Bulletin 513 Non-Reversing Circuit Breaker Type

Introduction Standards Compliance and Certifications Configuration of a Basic Combination Starter Product Selection Modifications for Combination Devices
Accessories Specifications Full Load Motor Currents Approximate Dimensions Renewal Parts
Product Selection

Build a Catalog Number


Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA Size Continuous Ampere Rating [A]‡  Maximum Horsepower Rating
Full Load Current Must Not Exceed
Continuous Ampere Rating
Type 1
General
Purpose
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
(Door Safety
Hardware)
Type 4/4X
Watertight
Corrosion-
Resistant
Stainless Steel
Type 4/4X
Watertight
Corrosion-
Resistant
Non-metallic
Motor Voltages
200V 230V 460V 575V Cat. No.¬ T  Cat. No.¬ T  Cat. No.¬ T  Cat. No.¬ T  Cat. No.¬ T 
0 18 0…1/3 0…1/3 513-AAÄ-µ-32 513-AFÄ-µ-32 513-AJÄ-µ-32 513-ACÄ-µ-32 513-ASÄ-µ-32
1/2…1 1/2…1 0…1 0…1 513-AAÄ-µ-35 513-AFÄ-µ-35 513-AJÄ-µ-35 513-ACÄ-µ-35 513-ASÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 513-AAÄ-µ-38 513-AFÄ-µ-38 513-AJÄ-µ-38 513-ACÄ-µ-38 513-ASÄ-µ-38
5 5 513-AAÄ-µ-39 513-AFÄ-µ-39 513-AJÄ-µ-39 513-ACÄ-µ-39 513-ASÄ-µ-39
1 27 0…1/3 0…1/3 513-BAÄ-µ-32 513-BFÄ-µ-32 513-BJÄ-µ-32 513-BCÄ-µ-32 513-BSÄ-µ-32
1/2…1 1/2…1 0…1 0…1 513-BAÄ-µ-35 513-BFÄ-µ-35 513-BJÄ-µ-35 513-BCÄ-µ-35 513-BSÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 513-BAÄ-µ-38 513-BFÄ-µ-38 513-BJÄ-µ-38 513-BCÄ-µ-38 513-BSÄ-µ-38
5 513-BAÄ-µ-39 513-BFÄ-µ-39 513-BJÄ-µ-39 513-BCÄ-µ-39 513-BSÄ-µ-39
7-1/2 5…7-1/2 5…7-1/2 5…7-1/2 513-BAÄ-µ-40 513-BFÄ-µ-40 513-BJÄ-µ-40 513-BCÄ-µ-40 513-BSÄ-µ-40
10 10 513-BAÄ-µ-41 513-BFÄ-µ-41 513-BJÄ-µ-41 513-BCÄ-µ-41 513-BSÄ-µ-41
2 45 10 10 513-CAÄ-µ-41 513-CFÄ-µ-41 513-CJÄ-µ-41 513-CCÄ-µ-41 513-CSÄ-µ-41
15 15 15 513-CAÄ-µ-42 513-CFÄ-µ-42 513-CJÄ-µ-42 513-CCÄ-µ-42 513-CSÄ-µ-42
20…25 20…25 513-CAÄ-µ-44 513-CFÄ-µ-44 513-CJÄ-µ-44 513-CCÄ-µ-44 513-CSÄ-µ-44
  
¬ To order starters (0 through 4) with current limiters, add the letter “C” at the end of the listed Cat. No. Example: Cat. No. 513-AAÄ-µ-35C.
T To order Visa-Window Breakers for certain mining applications (Canada only), add the letter “V” to the Cat. No. Example: Cat. No. 513-BAÄ-µ-35V.
‡ When controlling high efficiency motors – consult your local Allen-Bradley distributor for proper circuit breaker selection.

Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 513-BAÄ-µ-35 becomes Cat. No. 513-BAB-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) HD AD BD CD
  

µ Overload Relay Code

Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset)
to complete the cat. no.
Example: Cat. No. 513-BAB-32 becomes Cat. No. 513-BAB-A2F-32.


Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA Size Continuous Ampere Rating [A]‡  Maximum Horsepower Rating
Full Load Current Must Not Exceed
Continuous Ampere Rating
Hazardous Locations
Motor Voltage Type 1
General Purpose
Type 3R/4/12
Rainproof, Waterproof, Dustlight
Type 3R/4/12
Rainproof, Waterproof, Dustlight (Door Safety Hardware)
Type 4/4X
Watertight Corrosion-Resistant Stainless Steel
Type 4/4X
Watertight Corrosion-Resistant Non-metallic
200V 230V 460V 575V Cat. No.¬ T  Cat. No.¬ T  Cat. No.¬ T  Cat. No.¬ T  Cat. No.¬ T 
3 90 15…25 20…25 513-DAÄ-µ-44 513-DFÄ-µ-44 513-DJÄ-µ-44 513-DCÄ-µ-44 513-DSÄ-µ-44
30 30 513-DAÄ-µ-45 513-DFÄ-µ-45 513-DJÄ-µ-45 513-DCÄ-µ-45 513-DSÄ-µ-45
30…50 40…50 513-DAÄ-µ-47 513-DFÄ-µ-47 513-DJÄ-µ-47 513-DCÄ-µ-47 513-DSÄ-µ-47
4 135 30 513-EAÄ-µ-45 513-EFÄ-µ-45 513-EJÄ-µ-45 513-ECÄ-µ-45 513-ESÄ-µ-45
40 40 513-EAÄ-µ-46 513-EFÄ-µ-46 513-EJÄ-µ-46 513-ECÄ-µ-46 513-ESÄ-µ-46
50 513-EAÄ-µ-47 513-EFÄ-µ-47 513-EJÄ-µ-47 513-ECÄ-µ-47 513-ESÄ-µ-47
60 513-EAÄ-µ-48 513-EFÄ-µ-48 513-EJÄ-µ-48 513-ECÄ-µ-48 513-ESÄ-µ-48
60…75 513-EAÄ-µ-49 513-EFÄ-µ-49 513-EJÄ-µ-49 513-ECÄ-µ-49 513-ESÄ-µ-49
100 75…100 513-EAÄ-µ-50 513-EFÄ-µ-50 513-EJÄ-µ-50 513-ECÄ-µ-50 513-ESÄ-µ-50
5 270 50…60 513-FAÄ-µ-48 513-FFÄ-µ-48 513-FJÄ-µ-48 513-FCÄ-µ-48 513-FSÄ-µ-48
75 60…75 513-FAÄ-µ-49 513-FFÄ-µ-49 513-FJÄ-µ-49 513-FCÄ-µ-49 513-FSÄ-µ-49
100 513-FAÄ-µ-50 513-FFÄ-µ-50 513-FJÄ-µ-50 513-FCÄ-µ-50 513-FSÄ-µ-50
125 513-FAÄ-µ-51 513-FFÄ-µ-51 513-FJÄ-µ-51 513-FCÄ-µ-51 513-FSÄ-µ-51
125…150 513-FAÄ-µ-52 513-FFÄ-µ-52 513-FJÄ-µ-52 513-FCÄ-µ-52 513-FSÄ-µ-52
200 150…200 513-FAÄ-µ-54 513-FFÄ-µ-54 513-FJÄ-µ-54 513-FCÄ-µ-54 513-FSÄ-µ-54
6 540 100 513-GFÄ-µ-50T 513-GCÄ-µ-50T
125 125 513-GFÄ-µ-51T 513-GCÄ-µ-51T
150 150 513-GFÄ-µ-52T 513-GCÄ-µ-52T
200 513-GFÄ-µ-54T 513-GCÄ-µ-54T
250 250 513-GFÄ-µ-56T 513-GCÄ-µ-56T
300 300 513-GFÄ-µ-57T 513-GCÄ-µ-57T
350 513-GFÄ-µ-58T 513-GCÄ-µ-58T
513-GFÄ-µ-59T 513-GCÄ-µ-59T
7 810 250 513-HFÄ-µ-56T
300 513-HFÄ-µ-57T
450…500 513-HFÄ-µ-61T
450…600 513-HFÄ-µ-62T
  
¬ For Type 3R applications it is necessary that a drain or breather and drain fitting be added to the enclosure.
T To order Visa-Window Breakers for certain mining applications (Canada only), add the letter “V” to the Cat. No. Example: Cat. No. 513-BUÄ-µ-35V.
‡ When controlling high efficiency motors – consult your local Allen-Bradley distributor for proper circuit breaker selection.

Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 513-BUÄ-µ-35 becomes Cat. No. 513-BUA-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) HD AD BD CD
  

µ Overload Relay Code

Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset)
to complete the cat. no.
Example: Cat. No. 513-BAB-µ-32 becomes Cat. No. 513-BAB-A2F-32.


Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA Size Continuous Ampere Rating [A]Ø  Maximum Horsepower Rating
Full Load Current Must Not Exceed
Continuous Ampere Rating
Hazardous Locations
Unilock Enclosure Bolted Enclosure
Motor Voltage Type 3R/7 & 9
Class I, Groups C & D
Class II, Groups E, F & G

– Divisions 1 & 2 –
Type 7 & 9
Class I, Groups C & D
Class II, Groups E, F & G

– Divisions 1 & 2 –
Type 3R/7 & 9
Class I, Groups C & D
Class II, Groups E, F & G

– Divisions 1 & 2 –
200V 230V 460V 575V Cat. No.¬ T  Cat. No.T  Cat. No.¬ T ‡ 
0 18 0…1/3 0…1/3 513-AUÄ-µ-32 513-AEÄ-µ-32 513-AHÄ-µ-32
1/2…1 1/2…1 0…1 0…1 513-AUÄ-µ-35 513-AEÄ-µ-35 513-AHÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 513-AUÄ-µ-38 513-AEÄ-µ-38 513-AHÄ-µ-38
5 5 513-AUÄ-µ-39 513-AEÄ-µ-39 513-AHÄ-µ-39
1 27 0…1/3 0…1/3 513-BUÄ-µ-32 513-BEÄ-µ-32 513-BHÄ-µ-32
1/2…1 1/2…1 0…1 0…1 513-BUÄ-µ-35 513-BEÄ-µ-35 513-BHÄ-µ-35
1-1/2…3 1-1/2…3 1-1/2…3 1-1/2…3 513-BUÄ-µ-38 513-BEÄ-µ-38 513-BHÄ-µ-38
5 513-BUÄ-µ-39 513-BEÄ-µ-39 513-BHÄ-µ-39
7-1/2 5…7-1/2 5…7-1/2 5…7-1/2 513-BUÄ-µ-40 513-BEÄ-µ-40 513-BHÄ-µ-40
10 10 513-BUÄ-µ-41 513-BEÄ-µ-41 513-BHÄ-µ-41
2 45 10 10 513-CUÄ-µ-41 513-CEÄ-µ-41 513-CHÄ-µ-41
15 15 15 513-CUÄ-µ-42 513-CEÄ-µ-42 513-CHÄ-µ-42
20…25 20…25 513-CUÄ-µ-44 513-CEÄ-µ-44 513-CHÄ-µ-44
3 90 15…25 20…25 513-DUÄ-µ-44 513-DEÄ-µ-44 513-DHÄ-µ-44
30 30 513-DUÄ-µ-45 513-DEÄ-µ-45 513-DHÄ-µ-45
30…50 40…50 513-DUÄ-µ-47 513-DEÄ-µ-47 513-DHÄ-µ-47
4 135 30 513-EUÄ-µ-45 513-EEÄ-µ-45 513-EHÄ-µ-45
40 40 513-EUÄ-µ-46 513-EEÄ-µ-46 513-EHÄ-µ-46
50 513-EUÄ-µ-47 513-EEÄ-µ-47 513-EHÄ-µ-47
60 513-EUÄ-µ-48 513-EEÄ-µ-48 513-EHÄ-µ-48
60…75 513-EUÄ-µ-49 513-EEÄ-µ-49 513-EHÄ-µ-49
100 75…100 513-EUÄ-µ-50 513-EEÄ-µ-50 513-EHÄ-µ-50
5 270§  50…60 50…60 50…60 50…60 513-FUÄ-µ-48 513-FEÄ-µ-48 513-FHÄ-µ-48
75 60…75 513-FUÄ-µ-49 513-FEÄ-µ-49 513-FHÄ-µ-49
100 513-FUÄ-µ-50 513-FEÄ-µ-50 513-FHÄ-µ-50
125 513-FUÄ-µ-51 513-FEÄ-µ-51 513-FHÄ-µ-51
125…150§  513-FUÄ-µ-52 513-FEÄ-µ-52 513-FHÄ-µ-52
200 150…200 513-FUÄ-µ-54 513-FEÄ-µ-54 513-FHÄ-µ-54
  
¬ For Type 3R applications it is necessary that a drain or breather and drain fitting be added to the enclosure.
T To order Visa-Window Breakers for certain mining applications (Canada only), add the letter “V” to the Cat. No. Example: Cat. No. 513-BUÄ-µ-35V.
‡ Includes drain and cover with gasket.
§ NEMA size 5 Unilock enclosed starters have a continuous ampere rating of 210 A.
§ Bolted Enclosure suitable for use on motors from 125…200 HP, 460V.
Ø When controlling high efficiency motors – consult your local Allen-Bradley distributor for proper circuit breaker selection.

Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 513-BUÄ-µ-35 becomes Cat. No. 513-BUA-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) HD AD BD CD
  

µ Overload Relay Code

Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset)
to complete the cat. no.
Example: Cat. No. 513-BUB-µ-35 becomes Cat. No. 513-BUB-A2D-35.