Combination Contactors, Starters, and Pump Control Panels

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Combination Contactors, Starters, and Pump Control Panels > Bulletin 522 Multi-Speed Disconnect Type

Bulletin 522 Multi-Speed Disconnect Type

Introduction Standards Compliance and Certifications Configuration of a Basic Combination Starter Product Selection Modifications for Combination Devices Accessories
Specifications Full Load Motor Currents Approximate Dimensions Heater Element Selection Renewal Parts
Configuration of a Basic Combination Starter

The information below is for reference purposes only. Not all combinations will produce a valid cat. no. Refer to the tables on the following pages for product selection.

Example Cat. No.

512 A    A    CD A2D 1 24R 90
a    b    c    d    e    f

a    b
Bulletin No. Starter Size
Bulletin No. Description NEMA Size Code NEMA Size
502 Combination contactor with disconnect switch A 0
503 Combination contactor with circuit breaker B 1
506 Reversing combination starter with disconnect switch C 2
506X Reversing combination starter with disconnect switch in a narrow enclosure D 3
507 Reversing combination starter with circuit breaker E 4
507X Reversing combination starter with circuit breaker in a narrow enclosure F 5
512 Non-reversing combination starter with disconnect switch G 6
512H Horizontal mounting combination starter with disconnect switch H 7
512M Non-reversing combination starter with disconnect switch — extra panel space  
512V Non-reversing vacuum combination starter with disconnect switch
513 Non-reversing combination starter with circuit breaker
513H Horizontal mounting combination starter with circuit breaker
513M Non-reversing combination starter with circuit breaker — extra panel space
513V Non-reversing vacuum combination starter with circuit breaker
522E 2-speed, 2-winding, full voltage, multi-speed combination starter with disconnect switch
522F 2-speed, 1-winding, constant or variable torque, full voltage, multi-speed combination starter with disconnect switch
522G 2-speed, 1-winding, constant horsepower, full voltage, multi-speed combination starter with disconnect switch
523E 2-speed, 2-winding, full voltage, multi-speed combination starter with circuit breaker
523F 2-speed, 1-winding, constant or variable torque, full voltage, multi-speed combination starter with circuit breaker
523G 2-speed, 1-winding, constant horsepower, full voltage, multi-speed combination starter with circuit breaker
1232X Pump panel with disconnect switch
1232V Pump panel with vacuum contactor and disconnect switch
1233X Pump panel with circuit breaker
1233V Pump panel with vacuum contactor and circuit breaker

c    d
Enclosure Type Coil Voltage
Code Type Voltage
Code
Description Line
Voltage
[V]
Coil
Voltage
[V]
A Type 1: General purpose, painted metal enclosure with spring latch door fastener, external overload relay reset, and non-metallic handle H Common Control
(without
transformer)
208 208
F Type 3R/4/12: Rainproof, watertight, dusttight, painted metal enclosure with screw fasteners, external overload relay reset, and non-metallic handle A 240 240
J Type 3R/4/12: Rainproof, watertight, dusttight, painted metal enclosure with door safety hardware, metal handle, and NO external overload relay reset B 480 480
D Type 3R/4/12: Rainproof, watertight, dusttight, painted metal enclosure with door safety hardware, external overload relay reset, and metal handle C 600 600
N Type 3R: Rainproof, painted metal extra-capacity enclosure with screw fasteners, external overload relay reset, and a non-metallic handle H Transformer
Control¬ 
208 120
C Type 4/4X: Watertight corrosion-resistant stainless steel enclosure with screw fasteners, external overload relay reset, and a stainless steel handle A 240 120
S Type 4/4X: Watertight corrosion-resistant non-metallic enclosure with screw fasteners, external overload relay reset, and a non-metallic handle B 480 120
K Type 12: Hazardous location (Class II, Division 2, Group F + G and Class III, Divisions 1 + 2) painted metal enclosure with screw fasteners, NO external overload relay reset, and a non-metallic handle. C 600 120
L Type 12: Hazardous location (Class II, Division 2, Group F + G and Class III, Divisions 1 + 2) painted metal enclosure with screw fasteners, external overload relay reset, and a non-metallic handle. HD Separate Control
(without
transformer)
208 120
E Type 7+9: Hazardous location bolted enclosure, metal handle. AD 240 120
H Type 3R/7/9: Hazardous location bolted enclosure, rain proof, metal handle. BD 480 120
U Type 3R/7/9: Hazardous location Unilock enclosure, rain proof, metal handle. CD 600 120

e    f
Overload Relay Options
Code Description See For Use on Bulletins 502, 502L, 503, 503L, 506, 506X, 507, 507X, 512, 512H, 512M, 512V, 513, 513H, 513M, 513V, 522, 522E, 522F, 522G, 523, 523E, 523F, 523G, 530, 532, 533, 540, 542, 543, 570, 572, 573, 1242, 1243, 1272, 1273, 1232X, 1232V, 1233X, and 1233V
None Eutectic Alloy  
See E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset)
Solid-State

¬   Note
When selecting a factory-installed control circuit transformer use the Transformer Control Voltage Suffix Code to denote the transformer primary voltage. The transformer secondary voltage and starter coil will both be 120V AC by default. Example: Cat. No. 512-BAB-6P-24R will have a transformer with a 480V primary voltage, 120V secondary voltage, and a 120V starter coil voltage.