Combination Contactors, Starters, and Pump Control Panels

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Combination Contactors, Starters, and Pump Control Panels > Bulletin 507 Reversing Circuit Breaker Type

Bulletin 507 Reversing Circuit Breaker Type

Introduction Standards Compliance and Certifications Configuration of a Basic Combination Starter Product Selection Modifications for Combination Devices
Accessories Specifications Full Load Motor Currents Approximate Dimensions Renewal Parts
Product Selection

Build a Catalog Number


Heater Elements — Starters with eutectic alloy overload relay require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA
Size
Continuous
Ampere
Rating [A]§ 
Maximum Horsepower Rating
Full Load Current Must Not Exceed
Continuous Ampere Rating
Type 1
General
Purpose
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
(Door Safety
Hardware)
Type 4/4X
Watertight
Corrosion
Resistant
Stainless Steel
Motor Voltage
200V 230V 460V 575V Cat. No.⋆ ‡  Cat. No.⋆ ‡  Cat. No.⋆ ‡  Cat. No.⋆ ‡ 
0 18 0…1/3 0…1/3 507-AAÄ-µ-32 507-AFÄ-µ-32 507-AJÄ-µ-32 507-ACÄ-µ-32
1/2…1 1/2…1 0…1 0…1 507-AAÄ-µ-35 507-AFÄ-µ-35 507-AJÄ-µ-35 507-ACÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 507-AAÄ-µ-38 507-AFÄ-µ-38 507-AJÄ-µ-38 507-ACÄ-µ-38
5 5 507-AAÄ-µ-39 507-AFÄ-µ-39 507-AJÄ-µ-39 507-ACÄ-µ-39
1 27 0…1/3 0…1/3 507-BAÄ-µ-32 507-BFÄ-µ-32 507-BJÄ-µ-32 507-BCÄ-µ-32
1/2…1 1/2…1 0…1 0…1 507-BAÄ-µ-35 507-BFÄ-µ-35 507-BJÄ-µ-35 507-BCÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 507-BAÄ-µ-38 507-BFÄ-µ-38 507-BJÄ-µ-38 507-BCÄ-µ-38
5 507-BAÄ-µ-39 507-BFÄ-µ-39 507-BJÄ-µ-39 507-BCÄ-µ-39
7-1/2 5…7-1/2 5…7-1/2 5…7-1/2 507-BAÄ-µ-40 507-BFÄ-µ-40 507-BJÄ-µ-40 507-BCÄ-µ-40
10 10 507-BAÄ-µ-41 507-BFÄ-µ-41 507-BJÄ-µ-41 507-BCÄ-µ-41
2 45 10 10 507-CAÄ-µ-41 507-CFÄ-µ-41 507-CJÄ-µ-41 507-CCÄ-µ-41
15 15 15 507-CAÄ-µ-42 507-CFÄ-µ-42 507-CJÄ-µ-42 507-CCÄ-µ-42
20…25 20…25 507-CAÄ-µ-44 507-CFÄ-µ-44 507-CJÄ-µ-44 507-CCÄ-µ-44
3 90 15…25 20…25 507-DAÄ-µ-44 507-DFÄ-µ-44 507-DJÄ-µ-44 507-DCÄ-µ-44
30 30 507-DAÄ-µ-45 507-DFÄ-µ-45 507-DJÄ-µ-45 507-DCÄ-µ-45
30…50 40…50 507-DAÄ-µ-47 507-DFÄ-µ-47 507-DJÄ-µ-47 507-DCÄ-µ-47
4 135 30 507-EAÄ-µ-45 507-EFÄ-µ-45 507-EJÄ-µ-45 507-ECÄ-µ-45
40 40 507-EAÄ-µ-46 507-EFÄ-µ-46 507-EJÄ-µ-46 507-ECÄ-µ-46
50 507-EAÄ-µ-47 507-EFÄ-µ-47 507-EJÄ-µ-47 507-ECÄ-µ-47
60 507-EAÄ-µ-48 507-EFÄ-µ-48 507-EJÄ-µ-48 507-ECÄ-µ-48
60…75 507-EAÄ-µ-49 507-EFÄ-µ-49 507-EJÄ-µ-49 507-ECÄ-µ-49
100 75…100 507-EAÄ-µ-50 507-EFÄ-µ-50 507-EJÄ-µ-50 507-ECÄ-µ-50
5 270 50…60 60 507-FAÄ-µ-48 507-FFÄ-µ-48 507-FJÄ-µ-48 507-FCÄ-µ-48
75 507-FAÄ-µ-49 507-FFÄ-µ-49 507-FJÄ-µ-49 507-FCÄ-µ-49
75…100 507-FAÄ-µ-50 507-FFÄ-µ-50 507-FJÄ-µ-50 507-FCÄ-µ-50
125 507-FAÄ-µ-51 507-FFÄ-µ-51 507-FJÄ-µ-51 507-FCÄ-µ-51
125…150 150 507-FAÄ-µ-52 507-FFÄ-µ-52 507-FJÄ-µ-52 507-FCÄ-µ-52
200 200 507-FAÄ-µ-54 507-FFÄ-µ-54 507-FJÄ-µ-54 507-FCÄ-µ-54
  

⋆ Bulletin 507 Narrow Enclosure — Sizes 0 & 1 are supplied in a (30 in. H x 20 in. W) enclosure. If a narrow enclosure (27 in. H x 10 in. W) is required, add the letter X to the Bulletin Number (507X).
‡ To order Visa-Window Breakers for certain mining applications (Canada only), add the letter V to the cat. no. Example: Cat. No. 507-BAÄ-µ-35V.
§ When controlling high efficiency motors – consult your local Rockwell Automation sales office or Allen-Bradley distributor for proper circuit breaker selection.


Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 507-BAÄ-µ-35 becomes Cat. No. 507-BAB-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) AD AD CD CD
  

µ Overload Relay Code

Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Single-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no.
Example: Cat. No. 507-BAB-µ-35 becomes Cat. No. 507-BAB-A2E-35.


Heater Elements — Starters with eutectic alloy overload relay require 3 heater elements. Located on Bulletin 592.
NEMA
Size
Continuous
Ampere
Rating [A]§ 
Maximum Horsepower Rating
Full Load Current Must Not Exceed
Continuous Ampere Rating
Type 3R, 7 & 9 Bolted
Class I, Groups C & D
Class II, Groups E, F & G
– Divisions 1 & 2 –
Type 7 & 9
Bolted
Class I, Groups C & D
Class II, Groups E, F & G
– Divisions 1 & 2 –
Motor Voltage
200V 230V 460V 575V Cat. No.⋆ ‡  Cat. No.‡ 
0 18 0…1/3 0…1/3 507-AHÄ-µ-32 507-AEÄ-µ-32
1/2…1 1/2…1 0…1 0…1 507-AHÄ-µ-35 507-AEÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 507-AHÄ-µ-38 507-AEÄ-µ-38
5 5 507-AHÄ-µ-39 507-AEÄ-µ-39
1 27 0…1/3 0…1/3 507-BHÄ-µ-32 507-BEÄ-µ-32
1/2…1 1/2…1 0…1 0…1 507-BHÄ-µ-35 507-BEÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 507-BHÄ-µ-38 507-BEÄ-µ-38
5 507-BHÄ-µ-39 507-BEÄ-µ-39
7-1/2 5…7-1/2 5…7-1/2 5…7-1/2 507-BHÄ-µ-40 507-BEÄ-µ-40
10 10 507-BHÄ-µ-41 507-BEÄ-µ-41
2 45 10 10 507-CHÄ-µ-41 507-CEÄ-µ-41
15 15 15 507-CHÄ-µ-42 507-CEÄ-µ-42
20…25 20…25 507-CHÄ-µ-44 507-CEÄ-µ-44
3 90 15…25 20…25 507-DHÄ-µ-44 507-DEÄ-µ-44
30 30 507-DHÄ-µ-45 507-DEÄ-µ-45
30…50 40…50 507-DHÄ-µ-47 507-DEÄ-µ-47
4 135 30 507-EHÄ-µ-45 507-EEÄ-µ-45
40 40 507-EHÄ-µ-46 507-EEÄ-µ-46
50 507-EHÄ-µ-47 507-EEÄ-µ-47
60 507-EHÄ-µ-48 507-EEÄ-µ-48
60…75 507-EHÄ-µ-49 507-EEÄ-µ-49
75…100 507-EHÄ-µ-50 507-EEÄ-µ-50
  

⋆ Includes drain and cover with gasket.
‡ To order Visa-Window Breakers for certain mining applications (Canada only), add the letter V to the cat. no. Example: Cat. No. 507-BHÄ-µ-35V.
§ When controlling high efficiency motors – consult your local Rockwell Automation sales office or Allen-Bradley distributor for proper circuit breaker selection.


Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 507-BEÄ-µ-35 becomes Cat. No. 507-BEB-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) AD AD CD CD
  

µ Overload Relay Code

Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Three-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no.
Example: Cat. No. 507-BHB-µ-35 becomes Cat. No. 507-BHB-A2E-35.