Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Combination Contactors, Starters, and Pump Control Panels > Bulletin 513 Non-Reversing Circuit Breaker Type
Bulletin 513 Non-Reversing Circuit Breaker Type
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Combination Starter | Product Selection | Modifications for Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
| Build a Catalog Number |
| Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements. | ||||||||||
| NEMA Size | Continuous Ampere Rating [A] | Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Type 1 General Purpose |
Type 3R/4/12 Rainproof, Waterproof, Dusttight |
Type 3R/4/12 Rainproof, Waterproof, Dusttight (Door Safety Hardware) |
Type 4/4X Watertight Corrosion- Resistant Stainless Steel |
Type 4/4X Watertight Corrosion- Resistant Non-metallic |
|||
| Motor Voltages | ||||||||||
| 200V | 230V | 460V | 575V | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | ||
| 0 | 18 | 0…1/3 | 0…1/3 | — | — | 513-AAÄ-µ-32 | 513-AFÄ-µ-32 | 513-AJÄ-µ-32 | 513-ACÄ-µ-32 | 513-ASÄ-µ-32 |
| 1/2…1 | 1/2…1 | 0…1 | 0…1 | 513-AAÄ-µ-35 | 513-AFÄ-µ-35 | 513-AJÄ-µ-35 | 513-ACÄ-µ-35 | 513-ASÄ-µ-35 | ||
| 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 513-AAÄ-µ-38 | 513-AFÄ-µ-38 | 513-AJÄ-µ-38 | 513-ACÄ-µ-38 | 513-ASÄ-µ-38 | ||
| — | — | 5 | 5 | 513-AAÄ-µ-39 | 513-AFÄ-µ-39 | 513-AJÄ-µ-39 | 513-ACÄ-µ-39 | 513-ASÄ-µ-39 | ||
| 1 | 27 | 0…1/3 | 0…1/3 | — | — | 513-BAÄ-µ-32 | 513-BFÄ-µ-32 | 513-BJÄ-µ-32 | 513-BCÄ-µ-32 | 513-BSÄ-µ-32 |
| 1/2…1 | 1/2…1 | 0…1 | 0…1 | 513-BAÄ-µ-35 | 513-BFÄ-µ-35 | 513-BJÄ-µ-35 | 513-BCÄ-µ-35 | 513-BSÄ-µ-35 | ||
| 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 513-BAÄ-µ-38 | 513-BFÄ-µ-38 | 513-BJÄ-µ-38 | 513-BCÄ-µ-38 | 513-BSÄ-µ-38 | ||
| 5 | — | — | — | 513-BAÄ-µ-39 | 513-BFÄ-µ-39 | 513-BJÄ-µ-39 | 513-BCÄ-µ-39 | 513-BSÄ-µ-39 | ||
| 7-1/2 | 5…7-1/2 | 5…7-1/2 | 5…7-1/2 | 513-BAÄ-µ-40 | 513-BFÄ-µ-40 | 513-BJÄ-µ-40 | 513-BCÄ-µ-40 | 513-BSÄ-µ-40 | ||
| — | — | 10 | 10 | 513-BAÄ-µ-41 | 513-BFÄ-µ-41 | 513-BJÄ-µ-41 | 513-BCÄ-µ-41 | 513-BSÄ-µ-41 | ||
| 2 | 45 | 10 | 10 | — | — | 513-CAÄ-µ-41 | 513-CFÄ-µ-41 | 513-CJÄ-µ-41 | 513-CCÄ-µ-41 | 513-CSÄ-µ-41 |
| — | 15 | 15 | 15 | 513-CAÄ-µ-42 | 513-CFÄ-µ-42 | 513-CJÄ-µ-42 | 513-CCÄ-µ-42 | 513-CSÄ-µ-42 | ||
| — | — | 20…25 | 20…25 | 513-CAÄ-µ-44 | 513-CFÄ-µ-44 | 513-CJÄ-µ-44 | 513-CCÄ-µ-44 | 513-CSÄ-µ-44 | ||
| ¬ To order starters (0 through 4) with current limiters, add the letter C at the end of the listed Cat. No. Example: Cat. No. 513-AAÄ-µ-35C. | ||||||||||
| T To order Visa-Window Breakers for certain mining applications (Canada only), add the letter V to the Cat. No. Example: Cat. No. 513-BAÄ-µ-35V. | ||||||||||
| When controlling high efficiency motors consult your local Allen-Bradley distributor for proper circuit breaker selection. | ||||||||||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 513-BAÄ-µ-35 becomes Cat. No. 513-BAB-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 208 | 230…240 | 460…480 | 575…600 | ||
| Common Control | AC, 60 Hz | H | A | B | C | |
| Transformer Control (See Configuration of a Basic Combination Starter Note) | ||||||
| 120V Separate Control (without transformer) | HD | AD | BD | CD | ||
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no.
Example: Cat. No. 513-BAB-32 becomes Cat. No. 513-BAB-A2F-32.
| Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements. | ||||||||||
| NEMA Size | Continuous Ampere Rating [A] | Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Hazardous Locations | |||||||
| Motor Voltage | Type 1 General Purpose |
Type 3R/4/12 Rainproof, Waterproof, Dustlight |
Type 3R/4/12 Rainproof, Waterproof, Dustlight (Door Safety Hardware) |
Type 4/4X Watertight Corrosion-Resistant Stainless Steel |
Type 4/4X Watertight Corrosion-Resistant Non-metallic |
|||||
| 200V | 230V | 460V | 575V | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | Cat. No.¬ T | ||
| 3 | 90 | 15…25 | 20…25 | — | — | 513-DAÄ-µ-44 | 513-DFÄ-µ-44 | 513-DJÄ-µ-44 | 513-DCÄ-µ-44 | 513-DSÄ-µ-44 |
| — | 30 | — | 30 | 513-DAÄ-µ-45 | 513-DFÄ-µ-45 | 513-DJÄ-µ-45 | 513-DCÄ-µ-45 | 513-DSÄ-µ-45 | ||
| — | — | 30…50 | 40…50 | 513-DAÄ-µ-47 | 513-DFÄ-µ-47 | 513-DJÄ-µ-47 | 513-DCÄ-µ-47 | 513-DSÄ-µ-47 | ||
| 4 | 135 | 30 | — | — | — | 513-EAÄ-µ-45 | 513-EFÄ-µ-45 | 513-EJÄ-µ-45 | 513-ECÄ-µ-45 | 513-ESÄ-µ-45 |
| 40 | 40 | — | — | 513-EAÄ-µ-46 | 513-EFÄ-µ-46 | 513-EJÄ-µ-46 | 513-ECÄ-µ-46 | 513-ESÄ-µ-46 | ||
| — | 50 | — | — | 513-EAÄ-µ-47 | 513-EFÄ-µ-47 | 513-EJÄ-µ-47 | 513-ECÄ-µ-47 | 513-ESÄ-µ-47 | ||
| — | — | — | 60 | 513-EAÄ-µ-48 | 513-EFÄ-µ-48 | 513-EJÄ-µ-48 | 513-ECÄ-µ-48 | 513-ESÄ-µ-48 | ||
| — | — | 60…75 | — | 513-EAÄ-µ-49 | 513-EFÄ-µ-49 | 513-EJÄ-µ-49 | 513-ECÄ-µ-49 | 513-ESÄ-µ-49 | ||
| — | — | 100 | 75…100 | 513-EAÄ-µ-50 | 513-EFÄ-µ-50 | 513-EJÄ-µ-50 | 513-ECÄ-µ-50 | 513-ESÄ-µ-50 | ||
| 5 | 270 | 50…60 | — | — | — | 513-FAÄ-µ-48 | 513-FFÄ-µ-48 | 513-FJÄ-µ-48 | 513-FCÄ-µ-48 | 513-FSÄ-µ-48 |
| 75 | 60…75 | — | — | 513-FAÄ-µ-49 | 513-FFÄ-µ-49 | 513-FJÄ-µ-49 | 513-FCÄ-µ-49 | 513-FSÄ-µ-49 | ||
| — | 100 | — | — | 513-FAÄ-µ-50 | 513-FFÄ-µ-50 | 513-FJÄ-µ-50 | 513-FCÄ-µ-50 | 513-FSÄ-µ-50 | ||
| — | — | — | 125 | 513-FAÄ-µ-51 | 513-FFÄ-µ-51 | 513-FJÄ-µ-51 | 513-FCÄ-µ-51 | 513-FSÄ-µ-51 | ||
| — | — | 125…150 | — | 513-FAÄ-µ-52 | 513-FFÄ-µ-52 | 513-FJÄ-µ-52 | 513-FCÄ-µ-52 | 513-FSÄ-µ-52 | ||
| — | — | 200 | 150…200 | 513-FAÄ-µ-54 | 513-FFÄ-µ-54 | 513-FJÄ-µ-54 | 513-FCÄ-µ-54 | 513-FSÄ-µ-54 | ||
| 6 | 540 | 100 | — | — | — | — | 513-GFÄ-µ-50T | — | 513-GCÄ-µ-50T | — |
| 125 | 125 | — | — | — | 513-GFÄ-µ-51T | — | 513-GCÄ-µ-51T | — | ||
| 150 | 150 | — | — | — | 513-GFÄ-µ-52T | — | 513-GCÄ-µ-52T | — | ||
| — | 200 | — | — | — | 513-GFÄ-µ-54T | — | 513-GCÄ-µ-54T | — | ||
| — | — | 250 | 250 | — | 513-GFÄ-µ-56T | — | 513-GCÄ-µ-56T | — | ||
| — | — | 300 | 300 | — | 513-GFÄ-µ-57T | — | 513-GCÄ-µ-57T | — | ||
| — | — | — | 350 | — | 513-GFÄ-µ-58T | — | 513-GCÄ-µ-58T | — | ||
| — | — | — | — | — | 513-GFÄ-µ-59T | — | 513-GCÄ-µ-59T | — | ||
| 7 | 810 | — | 250 | — | — | — | 513-HFÄ-µ-56T | — | — | — |
| — | 300 | — | — | — | 513-HFÄ-µ-57T | — | — | — | ||
| — | — | 450…500 | — | — | 513-HFÄ-µ-61T | — | — | — | ||
| — | — | — | 450…600 | — | 513-HFÄ-µ-62T | — | — | — | ||
| ¬ For Type 3R applications it is necessary that a drain or breather and drain fitting be added to the enclosure. | ||||||||||
| T To order Visa-Window Breakers for certain mining applications (Canada only), add the letter V to the Cat. No. Example: Cat. No. 513-BUÄ-µ-35V. | ||||||||||
| When controlling high efficiency motors consult your local Allen-Bradley distributor for proper circuit breaker selection. | ||||||||||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 513-BUÄ-µ-35 becomes Cat. No. 513-BUA-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 208 | 230…240 | 460…480 | 575…600 | ||
| Common Control | AC, 60 Hz | H | A | B | C | |
| Transformer Control (See Configuration of a Basic Combination Starter Note) | ||||||
| 120V Separate Control (without transformer) | HD | AD | BD | CD | ||
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no.
Example: Cat. No. 513-BAB-µ-32 becomes Cat. No. 513-BAB-A2F-32.
| Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements. | ||||||||
| NEMA Size | Continuous Ampere Rating [A]Ø | Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Hazardous Locations | |||||
| Unilock Enclosure | Bolted Enclosure | |||||||
| Motor Voltage | Type 3R/7 & 9 Class I, Groups C & D Class II, Groups E, F & G Divisions 1 & 2 |
Type 7 & 9 Class I, Groups C & D Class II, Groups E, F & G Divisions 1 & 2 |
Type 3R/7 & 9 Class I, Groups C & D Class II, Groups E, F & G Divisions 1 & 2 |
|||||
| 200V | 230V | 460V | 575V | Cat. No.¬ T | Cat. No.T | Cat. No.¬ T | ||
| 0 | 18 | 0…1/3 | 0…1/3 | — | — | 513-AUÄ-µ-32 | 513-AEÄ-µ-32 | 513-AHÄ-µ-32 |
| 1/2…1 | 1/2…1 | 0…1 | 0…1 | 513-AUÄ-µ-35 | 513-AEÄ-µ-35 | 513-AHÄ-µ-35 | ||
| 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 513-AUÄ-µ-38 | 513-AEÄ-µ-38 | 513-AHÄ-µ-38 | ||
| — | — | 5 | 5 | 513-AUÄ-µ-39 | 513-AEÄ-µ-39 | 513-AHÄ-µ-39 | ||
| 1 | 27 | 0…1/3 | 0…1/3 | — | — | 513-BUÄ-µ-32 | 513-BEÄ-µ-32 | 513-BHÄ-µ-32 |
| 1/2…1 | 1/2…1 | 0…1 | 0…1 | 513-BUÄ-µ-35 | 513-BEÄ-µ-35 | 513-BHÄ-µ-35 | ||
| 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 1-1/2…3 | 513-BUÄ-µ-38 | 513-BEÄ-µ-38 | 513-BHÄ-µ-38 | ||
| 5 | — | — | — | 513-BUÄ-µ-39 | 513-BEÄ-µ-39 | 513-BHÄ-µ-39 | ||
| 7-1/2 | 5…7-1/2 | 5…7-1/2 | 5…7-1/2 | 513-BUÄ-µ-40 | 513-BEÄ-µ-40 | 513-BHÄ-µ-40 | ||
| — | — | 10 | 10 | 513-BUÄ-µ-41 | 513-BEÄ-µ-41 | 513-BHÄ-µ-41 | ||
| 2 | 45 | 10 | 10 | — | — | 513-CUÄ-µ-41 | 513-CEÄ-µ-41 | 513-CHÄ-µ-41 |
| — | 15 | 15 | 15 | 513-CUÄ-µ-42 | 513-CEÄ-µ-42 | 513-CHÄ-µ-42 | ||
| — | — | 20…25 | 20…25 | 513-CUÄ-µ-44 | 513-CEÄ-µ-44 | 513-CHÄ-µ-44 | ||
| 3 | 90 | 15…25 | 20…25 | — | — | 513-DUÄ-µ-44 | 513-DEÄ-µ-44 | 513-DHÄ-µ-44 |
| — | 30 | — | 30 | 513-DUÄ-µ-45 | 513-DEÄ-µ-45 | 513-DHÄ-µ-45 | ||
| — | — | 30…50 | 40…50 | 513-DUÄ-µ-47 | 513-DEÄ-µ-47 | 513-DHÄ-µ-47 | ||
| 4 | 135 | 30 | — | — | — | 513-EUÄ-µ-45 | 513-EEÄ-µ-45 | 513-EHÄ-µ-45 |
| 40 | 40 | — | — | 513-EUÄ-µ-46 | 513-EEÄ-µ-46 | 513-EHÄ-µ-46 | ||
| — | 50 | — | — | 513-EUÄ-µ-47 | 513-EEÄ-µ-47 | 513-EHÄ-µ-47 | ||
| — | — | — | 60 | 513-EUÄ-µ-48 | 513-EEÄ-µ-48 | 513-EHÄ-µ-48 | ||
| — | — | 60…75 | — | 513-EUÄ-µ-49 | 513-EEÄ-µ-49 | 513-EHÄ-µ-49 | ||
| — | — | 100 | 75…100 | 513-EUÄ-µ-50 | 513-EEÄ-µ-50 | 513-EHÄ-µ-50 | ||
| 5 | 270§ | 50…60 | 50…60 | 50…60 | 50…60 | 513-FUÄ-µ-48 | 513-FEÄ-µ-48 | 513-FHÄ-µ-48 |
| 75 | 60…75 | — | — | 513-FUÄ-µ-49 | 513-FEÄ-µ-49 | 513-FHÄ-µ-49 | ||
| — | 100 | — | — | 513-FUÄ-µ-50 | 513-FEÄ-µ-50 | 513-FHÄ-µ-50 | ||
| — | — | — | 125 | 513-FUÄ-µ-51 | 513-FEÄ-µ-51 | 513-FHÄ-µ-51 | ||
| — | — | 125…150§ | — | 513-FUÄ-µ-52 | 513-FEÄ-µ-52 | 513-FHÄ-µ-52 | ||
| — | — | 200 | 150…200 | 513-FUÄ-µ-54 | 513-FEÄ-µ-54 | 513-FHÄ-µ-54 | ||
| ¬ For Type 3R applications it is necessary that a drain or breather and drain fitting be added to the enclosure. | ||||||||
| T To order Visa-Window Breakers for certain mining applications (Canada only), add the letter V to the Cat. No. Example: Cat. No. 513-BUÄ-µ-35V. | ||||||||
| Includes drain and cover with gasket. | ||||||||
| § NEMA size 5 Unilock enclosed starters have a continuous ampere rating of 210 A. | ||||||||
| § Bolted Enclosure suitable for use on motors from 125…200 HP, 460V. | ||||||||
| Ø When controlling high efficiency motors consult your local Allen-Bradley distributor for proper circuit breaker selection. | ||||||||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 513-BUÄ-µ-35 becomes Cat. No. 513-BUA-µ-35. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 208 | 230…240 | 460…480 | 575…600 | ||
| Common Control | AC, 60 Hz | H | A | B | C | |
| Transformer Control (See Configuration of a Basic Combination Starter Note) | ||||||
| 120V Separate Control (without transformer) | HD | AD | BD | CD | ||
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no.
Example: Cat. No. 513-BUB-µ-35 becomes Cat. No. 513-BUB-A2D-35.