Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Vacuum Contactors and Starters > Bulletin 1109 Non-Reversing Vacuum Starter
Bulletin 1109 Non-Reversing Vacuum Starter
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Vacuum Starter | Product Selection | Accessories | Specifications | Approximate Dimensions |
| Build a Catalog Number |
3-Phase, 200…1500V, 60 Hz
| Motor Switching Ratings | |||||||||||||
| 200…208V | 220…240V | 440…480V | 550…600V | 1000V | 1500V | Continuous Current Rating [A] | Cat. No. | ||||||
| [Hp] | [kW] | [Hp] | [kW] | [Hp] | [kW] | [Hp] | [kW] | [Hp] | [kW] | [Hp] | [kW] | ||
| 50 | 37 | 75 | 56 | 150 | 112 | 200 | 149 | 300 | 224 | 500 | 373 | 200 | 1109-BOÄ-µ |
| 125 | 93 | 150 | 112 | 300 | 224 | 350 | 261 | 700 | 522 | 850 | 634 | 400 | 1109-COÄ-µ |
| 200 | 149 | 200 | 149 | 400 | 298 | 600 | 447 | 1000 | 746 | 1200 | 895 | 600 | 1109-DOÄ-µ |
Ä Control Voltage Code
The cat. no. is incomplete. To complete the cat. no., select a control voltage code from the table below and insert into the cat. no.
Example: Cat. No. 1109-BOÄ becomes Cat. No. 1109-BOD.
| [V] | 120 | 125 | 240 | 250 | 380…415 | 440…480 | ||
| AC | 50/60 Hz | D | — | A | — | N | B | |
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from below to complete the cat. no. Example: Cat. No. 1109-BOD-µ becomes Cat. No. 1109-BOD-EEJ.