Specifications

20/25…40 FLA 1- and 2-Pole

Line and Load Terminals #10-32 screw or box lug
Wire Size
#10-32 screw #16…8 AWG
(stranding must be split for #8 wire)
Box Lug #14…4 AWG
Mechanical Life 1 000 000 operations
Electrical Life 250 000 operations
Recommended
Tightening Torque
#10-32 screw 25 lb•in
Box lug 40 lb•in
Quick Connects Power terminals Dual 0.250 QC (2)
Coil terminals 1-Pole: Quad 0.250 QC
2-Pole: Dual or Quad 0.250 QC
Arc Cover Optional
Insulation System 130 °C Class B
Temperature Range -40…+65 °C (-40…+150 °F)
Mounting Position Vertical All positions
Horizontal Base down only
Weight 1‑Pole
2‑Pole
0.5 lb
0.6 lb
  

20/25…40 FLA 3-Pole

Line and Load Terminals #10-32 screw or box lug
Wire Size
#10-32 screw #16…8 AWG
(stranding must be split for #8 wire)
Box Lug #14…4 AWG
Mechanical Life 1 000 000 operations
Electical Life 250 000 operations
Recommended
Tightening Torque
#10-32 screw 25 lb•in
Box lug 40 lb•in
Quick Connects Power terminals Dual 0.250 QC (2)
Coil terminals Quad 0.250 QC
Arc Cover Standard
Insulation System 130 °C Class B
Temperature Range -40…+65 °C (-40…+150 °F)
Mounting Position Vertical All positions
Horizontal Base down only
Weight 1 lb
  

50…60 FLA 3-Pole

Line and Load Terminals Box lug
Wire Size #14…2 AWG
Mechanical Life 500 000 operations
Electrical Life 250 000 operations
Recommended
Tightening Torque
50 lb•in
Quick Connects Power
terminals
Dual 0.250 QC (2)
Coil terminals #6-32 screw and 0.250 QC (2)
Arc Cover Standard
Insulation System 130 °C Class B
Temperature Range -40…+65 °C (-40…+150 °F)
Mounting Position Vertical All positions
Horizontal Base down only
Weight 2 lb
  

75…90 FLA 3-Pole

Line and Load Terminals Box lug
Wire Size #14…1/0 AWG
Mechanical Life 500 000 operations
Electrical Life 100 000 operations
Recommended
Tightening Torque
50 lb•in
Quick Connects Power terminals Dual 0.250 QC
Coil terminals #6-32 screw and 0.250 QC (2)
Arc Cover Standard
Insulation System 130 °C Class B
Temperature Range -40…+65 °C (-40…+150 °F)
Mounting Position Vertical All Positions
Horizontal Base down only
Weight 4 lb
  

20/25…40 FLA 4-Pole

Line and Load Terminals #10-32 screw or box lug
Wire Size
#10-32 screw #16…8 AWG
(stranding must be split for #8 wire)
Box lug #14…4 AWG
Mechanical Life 1 000 000 operations
Electrical Life 250 000 operations
Recommended
Tightening Torque
#10-32 screw 25 lb•in
Box lug 40 lb•in
Quick Connects Power terminals Dual 0.250 QC
Coil terminals Dual 0.250 QC (2)
Arc Cover Standard
Insulation System 130 °C Class B
Temperature Range -40…+65 °C (-40…+150 °F)
Mounting Position Vertical All positions
Horizontal Base down only
Weight 1.5 lb