Definite Purpose Contactors
| Product Overview |
|
| 2-pole |
|
| 4-pole |
Bulletin 400
- Available in the following ranges:
1-Pole: 20/25…40 A, 600V max.
2-Pole: 20/25…40 A, 600V max.
3-Pole: 20/25…90 A, 600V max.
4-Pole: 20/25…40 A, 600V max.
The Allen-Bradley Bulletin 400 Definite Purpose contactors are specifically designed for applications such as air-conditioning, refrigeration, resistive heating, data processing and food service equipment, pumps, and compressors.
Box lugs are standard on 40 A contactors and larger. A maximum of two auxiliary contact blocks (one on each side, four contacts max.) can be field installed.
Features Include:
- UL tested for lighting loads
- Compliant with international standards
- Standard and high fault short-circuit current rating (SCCR)
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA C22.2 No. 14
EN/IEC 60947-4-1
Certifications
UL Recognized (File No. E3125, Guide No. NLDX2)
CSA Certified (File No. LR1234)
CE Marked
SEMKO Certified
Your order must include: 1) complete cat. no. of selected contactor, and 2) auxiliary contacts, if required.
Catalog Number Explanation
| 400 | | DP40 | N | A | 3 | | K | |||
| a | b | c | d | e |
| a | b | c | d | |||||||
| Current Rating | Enclosure Code | Nominal Coil Voltage | Number of Poles | |||||||
| Code | Full Load Amps [A] | Code | Enclosure | Code | 50/60 Hz Frequency | Code | Description | |||
| DP25 | 20/25 | N | No enclosure/no exceptions | J | 24 | 1 | 1 pole | |||
| DP30 | 30 | D | 120 | 2 | 2 poles | |||||
| DP40 | 40 | A | 208/240 | 3 | 3 poles | |||||
| DP50 | 50 | F | 277 | 4 | 4 poles | |||||
| DP60 | 60 | LF | 347 | |||||||
| DP75 | 75 | B | 480 | |||||||
| DP90 | 90 | |||||||||
| e | e (cont'd) | |||
| Modifications | Modifications | |||
| Code | Description | 3-Pole — 20/25, 30, and 40 A only (SER A) | ||
| B | Box lug with DP25 or DP30 in 2nd position | Code | Description | |
| D | 400-DRA factory attached to DP (20/25…40 A) | AB1 | Auxiliary contact 1 N.O./1 N.C. with Quick Connect | |
| E | 2 poles with 3-pole base | A1 | Auxiliary contact SPDT with QC | |
| K | #6-32 screw coil terminal with DP25, DP30, or DP40 in 2nd position | A2 | Auxiliary contact 2 SPDT with QC | |
| R | Ring terminal for DP40…DP90 | 3-Pole — 50…90 A only | ||
| S | #10-32 SEMS terminal | Code | Description | |
| T | Coil terminals down | AB | Auxiliary contact 1 N.O./1 N.C. with QC | |
| U | Coil terminals on load side (T1/2, T2/4, T3/6) without quick connect line/load terminals | A | Auxiliary contact SPDT with QC | |
| X | Without quick connect terminals on line and load | 4-Pole — 20/25, 30, and 40 A only (SER A) | ||
| Code | Description | |||
| AB4 | Auxiliary contact 1 N.O./1 N.C. with QC | |||
| A4 | Auxiliary contact SPDT with QC | |||
| 3- and 4-Pole (SER B) — 20/25, 30, and 40 A only | ||||
| Code | Description | |||
| AB5 | Auxiliary contact 1 N.O./1 N.C. with QC | |||
| A5 | Auxiliary contact SPDT with QC | |||
| AA5 | Auxiliary contact 2 SPDT with QC | |||
Quick Selection Table
Contactors
| Number of Poles | FLA Rating [A] |
Arc Cover |
Standard Termination | Certifications | Page Number |
|
|
1 | 20…30 | Optional | #10-32 screw with 1/4 in. QC |
|
20/25…40 FLA 1- and 2-Pole |
| 40 | Box lug (option available to accept ring terminals) |
|||||
|
2 | 20…30 | #10-32 screw with 1/4 in. QC |
|
||
| 40 | Box lug (option available to accept ring terminals) |
|||||
|
3 | 20…30 | Standard | #10-32 screw with 1/4 in. QC |
|
20/25…40 FLA 3-Pole |
|
40 | Box lug (option available to accept ring terminals) |
|
|||
|
3 | 50, 60 | Standard | Box lug (option available to accept ring terminals) |
|
50…90 FLA 3-Pole |
|
75, 90 | Standard |
|
|||
|
4 | 20…30 | Standard | #10-32 screw with 1/4 in. QC |
|
20/25…40 FLA 4-Pole |
| 40 | Box lug (option available to accept ring terminals) |
|
||||
Product Selection
Your order must include: 1) complete cat. no. of selected contactor, and 2) auxiliary contacts, if required.
| Build a Catalog Number |
20/25…40 FLA 1- and 2-Pole
|
|
|
1-Pole Contactor with Shunt |
2-Pole Contactor with Optional Arc Cover |
| Full Load Amps [A] |
Number of Poles | Maximum Continuous Ampere Rating [A] |
Line Voltage [V AC] |
Locked Rotor Current [A] |
Resistive Current Rating [A] |
Voltage [V] |
Max. Single Phase Hp | Cat. No. | |
| Tungsten Lamp LoadsT | Ballast Lighting Load | ||||||||
| 20/25¬ | 1 | 25 | 240/277 | 150 | 30 | 120 | 1 | 400-DP25NÄ1 | |
| 480 | 50 | 30 | 240 | 2 | |||||
| 600 | 40 | 30 | |||||||
| 20/25¬ | 2 | 25 | 240/277 | 150 | 35 | 120 | 2 | 400-DP25NÄ2 | |
| 480 | 125 | 35 | 240 | 3 | |||||
| 600 | 100 | 35 | |||||||
| 30¬ | 1 | 28 | 240/277 | 150 | 40 | 120 | 1 | 400-DP30NÄ1 | |
| 480 | 75 | 40 | 240 | 2 | |||||
| 600 | 50 | 40 | |||||||
| 30¬ | 2 | 28 | 240/277 | 150 | 40 | 120 | 2 | 400-DP30NÄ2 | |
| 480 | 125 | 40 | 240 | 3 | |||||
| 600 | 100 | 40 | |||||||
| 40¬ | 1 | 35 | 240/277 | 240 | 50 | 120 | 3 | 400-DP40NÄ1 | |
| 480 | 200 | 50 | 240 | 7.5 | |||||
| 600 | 160 | 50 | |||||||
| 40¬ | 2 | 35 | 240/277 | 240 | 50 | 120 | 3 | 400-DP40NÄ2 | |
| 480 | 200 | 50 | 240 | 7.5 | |||||
| 600 | 160 | 50 | |||||||
| ¬ Coil terminal screws are not available on 1- and 2-pole contactors. | |||||||||
| T Max. 480V line 277V load | |||||||||
| Fluorescent | |||||||||
Ä AC Coil Voltage Code for 1- and 2-Pole Contactors
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no.
Example: Cat. No. 400-DP25NÄ1 becomes Cat. No. 400-DP25NJ1. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 24 | 120 | 208/240 | 277 | 480 | |
| Code | J | D | A | F | B | |
Coil Technical Data
| 20/25…40 A One-Pole Contactors | 20/25…40 A Two-Pole Contactors | ||||||||||
| Nominal AC Coil Voltage [V] | 24 | 120 | 208/240 | 277 | 480 | 24 | 120 | 208/240 | 277 | 480 | |
| Maximum Pickup Volts | 18 | 88 | 177 | 221 | 384 | 18 | 88 | 177 | 221 | 384 | |
| Drop-Out Volts Range | 6…15 | 20…70 | 40…140 | 50…165 | 150…270 | 6…15 | 20…70 | 40…140 | 50…165 | 150…270 | |
| Nominal Inrush VA | 50 Hz | 22.5 | 22.5 | 22.5 | 22.5 | 22.5 | 37 | 37 | 37 | 37 | 37 |
| 60 Hz | 20 | 20 | 20 | 20 | 20 | 35 | 35 | 35 | 35 | 35 | |
| Nominal Sealed VA | 50 Hz | 7 | 7 | 7 | 7 | 7 | 8 | 8 | 8 | 8 | 8 |
| 60 Hz | 5.25 | 5.25 | 5.25 | 5.25 | 5.25 | 7 | 7 | 7 | 7 | 7 | |
| Nominal DC Resistance (W) | 16.5 | 420 | 1850 | 2650 | 3050 | 11 | 250 | 1000 | 1600 | 3050 | |
Arc Cover
| Description | Cat. No. |
| 20/25 and 30 A 1-Pole | 400-C1 |
| 20/25 and 30 A 2-Pole | 400-C2 |
| 40 A 1 and 2 Pole | Standard |
20/25…40 FLA 3-Pole
|
| Full Load Amps [A] |
Number of Poles | Maximum Continuous Ampere Rating [A] |
Line Voltage [V AC] |
Locked Rotor Current [A] |
Resistive Current Rating [A] |
Voltage [V] |
Max. Horsepower | Cat. No. | ||
| Tungsten Lamp LoadsT | Ballast Lighting Load | Single Phase | Three Phase | |||||||
| 20/25 | 3 | 25 | 240/277 480 600 |
150 125 100 |
35 35 35 |
110/120 | 2 | — | 400-DP25NÄ3 | |
| 200/208 | — | 7.5 | ||||||||
| 240/277 | 5 | 10 | ||||||||
| 480 | — | 15 | ||||||||
| 600 | — | 20 | ||||||||
| 30 | 3 | 28 | 240/277 480 600 |
180 150 120 |
40 40 40 |
110/120 | 2 | — | 400-DP30NÄ3 | |
| 200/208 | — | 10 | ||||||||
| 240/277 | 5 | 10 | ||||||||
| 480 | — | 15 | ||||||||
| 600 | — | 20 | ||||||||
| 40¬ | 3 | 35 | — | 240/277 480 600 |
240 200 160 |
50 50 50 |
110/120 | 3 | — | 400-DP40NÄ3 |
| 200/208 | — | 10 | ||||||||
| 240/277 | 7.5 | 10 | ||||||||
| 480 | — | 20 | ||||||||
| 600 | — | 25 | ||||||||
| ¬ To use ring terminals on 40 FLA and larger power connections add the suffix R to the catalog number. Example: Cat. No. 400-DP40NÄ3 becomes Cat. No. 400-DP40NÄ3-R. |
||||||||||
| T Max. 480V line 277V load | ||||||||||
| Fluorescent | ||||||||||
Ä AC Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no.
Example: Cat. No. 400-DP25NÄ3 becomes Cat. No. 400-DP25NJ3. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 24 | 120 | 208/240 | 277 | 347 | 480 | |
| Code | J | D | A | F | LF | B | |
Coil Technical Data
| Nominal Coil Voltage | 24 | 120 | 208/240 | 277 | 347 | 480 | |
| Maximum Pickup Voltage [V] | 18 | 88 | 177 | 220 | 277 | 384 | |
| Drop-Out Voltage [V] | 6…15 | 20…70 | 40…140 | 65…185 | 85…225 | 150…270 | |
| Nominal Inrush VA | 50 Hz | 72 | 72 | 72 | 72 | 72 | 72 |
| 60 Hz | 64 | 64 | 64 | 64 | 64 | 64 | |
| Nominal Sealed VA | 50 Hz | 7.2 | 7.2 | 7.2 | 7.2 | 7.2 | 7.2 |
| 60 Hz | 6 | 6 | 6 | 6 | 6 | 6 | |
| Nominal DC Resistance (W) | 5.8 | 147 | 597 | 837 | 1330 | 2425 | |
Auxiliary Contacts
| Description | Cat. No. |
| 1 N.O./1 N.C. w/QC§ | 400-AB5 |
| SPDT w/QCs§ | 400-A5 |
| 2-SPDT w/QC§ | 400-AA5 |
| § Contact rating single-circuit N.O. or N.C.: | |
| [V] | 120 | 240 | 480 | 600 | |
| Current [A] | Break | 3.0 | 1.5 | 0.75 | 0.6 |
| Make | 30 | 15 | 7.5 | 6 | |
| Continuous | 10 | 10 | 10 | 10 | |
§ Contact rating SPDT:
10 A, 1/3 Hp, 125 or 250V AC;
1/2 A, 125V DC;
1/4 A, 250V DC;
4 A 120V AC on lamp load
50…90 FLA 3-Pole
|
|
|
| 50 and 60 FLA 3-Pole | 75 and 90 FLA 3-Pole |
| Full Load Amps [A] |
Number of Poles | Maximum Continuous Ampere Rating [A] |
Line Voltage [V AC] |
Locked Rotor Current [A] |
Resistive Current Rating [A] |
Voltage [V] |
Maximum Horsepower | Cat. No. | ||
| Tungsten Lamp LoadsT | Ballast Lighting Load | Single Phase | Three Phase | |||||||
| 50¬ | 3 | 53 | 240 480 600 |
300 250 200 |
65 65 65 |
110/120 | 3 | — | 400-DP50NÄ3 | |
| 200/208 | 7.5 | 15 | ||||||||
| 220…240 | 10 | 15 | ||||||||
| 480 | — | 25 | ||||||||
| 600 | — | 25 | ||||||||
| 60¬ | 3 | 53 | 240 480 600 |
360 300 240 |
75 75 75 |
110/120 | 5 | — | 400-DP60NÄ3 | |
| 200/208 | 7.5 | 25 | ||||||||
| 220…240 | 10 | 25 | ||||||||
| 480 | — | 30 | ||||||||
| 600 | — | 30 | ||||||||
| 75¬ | 3 | 63 | — | 240 480 600 |
450 375 300 |
93 93 93 |
110/120 | 5 | — | 400-DP75NÄ3 |
| 200/208 | 10 | 20 | ||||||||
| 240 | 15 | 25 | ||||||||
| 480 | — | 40 | ||||||||
| 600 | — | 40 | ||||||||
| 90¬ | 3 | 63 | — | 240 480 600 |
540 450 360 |
120 120 120 |
110/120 | 7.5 | — | 400-DP90NÄ3 |
| 200/208 | 15 | 25 | ||||||||
| 240 | 20 | 30 | ||||||||
| 480 | — | 50 | ||||||||
| 600 | — | 50 | ||||||||
| ¬ To use ring terminals on 40 FLA and larger power connections add the suffix R to the catalog number. Example: Cat. No. 400-DP60NÄ3 becomes Cat. No. 400-DP60NÄ3-R. |
||||||||||
| T Max. 480V line 277V load | Fluorescent | |||||||||
Ä AC Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no.
Example: Cat. No. 400-DP50NÄ3 becomes Cat. No. 400-DP50NJ3. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 24 | 120 | 208/240 | 277 | 480 | |
| Code | J | D | A | F | B | |
Coil Technical Data
| Nominal AC Coil Voltage [V] | 24 | 120 | 208/240 | 277 | 480 | ||||||
| 50 & 60 A |
75 & 90 A |
50 & 60 A |
75 & 90 A |
50 & 60 A |
75 & 90 A |
50 & 60 A |
75 & 90 A |
50 & 60 A |
75 & 90 A |
||
| Maximum Pickup Voltage [V] | 18 | 18 | 93 | 88 | 177 | 177 | 235 | 220 | 374 | 384 | |
| Drop-Out Voltage [V] | 6…15 | 6…15 | 20…70 | 20…70 | 40… 135 |
40… 110 |
50… 180 |
65… 185 |
120… 286 |
150… 270 |
|
| Nominal Inrush VA | 50 Hz | 140 | 285 | 140 | 285 | 140 | 285 | 140 | 285 | 140 | 285 |
| 60 Hz | 132 | 240 | 132 | 240 | 132 | 240 | 132 | 240 | 132 | 240 | |
| Nominal Sealed VA | 50 Hz | 20 | 42 | 20 | 42 | 20 | 42 | 20 | 42 | 20 | 42 |
| 60 Hz | 14 | 27 | 14 | 27 | 14 | 27 | 14 | 27 | 14 | 27 | |
| Nominal DC Resistance (W) | 2.4 | 0.63 | 45 | 15.6 | 180 | 63.5 | 280 | 84 | 852 | 255 | |
Auxiliary Contacts
| Description | Cat. No. |
| 1 N.O./1 N.C. w/QCs§ | 400-AB |
| SPDT w/QCs§ | 400-A |
| § Contact rating single-circuit N.O. or N.C.: | |
| [V] | 120 | 240 | 480 | 600 | |
| Current [A] |
Break | 3.0 | 1.5 | 0.75 | 0.6 |
| Make | 30 | 15 | 7.5 | 6 | |
| Continuous | 10 | 10 | 10 | 10 | |
§ Contact rating SPDT:
10 A, 1/3 Hp, 125 or 250V AC;
1/2 A, 125V DC;
1/4 A, 250V DC;
4 A 120V AC on lamp load
20/25…40 FLA 4-Pole
|
| Full Load Amps [A] |
Number of Poles | Maximum Continuous Ampere Rating [A] |
Line Voltage [V AC] |
Locked Rotor Current [A] |
Resistive Current Rating [A] |
Voltage [V] |
Maximum Horsepower | Cat. No. | ||
| Tungsten Lamp LoadsT | Ballast Lighting Load | Single Phase | Three Phase | |||||||
| 20/25 | 4 | 25 | 240/277 480 600 |
150 125 100 |
35 35 35 |
110/120 | 2 | — | 400-DP25NÄ4 | |
| 200/208 | — | 7.5 | ||||||||
| 240/277 | 5 | 10 | ||||||||
| 480 | — | 15 | ||||||||
| 600 | — | 20 | ||||||||
| 30 | 4 | 28 | 240/277 480 600 |
180 150 120 |
40 40 40 |
110/120 | 2 | — | 400-DP30NÄ4 | |
| 200/208 | — | 10 | ||||||||
| 240/277 | 5 | 10 | ||||||||
| 480 | — | 15 | ||||||||
| 600 | — | 20 | ||||||||
| 40 | 4 | 35 | 240/277 480 600 |
240 200 160 |
50 50 50 |
110/120 | 3 | — | 400-DP40NÄ4 | |
| 200/208 | — | 10 | ||||||||
| 240/277 | 7.5 | 10 | ||||||||
| 480 | — | 20 | ||||||||
| 600 | — | 25 | ||||||||
| T Max. 480V line 277V load | ||||||||||
| Fluorescent | ||||||||||
Ä AC Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no.
Example: Cat. No.400-DP25NÄ4 becomes Cat. No. 400-DP25NJ4. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 24 | 120 | 208/240 | 277 | 347 | 480 | |
| Code | J | D | A | F | LF | B | |
Coil Technical Data
| Nominal AC Coil Voltage [V] | 24 | 120 | 208/240 | 277 | 347 | 480 | |
| Maximum Pickup Voltage [V] | 18 | 88 | 177 | 220 | 277 | 384 | |
| Drop-Out Voltage [V] | 6…15 | 20…70 | 40…140 | 65…185 | 85…225 | 150…270 | |
| Nominal Inrush VA | 50 Hz | 82 | 82 | 82 | 82 | 82 | 82 |
| 60 Hz | 73 | 73 | 73 | 73 | 73 | 73 | |
| Nominal Sealed VA | 50 Hz | 9 | 9 | 9 | 9 | 9 | 9 |
| 60 Hz | 7.2 | 7.2 | 7.2 | 7.2 | 7.2 | 7.2 | |
| Nominal DC Resistance (W) | 5.25 | 133 | 540 | 760 | 1205 | 2195 | |
Auxiliary Contacts Series B Contactors Only
| Description | Cat. No. |
| SPDT w/QC | 400-A5 |
| 2-SPDT w/QC | 400-AA5 |
| 1 N.O./1 N.C. w/QC | 400-AB5 |
| [V] | 120 | 240 | 480 | 600 | |
| Current [A] | Break | 3.0 | 1.5 | 0.75 | 0.6 |
| Make | 30 | 15 | 7.5 | 6 | |
| Continuous | 10 | 10 | 10 | 10 | |
§ Contact rating SPDT:
10 A, 1/3 Hp, 125 or 250V AC;
1/2 A, 125V DC;
1/4 A, 250V DC;
4 A 120V AC on lamp load
Accessories
| Description | For Use With | Cat. No. | |
|
Mechanical Interlock Kit | 20/25…40 A 3-pole |
400-MK1 |
|
DIN Rail Adapter | 20/25…40 A 1-…4-pole |
400-DRA |
Modifications
| Description | Suffix Code | |
| Box lug with DP25 or DP30 in second position | B | |
| Molded coil (not available with 1 or 2 in fifth position) | C | |
| Factory-installed DIN Rail adapter (20…40 A) | D | |
| 2-pole with 3-pole base | E | |
| #6-32 screw coil terminal with DP25, DP30, or DP40 in second position (3- & 4-pole only) | K | |
| Ring terminal for DP40…DP90 | R | |
| #10-32 SEMS terminals with DP25, DP30, or DP40 in second position | S | |
| Coil terminals down | T | |
| Coil terminals on load side (T1/2, T2/4, T3/6) without quick connect (QC) line/load terminals | U | |
| Without QC terminals on line and load | X | |
| Auxiliary contact 1 N.O./1 N.C. with QC | ¬ | AB1 |
| Auxiliary contact SPDT with QC | ¬ | A1 |
| Auxiliary contact 2 SPDT with QC | ¬ | A2 |
| Auxiliary contact 1 N.O./1 N.C. with QC | T | AB |
| Auxiliary contact SPDT with QC | T | A |
| ¬ 3-pole 20/25, 30, and 40 A only. | ||
| T 3-pole 50…90 A only. | ||
Specifications
20/25…40 FLA 1- and 2-Pole
| Line and Load Terminals | #10-32 screw or box lug | |
| Wire Size |
#10-32 screw | #16…8 AWG (stranding must be split for #8 wire) |
| Box Lug | #14…4 AWG | |
| Mechanical Life | 1 000 000 operations | |
| Electrical Life | 250 000 operations | |
| Recommended Tightening Torque |
#10-32 screw | 25 lbin |
| Box lug | 40 lbin | |
| Quick Connects | Power terminals | Dual 0.250 QC (2) |
| Coil terminals | 1-Pole: Quad 0.250 QC 2-Pole: Dual or Quad 0.250 QC |
|
| Arc Cover | Optional | |
| Insulation System | 130 °C Class B | |
| Temperature Range | -40…+65 °C (-40…+150 °F) | |
| Mounting Position | Vertical | All positions |
| Horizontal | Base down only | |
| Weight | 1‑Pole 2‑Pole |
0.5 lb 0.6 lb |
20/25…40 FLA 3-Pole
| Line and Load Terminals | #10-32 screw or box lug | |
| Wire Size |
#10-32 screw | #16…8 AWG (stranding must be split for #8 wire) |
| Box Lug | #14…4 AWG | |
| Mechanical Life | 1 000 000 operations | |
| Electical Life | 250 000 operations | |
| Recommended Tightening Torque |
#10-32 screw | 25 lbin |
| Box lug | 40 lbin | |
| Quick Connects | Power terminals | Dual 0.250 QC (2) |
| Coil terminals | Quad 0.250 QC | |
| Arc Cover | Standard | |
| Insulation System | 130 °C Class B | |
| Temperature Range | -40…+65 °C (-40…+150 °F) | |
| Mounting Position | Vertical | All positions |
| Horizontal | Base down only | |
| Weight | 1 lb | |
50…60 FLA 3-Pole
| Line and Load Terminals | Box lug | |
| Wire Size | #14…2 AWG | |
| Mechanical Life | 500 000 operations | |
| Electrical Life | 250 000 operations | |
| Recommended Tightening Torque |
50 lbin | |
| Quick Connects | Power terminals |
Dual 0.250 QC (2) |
| Coil terminals | #6-32 screw and 0.250 QC (2) | |
| Arc Cover | Standard | |
| Insulation System | 130 °C Class B | |
| Temperature Range | -40…+65 °C (-40…+150 °F) | |
| Mounting Position | Vertical | All positions |
| Horizontal | Base down only | |
| Weight | 2 lb | |
75…90 FLA 3-Pole
| Line and Load Terminals | Box lug | |
| Wire Size | #14…1/0 AWG | |
| Mechanical Life | 500 000 operations | |
| Electrical Life | 100 000 operations | |
| Recommended Tightening Torque |
50 lbin | |
| Quick Connects | Power terminals | Dual 0.250 QC |
| Coil terminals | #6-32 screw and 0.250 QC (2) | |
| Arc Cover | Standard | |
| Insulation System | 130 °C Class B | |
| Temperature Range | -40…+65 °C (-40…+150 °F) | |
| Mounting Position | Vertical | All Positions |
| Horizontal | Base down only | |
| Weight | 4 lb | |
20/25…40 FLA 4-Pole
| Line and Load Terminals | #10-32 screw or box lug | |
| Wire Size |
#10-32 screw | #16…8 AWG (stranding must be split for #8 wire) |
| Box lug | #14…4 AWG | |
| Mechanical Life | 1 000 000 operations | |
| Electrical Life | 250 000 operations | |
| Recommended Tightening Torque |
#10-32 screw | 25 lbin |
| Box lug | 40 lbin | |
| Quick Connects | Power terminals | Dual 0.250 QC |
| Coil terminals | Dual 0.250 QC (2) | |
| Arc Cover | Standard | |
| Insulation System | 130 °C Class B | |
| Temperature Range | -40…+65 °C (-40…+150 °F) | |
| Mounting Position | Vertical | All positions |
| Horizontal | Base down only | |
| Weight | 1.5 lb | |
Approximate Dimensions
Dimensions shown in inches. Dimensions are not intended to be used for manufacturing purposes.
20/25…40 FLA 1- and 2-Pole
|
|
20/25…40 FLA 3-Pole
|
Dimensions shown in inches. Dimensions are not intended to be used for manufacturing purposes.
50 and 60 FLA 3-Pole
|
75 and 90 FLA 3-Pole
|
Dimensions shown in inches. Dimensions are not intended to be used for manufacturing purposes.
20/25…40 FLA 4-Pole
|
DIN Rail Adaptors
|
Terminations