Manual Motor Starters

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Manual Motor Starters > Bulletin 609 Single and Three Phase

Bulletin 609 Single and Three Phase

Introduction Standards Compliance and Certifications Product Selection Accessories Approximate Dimensions
Accessories

Pilot Light Kits

Kits are available for field installation of pilot lights in Type 1 General Purpose surface or flush mounting enclosures. As standard, a clear pilot light lens is supplied. Pilot lights are not available for Bulletin 609RS or 609TS manual starters.

Volts [V] Cat. No.
120 609-N10
240 609-N20
480 609-N40
600 609-N60
  

Pilot Lights Factory Installed

To order, add the following suffix code after the last letter in the listed Cat. No. Example: Cat. No. 609-AAXD4. Available for Type 1 General Purpose Enclosure only.

Volts [V] Suffix Code
120 D4
240 A4
480 B4
600 C4
  
Note:Replacement lamp is ANSI part number B2A (NE-51H), Cat. No. 609-N9.

Fusing

The Bulletin 609 is suitable for general installation in accordance with the local electrical code.

Group Fusing

The Bulletin 609 sizes 0 and 1 in Type 1, 4X, and 12 enclosures are UL Listed for group fusing with Class J fuses only. See table below for maximum fuse ratings.

Full Load Current of Smallest
Motor Amperes [A]
Maximum Fuse Ratings [A]
Nominal System Voltages
120…240V 480…600V
0.45…2.99 30 30
3.00…6.49 60 30
6.50…18.0 100