Bulletin 1100 Vacuum Contactors
| Product Overview |
|
|
|
| Insulation Barrier | 200 A Vacuum Contactor |
Bulletin 1100
- 1500V AC maximum
- 3300V AC maximum with insulating barrier
- Typical industry applications include:
- Mining and metals
- Pumps
- Process equipment
- Petroleum
- Chemical processing
- Hoists
- Conveyors
- Mining equipment
- Mining and metals
Bulletin 1100 open type contactor is designed for use up to 1500V maximum. By adding the optional insulating barrier, the 180, 200, 350, and 450 A non-reversing contactors can be used up to and including 3300V. Vacuum contactors are particularly well-suited in mining, pumping, and other applications where voltages above 600V are used. Bulletin 1100 line utilizes vacuum bottles to enclose the power switching contacts within the contactor. The use of vacuum technology results in particularly effective arc extinguishing above the 600V level and allows the design of a very compact, long lasting contactor.
| Table of Contents |
| Product Selection |
| Accessories |
| Contact Arrangements |
| Approximate Dimensions |
Standards Compliance and Certifications
Certifications
UL Recognized (File No. E3125; Guide No. NLDX)
CSA Certified (File No. LR1234)
Product Selection
Product Selection
Your order must include: 1) Cat. No. of vacuum contactor, 2) if required, Cat. No. of any accessories.
| Build a Catalog Number |
3-Phase, 1500V Maximum, 60 Hz (For ratings above 1500V, see below.)
| Horsepower Ratings Motor Voltage | Capacitor Switching kVAR ¬ | Transformer Primary Switching kVA T | Continuous Current Rating [A] |
Cat. No. | |||||||||||||||||
| 200V | 230V | 460V | 575V | 800V | 1100V | 1500V | 230V | 460V | 575V | 800V | 1100V | 1500V | 230V | 460V | 575V | 800V | 1100V | 1500V | |||
| — | — | — | — | 200 | 300 | 400 | — | — | — | 180 | 240 | 320 | — | — | — | — | — | — | 180 | 1100-AOÄ93 | |
| 60 | 60 | 150 | 150 | — | — | — | 50 | 99 | 124 | — | — | — | 36 | 69 | 86 | 66.5 | 91.4 | 124.7 | 200 | § | 1100-AOÄ93 |
| 100 | 125 | 250 | 300 | 400 | 600 | 900 | 73 | 142 | 176 | 241 | 330 | 450 | 67 | 129 | 163 | 244 | 348 | 433 | 350 | 1100-BOÄ93 | |
| 125 | 150 | 350 | 400 | 500 | 700 | 1000 | 93 | 186 | 236 | 287 | 340 | 500 | 81 | 161 | 189 | 275 | 381 | 519 | 450 | 1100-COÄ93 | |
| 200 | 250 | 500 | 600 | 800 | 1100 | 1600 | 200 | 400 | 500 | — | — | — | 125 | 250 | 310 | 410 | 570 | 775 | 610 | 1100-DOÄ93 | |
3-Phase, 3300V Maximum (Requires Insulation Barrier)
3300V AC Insulating Barriers (180… 450 A Only) — The ratings of the listed vacuum contactors can be increased to 3300V by replacing the standard safety shield. The replacement insulating barrier provides 3.3 kV line and load terminal isolation. Ratings change as indicated in the table below with the addition of this insulating barrier to listed contactors:
| Horsepower Ratings | kW Ratings | Continuous Current Rating [A] |
Cat. No. | ||||
| Motor Voltage | |||||||
| 2400V | 3000V | 3300V | 2400V | 3000V | 3300V | ||
| 3300V Insulating Barrier (Required to obtain ratings below) | — | 1100M-N1 | |||||
| 600 | 800 | 800 | 500 | 630 | 630 | 180 | 1100-AOÄ93 |
| 1200 | 1500 | 1500 | 1000 | 1250 | 1250 | 350 | 1100-BOÄ93 |
| 1500 | 2000 | 2000 | 1250 | 1500 | 1500 | 450 | 1100-COÄ93 |
Ä Coil Voltage Code
The cat. no. is incomplete. To complete the cat. no., select a coil voltage code from the table below and insert into the cat. no.
Example: Cat. No. 1100-AOÄ93 becomes Cat. No. 1100-AOD93.
| [V] | 100…127 | 100…110 | 200…240 | 200…220 | 380…440 | 460…550 | ||
| AC | 50/60 Hz | D | — | A | — | N | B | |
| DC | — | — | G | — | H | — | — | |
| ¬ Inrush current should be less than 1000% of IEC AC3 operational current. T For use on transformers having an inrush not more than 20 times the rated full load current irrespective of secondary load. Ratings do not apply to transformers used in resistive welder service. Devices with a continuous current rating of 610 A must use the 100…127V and 200…240V coils only. § For 200V continuous rating. |
||||||||
Accessories
Accessories
Auxiliary Contacts
Contactors are supplied with two normally open and two normally closed auxiliary contacts as standard. Additional auxiliary contacts, two normally open and two normally closed, can be added in the field.
| Auxiliary Contact (for 180…450 A devices) Cat. No. 1195-N1 Auxiliary Contact (for 610 A devices) Cat. No. 1195-N2 |
Contact Arrangements
Contact Arrangements
|
Approximate Dimensions
|