Manual Motor Starters

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Manual Motor Starters > Bulletin 609U with Under Voltage Protection

Bulletin 609U with Under Voltage Protection

Introduction Standards Compliance and Certifications Product Selection Modifications Approximate Dimensions
Modifications

Pilot Light Kits

Kits are available for field installation of pilot lights in Type 1 general purpose surface or flush mounting enclosures. A clear lens is provided as standard. Pilot lights are not available for Bulletin 609RS or 609TS manual starters.

Volts [V] NEMA Type Cat. No.
120 Type 1 609-N10
240 609-N20
480 609-N40
600 609-N60
  

Pilot Lights Factory Installed

To order, add the number 4 after the last letter in the listed cat. no. Example: Cat. No. 609U-AAXD becomes Cat. No. 609U-AAXD4. Available for Type 1 general purpose enclosure only.
Note:Replacement lamp is ANSI part number B2A (NE-51H), Allen-Bradley Cat. No. 609-N9.


Group Fusing

The Bulletin 609U and 609TU Sizes 0 and 1 in Type 1, 4/4X, and 3R/12 enclosures are UL Listed for group fusing with Class J fuses only. See table below for maximum fuse ratings.

Full Load Current of Smallest
Motor Amperes [A]
Maximum Fuse Ratings [A]
Nominal System Voltages
120…240V 480…600V
0.45…2.99 30 30
3.00…6.49 60 30
6.50…18.0 100
  

Typical Wiring Diagram

(See Applicable Codes and Laws)

Click to enlarge - 609U-1_158-1


★ Remove Jumper “A” to connect remote stop operator wires to vacated terminals.
Note:Jumper not available on devices in Type 7 and 9 Enclosure.