Bulletin 1100 Vacuum Contactors

Product Overview


Click to enlarge - 1100-1_16-1   Click to enlarge - 1100-1_16-2
Insulation Barrier 200 A Vacuum Contactor

Bulletin 1100


Bulletin 1100 open type contactor is designed for use up to 1500V maximum. By adding the optional insulating barrier, the 180, 200, 350, and 450 A non-reversing contactors can be used up to and including 3300V. Vacuum contactors are particularly well-suited in mining, pumping, and other applications where voltages above 600V are used. Bulletin 1100 line utilizes vacuum bottles to enclose the power switching contacts within the contactor. The use of vacuum technology results in particularly effective arc extinguishing above the 600V level and allows the design of a very compact, long lasting contactor.

Table of Contents
Product Selection
Accessories
Contact Arrangements
Approximate Dimensions

Standards Compliance and Certifications

Certifications

UL Recognized (File No. E3125; Guide No. NLDX)
CSA Certified (File No. LR1234)


Product Selection

Product Selection

Your order must include: 1) Cat. No. of vacuum contactor, 2) if required, Cat. No. of any accessories.

Build a Catalog Number


3-Phase, 1500V Maximum, 60 Hz (For ratings above 1500V, see below.)

Horsepower Ratings Motor Voltage Capacitor Switching kVAR ¬  Transformer Primary Switching kVA T  Continuous
Current
Rating [A]
Cat. No.
200V 230V 460V 575V 800V 1100V 1500V 230V 460V 575V 800V 1100V 1500V 230V 460V 575V 800V 1100V 1500V
200 300 400 180 240 320 180 1100-AOÄ93
60 60 150 150 50 99 124 36 69 86 66.5 91.4 124.7 200 §  1100-AOÄ93
100 125 250 300 400 600 900 73 142 176 241 330 450 67 129 163 244 348 433 350 1100-BOÄ93
125 150 350 400 500 700 1000 93 186 236 287 340 500 81 161 189 275 381 519 450 1100-COÄ93
200 250 500 600 800 1100 1600 200 400 500 125 250 310 410 570 775 610 ‡  1100-DOÄ93
  

3-Phase, 3300V Maximum (Requires Insulation Barrier)

3300V AC Insulating Barriers (180… 450 A Only) — The ratings of the listed vacuum contactors can be increased to 3300V by replacing the standard safety shield. The replacement insulating barrier provides 3.3 kV line and load terminal isolation. Ratings change as indicated in the table below with the addition of this insulating barrier to listed contactors:

Horsepower Ratings kW Ratings Continuous
Current
Rating [A]
Cat. No.
Motor Voltage
2400V 3000V 3300V 2400V 3000V 3300V
3300V Insulating Barrier (Required to obtain ratings below) 1100M-N1
600 800 800 500 630 630 180 1100-AOÄ93
1200 1500 1500 1000 1250 1250 350 1100-BOÄ93
1500 2000 2000 1250 1500 1500 450 1100-COÄ93
  

Ä Coil Voltage Code

The cat. no. is incomplete. To complete the cat. no., select a coil voltage code from the table below and insert into the cat. no.
Example: Cat. No. 1100-AOÄ93 becomes Cat. No. 1100-AOD93.


  [V]‡  100…127 100…110 200…240 200…220 380…440 460…550
AC 50/60 Hz D A N B
DC G H
  
¬ Inrush current should be less than 1000% of IEC AC3 operational current.
T For use on transformers having an inrush not more than 20 times the rated full load current irrespective of secondary load. Ratings do not apply to transformers used in resistive welder service.
‡ Devices with a continuous current rating of 610 A must use the 100…127V and 200…240V coils only.
§ For 200V continuous rating.

Accessories

Accessories

Auxiliary Contacts

Contactors are supplied with two normally open and two normally closed auxiliary contacts as standard. Additional auxiliary contacts, two normally open and two normally closed, can be added in the field.

Auxiliary Contact (for 180…450 A devices)
    Cat. No. 1195-N1
Auxiliary Contact (for 610 A devices)
    Cat. No. 1195-N2

Contact Arrangements

Contact Arrangements

Click to enlarge - 1100-1_17-1

Approximate Dimensions

Click to enlarge - 1100_dim