [V] | 24 | 110 | 120 | 125 | 208 | 220 | 240 | 250 | 277 | 380 | 415 | 440 | 480 | 550 | 600 |
| AC, 50 Hz | J | D | — | — | — | A | — | — | — | N | I | B | — | C | — |
| AC, 60 Hz | J | — | D | — | H | — | A | — | F | — | — | — | B | — | C |
| DC♦ | VL | — | — | VG | — | — | — | VG | — | — | — | — | — | — | — |
| ♦ When ordering a DC voltage code, add DC to the catalog number. Example: Cat. No. 500DC-BOVL930. | |||||||||||||||
Product Selection of NEMA sizes 00…5 as Factory Assembled
| NEMA Size |
Continuous Ampere Rating (A) |
Max. Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Open Type Without Enclosure | Type 1 General Purpose Enclosure |
Type 3R/4/12 Rainproof, Dusttight Industrial Use Enclosure |
Type 4/4X Watertight, Corrosion- Resistant Enclosures Stainless Steel⋆ |
|||
| Motor Voltage |
|
|
|||||||
| 200V | 230V | 50 Hz | 460… 575V |
||||||
| 380… 415V |
|||||||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||||||
| 3-Phase 4 Power Poles 600V AC Maximum 60 Hz | |||||||||
| 00 | 9 | 1.5 | 1.5 | 2 | 2 | — | — | — | — |
| 0 | 18 | 3 | 3 | 5 | 5 | ∆ | 500-AAÄ940 | 500-AJÄ940 | 500-ACÄ940 |
| 1 | 27 | 7.5 | 7.5 | 10 | 10 | ∆ | 500-BAÄ940 | 500-BJÄ940 | 500-BCÄ940 |
| 2 | 45 | 10 | 15 | 25 | 25 | ∆ | 500-CAÄ940 | 500-CJÄ940 | 500-CCÄ940 |
| 3 | 90 | 25 | 30 | 50 | 50 | ∆ | 500-DAÄ940 | 500-DJÄ940 | 500-DCÄ940 |
| 4 | 135 | 40 | 50 | 75 | 100 | ∆ | 500-EAÄ940 | 500-EJÄ940 | 500-ECÄ940 |
| 5 | 270 | 75 | 100 | 150 | 200 | 500-FOÄ940 | 500-FAÄ940 | 500-FJÄ940 | 500-FCÄ940 |
| 3-Phase 5 Power Poles 600V AC Maximum 60 Hz | |||||||||
| NEMA Size |
Continuous Ampere Rating [A] |
200V | 230V | 50 Hz | 460… 575V |
|
|||
| 380… 415V |
|||||||||
| 0 | 18 | 3 | 3 | 5 | 5 | ∆ | 500-AAÄ950 | 500-AJÄ950 | 500-ACÄ950 |
| 1 | 27 | 7.5 | 7.5 | 10 | 10 | ∆ | 500-BAÄ950 | 500-BJÄ950 | 500-BCÄ950 |
| 2 | 45 | 10 | 15 | 25 | 25 | ∆ | 500-CAÄ950 | 500-CJÄ950 | 500-CCÄ950 |
| 3 | 90 | 25 | 30 | 50 | 50 | ∆ | 500-DAÄ950 | 500-DJÄ950 | 500-DCÄ950 |
| 4 | 135 | 40 | 50 | 75 | 100 | ∆ | 500-EAÄ950 | 500-EJÄ950 | 500-ECÄ950 |
| ⋆ Fiberglass-reinforced polyester hubs are included with each starter. | |||||||||
| On size 7 and larger, the auxiliary contact is located on the control relay. | |||||||||
| ∆ See Product Selection of NEMA size 0…4 Modular Kits for NEMA size 0…4 open type contactors. | |||||||||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 500-AOÄ940 becomes Cat. No. 500-AOD940.
| [V] | 24 | 110 | 120 | 125 | 208 | 220 | 240 | 250 | 277 | 380 | 415 | 440 | 480 | 550 | 600 |
| AC, 50 Hz | J | D | — | — | — | A | — | — | — | N | I | B | — | C | — |
| AC, 60 Hz | J | — | D | — | H | — | A | — | F | — | — | — | B | — | C |
| DC♦ | VL | — | — | VG | — | — | — | VG | — | — | — | — | — | — | — |
| ♦ When ordering a DC voltage code, add "DC" to the catalog number. Example: Cat. No. 500DC-BOVL930. | |||||||||||||||
Special Purpose Enclosures
| Description | Hazardous Locations — Bolted Enclosures⋆ | ||
| Contactor | Type 7 & 9 Class I, Groups C & D Class II, Groups E, F, & G — Divisions 1 & 2 — |
Type 3R, 7 & 9 Class I, Groups C & D Class II, Groups E, F, & G — Divisions 1 & 2 — |
|
| Size | Poles | ||
| 0 | 3 | Available | Available |
| 1 | 3 | ||
| 2 | 3 | ||
| 3 | 3 | ||
| 4 | 3 | ||
| 5 | 3 | ||