Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Combination Contactors, Starters, and Pump Control Panels > Bulletin 502
Bulletin 502
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Combination Starter | Product Selection | Modifications for Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
| Build a Catalog Number |
| NEMA Size |
Continuous Ampere Rating [A] |
Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Line Voltage [V] |
Fuse Clip Rating Amperes [A] Fuses not included. Select per NEC |
Type 1 General Purpose |
Type 3R/4/12 Rainproof, Waterproof, Dusttight |
Type 3R/4/12 Rainproof, Waterproof, Dusttight (Door Safety Hardware) |
Type 4/4X Watertight Corrosion- Resistant Stainless Steel |
Type 4/4X Watertight Corrosion- Resistant Non-metallic |
|||
| Motor Voltage | ||||||||||||
| 60 Hz | 60 Hz | 50 Hz | 60 Hz | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | ||||
| 200V | 230V | 380… 415V |
460… 575V |
|||||||||
| 0 | 18 | 3 | 3 | — | — | 208…240 | 30 | 502-AAÄ-24R | 502-AFÄ-24R | 502-AJÄ-24R | 502-ACÄ-24R | 502-ASÄ-24R |
| — | — | 5 | 5 | 480…600 | 30 | 502-AAÄ-24R | 502-AFÄ-24R | 502-AJÄ-24R | 502-ACÄ-24R | 502-ASÄ-24R | ||
| 1 | 27 | 7-1/2 | 7-1/2 | — | — | 208…240 | 30 | 502-BAÄ-24R | 502-BFÄ-24R | 502-BJÄ-24R | 502-BCÄ-24R | 502-BSÄ-24R |
| — | — | 10 | 10 | 480…600 | 30 | 502-BAÄ-24R | 502-BFÄ-24R | 502-BJÄ-24R | 502-BCÄ-24R | 502-BSÄ-24R | ||
| 7-1/2 | 7-1/2 | — | — | 208…240 | 60 | 502-BAÄ-25R | 502-BFÄ-25R | 502-BJÄ-25R | 502-BCÄ-25R | 502-BSÄ-25R | ||
| — | — | 10 | 10 | 480…600 | 60 | 502-BAÄ-25R | 502-BFÄ-25R | 502-BJÄ-25R | 502-BCÄ-25R | 502-BSÄ-25R | ||
| 2 | 45 | — | — | 25 | 25 | 480…600 | 30 | 502-CAÄ-24R | 502-CFÄ-24R | 502-CJÄ-24R | 502-CCÄ-24R | 502-CSÄ-24R |
| 10 | 15 | — | — | 208…240 | 60 | 502-CAÄ-25R | 502-CFÄ-25R | 502-CJÄ-25R | 502-CCÄ-25R | 502-CSÄ-25R | ||
| — | — | 25 | 25 | 480…600 | 60 | 502-CAÄ-25R | 502-CFÄ-25R | 502-CJÄ-25R | 502-CCÄ-25R | 502-CSÄ-25R | ||
| 10 | 15 | — | — | 208…240 | 100 | 502-CAÄ-26J | 502-CFÄ-26J | 502-CJÄ-26J | 502-CCÄ-26J | 502-CSÄ-26J | ||
| — | — | 25 | 25 | 480…600 | 100 | 502-CAÄ-26J | 502-CFÄ-26J | 502-CJÄ-26J | 502-CCÄ-26J | 502-CSÄ-26J | ||
| 3 | 90 | — | — | 50 | 50 | 480…600 | 60 | 502-DAÄ-25R | 502-DFÄ-25R | 502-DJÄ-25R | 502-DCÄ-25R | 502-DSÄ-25R |
| 25 | 30 | — | — | 208…240 | 100 | 502-DAÄ-26R | 502-DFÄ-26R | 502-DJÄ-26R | 502-DCÄ-26R | 502-DSÄ-26R | ||
| — | — | 50 | 50 | 480…600 | 100 | 502-DAÄ-26R | 502-DFÄ-26R | 502-DJÄ-26R | 502-DCÄ-26R | 502-DSÄ-26R | ||
| 25 | 30 | — | — | 208…240 | 200 | 502-DAÄ-27J | 502-DFÄ-27J | 502-DJÄ-27J | 502-DCÄ-27J | 502-DSÄ-27J | ||
| — | — | 50 | 50 | 480…600 | 200 | 502-DAÄ-27J | 502-DFÄ-27J | 502-DJÄ-27J | 502-DCÄ-27J | 502-DSÄ-27J | ||
| 4 | 135 | — | — | 75 | 100 | 480…600 | 100 | 502-EAÄ-26R | 502-EFÄ-26R | 502-EJÄ-26R | 502-ECÄ-26R | 502-ESÄ-26R |
| 40 | 50 | — | — | 208…240 | 200 | 502-EAÄ-27R | 502-EFÄ-27R | 502-EJÄ-27R | 502-ECÄ-27R | 502-ESÄ-27R | ||
| — | — | 75 | 100 | 480…600 | 200 | 502-EAÄ-27R | 502-EFÄ-27R | 502-EJÄ-27R | 502-ECÄ-27R | 502-ESÄ-27R | ||
| 40 | 50 | — | — | 208…240 | 400 | 502-EAÄ-28J | 502-EFÄ-28J | 502-EJÄ-28J | 502-ECÄ-28J | 502-ESÄ-28J | ||
| — | — | 75 | 100 | 480…600 | 400 | 502-EAÄ-28J | 502-EFÄ-28J | 502-EJÄ-28J | 502-ECÄ-28J | 502-ESÄ-28J | ||
| 5 | 270 | 40 | 50 | — | — | 208…240 | 200 | 502-FAÄ-27R | 502-FFÄ-27R | 502-FJÄ-27R | 502-FCÄ-27R | 502-FSÄ-27R |
| — | — | 75 | 100 | 480…600 | 200 | 502-FAÄ-27R | 502-FFÄ-27R | 502-FJÄ-27R | 502-FCÄ-27R | 502-FSÄ-27R | ||
| 75 | 100 | 150 | 200 | 208…600 | 400 | 502-FAÄ-28R | 502-FFÄ-28R | 502-FJÄ-28R | 502-FCÄ-28R | 502-FSÄ-28R | ||
| — | — | 150 | 200 | 480…600 | 400 | 502-FAÄ-28R | 502-FFÄ-28R | 502-FJÄ-28R | 502-FCÄ-28R | 502-FSÄ-28R | ||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 502-AAÄ-24R becomes Cat. No. 502-AAB-24R. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 208 | 230…240 | 460…480 | 575…600 | ||
| Common Control | AC, 60 Hz |
H | A | B | C | |
| Transformer Control (See Configuration of a Basic Combination Starter Note) | ||||||
| 120V Separate Control (without transformer) | AD | AD | CD | CD | ||
¬ Non-Fusible Disconnect Type
Cat. nos. listed above include a fusible disconnect switch with Class R or J fuse clips. To order a non-fusible disconnect switch, eliminate the fuse clip code from the cat. no. Example: Cat. No. 502-BFB-24R becomes Cat. No. 502-BFB.
T Class H fuse clips can be supplied. Example: Cat. No. 502-AAÄ-24R becomes Cat. No. 502-AAÄ-24. Class J fuse clips can be supplied. Example: Cat. No. 502-AAÄ-24R becomes Cat. No. 502-AAÄ-24J. Class HRC form II fuse clips can be supplied. Example: Cat. No. 502-AAÄ-24R becomes Cat. No. 502-AAÄ-24E.