Combination Contactors, Starters, and Pump Control Panels

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Combination Contactors, Starters, and Pump Control Panels > Bulletin 522 Multi-Speed Disconnect Type

Bulletin 522 Multi-Speed Disconnect Type

Introduction Standards Compliance and Certifications Configuration of a Basic Combination Starter Product Selection Modifications for Combination Devices
Accessories Specifications Full Load Motor Currents Approximate Dimensions Renewal Parts
Product Selection

2-Speed Separate Winding, 3-Pole – 3-Pole, Constant or Variable Torque

Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements for each speed located on Eutectic Alloy Overload Relay Heater Elements.
NEMA
Size
Con-
tinuous
Ampere
Rating
[A]
Maximum Hp Rating
FLC Must Not Exceed
Continuous Ampere Rating
Line
Voltage
[V]
Fuse Clip
Rating
Amperes
[A]
Fuses not
included.
Select per NEC
Type 1
General Purpose
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
(Door Safety
Hardware)
Type 4/4X
Watertight
Corrosion-Resistant
Stainless Steel
Motor Voltage
60 Hz 60 Hz 50 Hz 60 Hz
200V 230V 380…
415V
460…
575V
Cat. No.⋆ ‡ §  Cat. No.⋆ ‡ §  Cat. No.⋆ ‡ §  Cat. No.⋆ ‡ § 
1 27 5 5 208…240 30 522E-BAÄ-µ-µ-24R 522E-BFÄ-µ-µ-24R 522E-BJÄ-µ-µ-24R 522E-BCÄ-µ-µ-24R
7-1/2 7-1/2 480…600 30 522E-BAÄ-µ-µ-24R 522E-BFÄ-µ-µ-24R 522E-BJÄ-µ-µ-24R 522E-BCÄ-µ-µ-24R
7-1/2 7-1/2 208…240 30 522E-BAÄ-µ-µ-24R 522E-BFÄ-µ-µ-24R 522E-BJÄ-µ-µ-24R 522E-BCÄ-µ-µ-24R
10 10 480…600 30 522E-BAÄ-µ-µ-24R 522E-BFÄ-µ-µ-24R 522E-BJÄ-µ-µ-24R 522E-BCÄ-µ-µ-24R
7-1/2 7-1/2 208…240 60 522E-BAÄ-µ-µ-25R 522E-BFÄ-µ-µ-25R 522E-BJÄ-µ-µ-25R 522E-BCÄ-µ-µ-25R
10 10 480…600 60 522E-BAÄ-µ-µ-25R 522E-BFÄ-µ-µ-25R 522E-BJÄ-µ-µ-25R 522E-BCÄ-µ-µ-25R
2 45 10 15 208…240 60 522E-CAÄ-µ-µ-25R 522E-CFÄ-µ-µ-25R 522E-CJÄ-µ-µ-25R 522E-CCÄ-µ-µ-25R
25 25 480…600 60 522E-CAÄ-µ-µ-25R 522E-CFÄ-µ-µ-25R 522E-CJÄ-µ-µ-25R 522E-CCÄ-µ-µ-25R
10 15 208…240 100 522E-CAÄ-µ-µ-26J 522E-CFÄ-µ-µ-26J 522E-CJÄ-µ-µ-26J 522E-CCÄ-µ-µ-26J
25 25 480…600 100 522E-CAÄ-µ-µ-26J 522E-CFÄ-µ-µ-26J 522E-CJÄ-µ-µ-26J 522E-CCÄ-µ-µ-26J
3 90 25 30 208…240 100 522E-DAÄ-µ-µ-26R 522E-DFÄ-µ-µ-26R 522E-DJÄ-µ-µ-26R 522E-DCÄ-µ-µ-26R
50 50 480…600 100 522E-DAÄ-µ-µ-26R 522E-DFÄ-µ-µ-26R 522E-DJÄ-µ-µ-26R 522E-DCÄ-µ-µ-26R
25 30 208…240 200 522E-DAÄ-µ-µ-27J 522E-DFÄ-µ-µ-27J 522E-DJÄ-µ-µ-27J 522E-DCÄ-µ-µ-27J
50 50 480…600 200 522E-DAÄ-µ-µ-27J 522E-DFÄ-µ-µ-27J 522E-DJÄ-µ-µ-27J 522E-DCÄ-µ-µ-27J
4 135 40 50 208…240 200 522E-EAÄ-µ-µ-27R 522E-EFÄ-µ-µ-27R 522E-EJÄ-µ-µ-27R 522E-ECÄ-µ-µ-27R
75 100 480…600 200 522E-EAÄ-µ-µ-27R 522E-EFÄ-µ-µ-27R 522E-EJÄ-µ-µ-27R 522E-ECÄ-µ-µ-27R
40 50 208…240 400 522E-EAÄ-µ-µ-28J 522E-EFÄ-µ-µ-28J 522E-EJÄ-µ-µ-28J 522E-ECÄ-µ-µ-28J
75 100 480…600 400 522E-EAÄ-µ-µ-28J 522E-EFÄ-µ-µ-28J 522E-EJÄ-µ-µ-28J 522E-ECÄ-µ-µ-28J
5 270 40 50 208…240 200 522E-FAÄ-µ-µ-27R 522E-FFÄ-µ-µ-27R 522E-FJÄ-µ-µ-27R 522E-FCÄ-µ-µ-27R
75 100 480…600 200 522E-FAÄ-µ-µ-27R 522E-FFÄ-µ-µ-27R 522E-FJÄ-µ-µ-27R 522E-FCÄ-µ-µ-27R
75 100 150 200 208…600 400 522E-FAÄ-µ-µ-28R 522E-FFÄ-µ-µ-28R 522E-FJÄ-µ-µ-28R 522E-FCÄ-µ-µ-28R
  

⋆  Non-Fusible Disconnect Type

Cat. nos. listed above include a fusible disconnect switch with Class R or J fuse clips. To order a non-fusible disconnect switch, eliminate the fuse clip code from the cat. no. Example: Cat. No. 522E-BFB-24R becomes Cat. No. 522E-BFB.


‡ Class H fuse clips can be supplied. Example: Cat. No. 522E-BAÄ-µµ24R becomes Cat. No. 522E-BAÄ-µµ24. Class J fuse clips can be supplied. Example: Cat. No. 522E-BAÄ-µµ24R becomes Cat. No. 522E-BAÄ-µµ24J. Class HRC form II fuse clips can be supplied. Example: Cat. No. 522E-BAÄ-µµ24R becomes Cat. No. 522E-BAÄ-µµ24E.
§ These starters are for wye connected motor windings. They may not be used with open delta connected motor windings. For starters to be used with open delta connected separate winding motors, use consequent pole starter, and furnish complete ordering information, see Ä Coil Voltage Code.


Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 522E-BAÄ-µ-µ-24R becomes Cat. No. 522E-BAB-µ-µ-24R. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) AD AD CD CD
  

µ-µ Overload Relay Code

Use to order solid-state overload relays. Do not use when ordering eutectic alloy overload relays. The cat. no. as listed is incomplete. Select two overload relay codes from E1 Plus Solid-State Three-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no. The first code will denote the high speed overload relay and the second code will denote the low speed overload relay.
Example: Cat. No. 522E-BAB-µ-µ-24R becomes Cat. No. 522E-BAB-A2E-A2E-24R.


Build a Catalog Number


2-Speed Separate Winding, 3-Pole – 3-Pole, Constant Horsepower

Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements for each overload. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA
Size
Con-
tinuous
Ampere
Rating
[A]
Maximum Hp Rating
Full Load Current Must Not Exceed Continuous Ampere Rating
Line
Voltage
[V]
Fuse Clip Rating Amperes [A]
Fuses not included. Select per NEC
Type 1
General Purpose
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
(Door Safety
Hardware)
Type 4/4X
Watertight
Corrosion-
Resistant
Stainless Steel
Motor Voltage
60 Hz 60 Hz 50 Hz 60 Hz
200V 230V 380…
415V
460…
575V
Cat. No.⋆ ‡ §  Cat. No.⋆ ‡ §  Cat. No.⋆ ‡ §  Cat. No.⋆ ‡ § 
1 27 5 5 208…240 30 522E-BAÄ-µ-µ-24R 522E-BFÄ-µ-µ-24R 522E-BJÄ-µ-µ-24R 522E-BCÄ-µ-µ-24R
7-1/2 7-1/2 480…600 30 522E-BAÄ-µ-µ-24R 522E-BFÄ-µ-µ-24R 522E-BJÄ-µ-µ-24R 522E-BCÄ-µ-µ-24R
5 5 208…240 60 522E-BAÄ-µ-µ-25R 522E-BFÄ-µ-µ-25R 522E-BJÄ-µ-µ-25R 522E-BCÄ-µ-µ-25R
7-1/2 7-1/2 480…600 60 522E-BAÄ-µ-µ-25R 522E-BFÄ-µ-µ-25R 522E-BJÄ-µ-µ-25R 522E-BCÄ-µ-µ-25R
2 45 7-1/2 10 208…240 60 522E-CAÄ-µ-µ-25R 522E-CFÄ-µ-µ-25R 522E-CJÄ-µ-µ-25R 522E-CCÄ-µ-µ-25R
20 20 480…600 60 522E-CAÄ-µ-µ-25R 522E-CFÄ-µ-µ-25R 522E-CJÄ-µ-µ-25R 522E-CCÄ-µ-µ-25R
7-1/2 10 208…240 100 522E-CAÄ-µ-µ-26J 522E-CFÄ-µ-µ-26J 522E-CJÄ-µ-µ-26J 522E-CCÄ-µ-µ-26J
20 20 480…600 100 522E-CAÄ-µ-µ-26J 522E-CFÄ-µ-µ-26J 522E-CJÄ-µ-µ-26J 522E-CCÄ-µ-µ-26J
3 90 20 25 208…240 100 522E-DAÄ-µ-µ-26R 522E-DFÄ-µ-µ-26R 522E-DJÄ-µ-µ-26R 522E-DCÄ-µ-µ-26R
40 40 480…600 100 522E-DAÄ-µ-µ-26R 522E-DFÄ-µ-µ-26R 522E-DJÄ-µ-µ-26R 522E-DCÄ-µ-µ-26R
20 25 208…240 200 522E-DAÄ-µ-µ-27J 522E-DFÄ-µ-µ-27J 522E-DJÄ-µ-µ-27J 522E-DCÄ-µ-µ-27J
40 40 480…600 200 522E-DAÄ-µ-µ-27J 522E-DFÄ-µ-µ-27J 522E-DJÄ-µ-µ-27J 522E-DCÄ-µ-µ-27J
4 135 30 40 208…240 200 522E-EAÄ-µ-µ-27R 522E-EFÄ-µ-µ-27R 522E-EJÄ-µ-µ-27R 522E-ECÄ-µ-µ-27R
60 75 480…600 200 522E-EAÄ-µ-µ-27R 522E-EFÄ-µ-µ-27R 522E-EJÄ-µ-µ-27R 522E-ECÄ-µ-µ-27R
30 40 208…240 400 522E-EAÄ-µ-µ-28J 522E-EFÄ-µ-µ-28J 522E-EJÄ-µ-µ-28J 522E-ECÄ-µ-µ-28J
60 75 480…600 400 522E-EAÄ-µ-µ-28J 522E-EFÄ-µ-µ-28J 522E-EJÄ-µ-µ-28J 522E-ECÄ-µ-µ-28J
5 270 30 40 208…240 200 522E-FAÄ-µ-µ-27R 522E-FFÄ-µ-µ-27R 522E-FJÄ-µ-µ-27R 522E-FCÄ-µ-µ-27R
60 75 480…600 200 522E-FAÄ-µ-µ-27R 522E-FFÄ-µ-µ-27R 522E-FJÄ-µ-µ-27R 522E-FCÄ-µ-µ-27R
60 75 100 150 208…600 400 522E-FAÄ-µ-µ-28R 522E-FFÄ-µ-µ-28R 522E-FJÄ-µ-µ-28R 522E-FCÄ-µ-µ-28R
  

⋆  Non-Fusible Disconnect Type

Cat. nos. listed above include a fusible disconnect switch with Class R or J fuse clips. To order a non-fusible disconnect switch, eliminate the fuse clip code from the cat. no. Example: Cat. No. 522E-BFB-24R becomes Cat. No. 522E-BFB.


‡ Class H fuse clips can be supplied. Example: Cat. No. 522E-BAÄ-µµ24R becomes Cat. No. 522E-BAÄ-µµ24. Class J fuse clips can be supplied. Example: Cat. No. 522E-BAÄ-µµ24R becomes Cat. No. 522E-BAÄ-µµ24J. Class HRC form II fuse clips can be supplied. Example: Cat. No. 522E-BAÄ-µµ24R becomes Cat. No. 522E-BA-Ä-µµ24E.
§ These starters are for wye connected motor windings. They may not be used with open delta connected motor windings. For starters to be used with open delta connected separate winding motors, use consequent pole starter, and furnish complete ordering information, see Ä Coil Voltage Code.


Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 522E-BAÄ-µ-µ-24R becomes Cat. No. 522E-BAB-µ-µ-24R. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) AD AD CD CD
  

µ-µ Overload Relay Code

Use to order solid-state overload relays. Do not use when ordering eutectic alloy overload relays. The cat. no. as listed is incomplete. Select two overload relay codes from E1 Plus Solid-State Three-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no. The first code will denote the high speed overload relay and the second code will denote the low speed overload relay. Example: Cat. No. 522E-BAB-µ-µ-24R becomes Cat. No. 522E-BAB-A2E-A2E-24R.

Build a Catalog Number


2-Speed Consequent Pole, 5-Pole – 3-Pole, Single Winding, Constant or Variable Torque

Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements for each speed. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA
Size
Con-
tinuous
Ampere
Rating [A]
Maximum Hp Rating
Full Load Current Must Not Exceed Continuous Ampere Rating
Line
Voltage
[V]
Fuse Clip Rating Amperes [A]
Fuses not included. Select per NEC
Type 1
General Purpose
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
(Door Safety
Hardware)
Type 4/4X
Watertight
Corrosion-
Resistant
Stainless Steel
Motor Voltage
60 Hz 60 Hz 50 Hz 60 Hz
200V 230V230V 380…
415V
460…
575V
Cat. No.⋆ ‡  Cat. No.⋆ ‡  Cat. No.⋆ ‡  Cat. No.⋆ ‡ 
1 27 7-1/2 7-1/2 208…240 30 522F-BAÄ-µ-µ-24R 522F-BFÄ-µ-µ-24R 522F-BJÄ-µ-µ-24R 522F-BCÄ-µ-µ-24R
10 10 480…600 30 522F-BAÄ-µ-µ-24R 522F-BFÄ-µ-µ-24R 522F-BJÄ-µ-µ-24R 522F-BCÄ-µ-µ-24R
7-1/2 7-1/2 208…240 60 522F-BAÄ-µ-µ-25R 522F-BFÄ-µ-µ-25R 522F-BJÄ-µ-µ-25R 522F-BCÄ-µ-µ-25R
10 10 480…600 60 522F-BAÄ-µ-µ-25R 522F-BFÄ-µ-µ-25R 522F-BJÄ-µ-µ-25R 522F-BCÄ-µ-µ-25R
2 45 10 15 208…240 60 522F-CAÄ-µ-µ-25R 522F-CFÄ-µ-µ-25R 522F-CJÄ-µ-µ-25R 522F-CCÄ-µ-µ-25R
25 25 480…600 60 522F-CAÄ-µ-µ-25R 522F-CFÄ-µ-µ-25R 522F-CJÄ-µ-µ-25R 522F-CCÄ-µ-µ-25R
10 15 208…240 100 522F-CAÄ-µ-µ-26J 522F-CFÄ-µ-µ-26J 522F-CJÄ-µ-µ-26J 522F-CCÄ-µ-µ-26J
25 25 480…600 100 522F-CAÄ-µ-µ-26J 522F-CFÄ-µ-µ-26J 522F-CJÄ-µ-µ-26J 522F-CCÄ-µ-µ-26J
3 90 25 30 208…240 100 522F-DAÄ-µ-µ-26R 522F-DFÄ-µ-µ-26R 522F-DJÄ-µ-µ-26R 522F-DCÄ-µ-µ-26R
50 50 480…600 100 522F-DAÄ-µ-µ-26R 522F-DFÄ-µ-µ-26R 522F-DJÄ-µ-µ-26R 522F-DCÄ-µ-µ-26R
25 30 208…240 200 522F-DAÄ-µ-µ-27J 522F-DFÄ-µ-µ-27J 522F-DJÄ-µ-µ-27J 522F-DCÄ-µ-µ-27J
50 50 480…600 200 522F-DAÄ-µ-µ-27J 522F-DFÄ-µ-µ-27J 522F-DJÄ-µ-µ-27J 522F-DCÄ-µ-µ-27J
4 135 40 50 208…240 200 522F-EAÄ-µ-µ-27R 522F-EFÄ-µ-µ-27R 522F-EJÄ-µ-µ-27R 522F-ECÄ-µ-µ-27R
75 100 480…600 200 522F-EAÄ-µ-µ-27R 522F-EFÄ-µ-µ-27R 522F-EJÄ-µ-µ-27R 522F-ECÄ-µ-µ-27R
40 50 208…240 400 522F-EAÄ-µ-µ-28J 522F-EFÄ-µ-µ-28J 522F-EJÄ-µ-µ-28J 522F-ECÄ-µ-µ-28J
75 100 480…600 400 522F-EAÄ-µ-µ-28J 522F-EFÄ-µ-µ-28J 522F-EJÄ-µ-µ-28J 522F-ECÄ-µ-µ-28J
5 270 40 50 208…240 200 522F-FAÄ-µ-µ-27R 522F-FFÄ-µ-µ-27R 522F-FJÄ-µ-µ-27R
75 100 480…600 200 522F-FAÄ-µ-µ-27R 522F-FFÄ-µ-µ-27R 522F-FJÄ-µ-µ-27R
75 100 150 200 208…600 400 522F-FAÄ-µ-µ-28R 522F-FFÄ-µ-µ-28R 522F-FJÄ-µ-µ-28R
  

⋆  Non-Fusible Disconnect Type

Cat. nos. listed above include a fusible disconnect switch with Class R or J fuse clips. To order a non-fusible disconnect switch, eliminate the fuse clip code from the cat. no. Example: Cat. No. 522F-BJB-24R becomes Cat. No. 522F-BJB.


‡ Class H fuse clips can be supplied. Example: Cat. No. 522F-BAÄ-µµ24R becomes Cat. No. 522F-BAÄ-µµ24. Class J fuse clips can be supplied. Example: Cat. No. 522F-BAÄ-µµ24R becomes Cat. No. 522F-BAÄ-µµ24J. Class HRC form II fuse clips can be supplied. Example: Cat. No. 522F-BAÄ-µµ24R becomes Cat. No. 522F-BAÄ-µµ24E.


Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 522F-BAÄ-µ-µ-24R becomes Cat. No. 522F-BAB-µ-µ-24R. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) AD AD CD CD
  

µ-µ Overload Relay Code

Use to order solid-state overload relays. Do not use when ordering eutectic alloy overload relays. The cat. no. as listed is incomplete. Select two overload relay codes from E1 Plus Solid-State Three-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no. The first code will denote the high speed overload relay and the second code will denote the low speed overload relay. Example: Cat. No. 522F-BAB-µ-µ-24R becomes Cat. No. 522F-BAB-A2E-A2E-24R.

Build a Catalog Number


2-Speed Consequent Pole, 5-Pole – 3-Pole, Single Winding, Constant Horsepower

Heater Elements — Starters with eutectic alloy overhead relays require 3 heater elements for each overload. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA
Size
Con-
tinuous
Ampere
Rating
[A]
Maximum Hp Rating
Full Load Current Must Not Exceed Continuous Ampere Rating
Line
Voltage
[V]
Fuse Clip Rating Amperes [A]
Fuses not included. Select per NEC
Type 1
General Purpose
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
Type 3R/4/12
Rainproof,
Waterproof,
Dusttight
(Door Safety
Hardware)
Type 4/4X
Watertight
Corrosion-
Resistant
Stainless Steel
Motor Voltage
60 Hz 60 Hz 50 Hz 60 Hz
200V 230V 380…
415V
460…
575V460…
575V
Cat. No.⋆ ‡  Cat. No.⋆ ‡  Cat. No.⋆ ‡  Cat. No.⋆ ‡ 
1 27 5 5 208…240 30 522G-BAÄ-µ-µ-24R 522G-BFÄ-µ-µ-24R 522G-BJÄ-µ-µ-24R 522G-BCÄ-µ-µ-24R
7-1/2 7-1/2 480…600 30 522G-BAÄ-µ-µ-24R 522G-BFÄ-µ-µ-24R 522G-BJÄ-µ-µ-24R 522G-BCÄ-µ-µ-24R
5 5 208…240 60 522G-BAÄ-µ-µ-25R 522G-BFÄ-µ-µ-25R 522G-BJÄ-µ-µ-25R 522G-BCÄ-µ-µ-25R
7-1/2 7-1/2 480…600 60 522G-BAÄ-µ-µ-25R 522G-BFÄ-µ-µ-25R 522G-BJÄ-µ-µ-25R 522G-BCÄ-µ-µ-25R
2 45 7-1/2 10 208…240 60 522G-CAÄ-µ-µ-25R 522G-CFÄ-µ-µ-25R 522G-CJÄ-µ-µ-25R 522G-CCÄ-µ-µ-25R
20 20 480…600 60 522G-CAÄ-µ-µ-25R 522G-CFÄ-µ-µ-25R 522G-CJÄ-µ-µ-25R 522G-CCÄ-µ-µ-25R
7-1/2 10 208…240 100 522G-CAÄ-µ-µ-26J 522G-CFÄ-µ-µ-26J 522G-CJÄ-µ-µ-26J 522G-CCÄ-µ-µ-26J
20 20 480…600 100 522G-CAÄ-µ-µ-26J 522G-CFÄ-µ-µ-26J 522G-CJÄ-µ-µ-26J 522G-CCÄ-µ-µ-26J
3 90 20 25 208…240 100 522G-DAÄ-µ-µ-26R 522G-DFÄ-µ-µ-26R 522G-DJÄ-µ-µ-26R 522G-DCÄ-µ-µ-26R
40 40 480…600 100 522G-DAÄ-µ-µ-26R 522G-DFÄ-µ-µ-26R 522G-DJÄ-µ-µ-26R 522G-DCÄ-µ-µ-26R
20 25 208…240 200 522G-DAÄ-µ-µ-27J 522G-DFÄ-µ-µ-27J 522G-DJÄ-µ-µ-27J 522G-DCÄ-µ-µ-27J
40 40 480…600 200 522G-DAÄ-µ-µ-27J 522G-DFÄ-µ-µ-27J 522G-DJÄ-µ-µ-27J 522G-DCÄ-µ-µ-27J
4 135 30 40 208…240 200 522G-EAÄ-µ-µ-27R 522G-EFÄ-µ-µ-27R 522G-EJÄ-µ-µ-27R 522G-ECÄ-µ-µ-27R
60 75 480…600 200 522G-EAÄ-µ-µ-27R 522G-EFÄ-µ-µ-27R 522G-EJÄ-µ-µ-27R 522G-ECÄ-µ-µ-27R
30 40 208…240 400 522G-EAÄ-µ-µ-28J 522G-EFÄ-µ-µ-28J 522G-EJÄ-µ-µ-28J 522G-ECÄ-µ-µ-28J
60 75 480…600 400 522G-EAÄ-µ-µ-28J 522G-EFÄ-µ-µ-28J 522G-EJÄ-µ-µ-28J 522G-ECÄ-µ-µ-28J
5 270 30 40 208…240 200 522G-FAÄ-µ-µ-27R 522G-FFÄ-µ-µ-27R 522G-FJÄ-µ-µ-27R
60 75 480…600 200 522G-FAÄ-µ-µ-27R 522G-FFÄ-µ-µ-27R 522G-FJÄ-µ-µ-27R
60 75 100 150 208…600 400 522G-FAÄ-µ-µ-28R 522G-FFÄ-µ-µ-28R 522G-FJÄ-µ-µ-28R
  

⋆  Non-Fusible Disconnect Type

Cat. nos. listed above include a fusible disconnect switch with Class R or J fuse clips. To order a non-fusible disconnect switch, eliminate the fuse clip code from the cat. no. Example: Cat. No. 522G-BJB-24R becomes Cat. No. 522G-BJB.


‡ Class H fuse clips can be supplied. Example: Cat. No. 522G-BAÄ-µµ24R becomes Cat. No. 522G-BAÄ-µµ24. Class J fuse clips can be supplied. Example: Cat. No. 522G-BAÄ-µµ24R becomes Cat. No. 522G-BAÄ-µµ24J. Class HRC form II fuse clips can be supplied. Example: Cat. No. 522G-BAÄ-µµ24R becomes Cat. No. 522G-BAÄ-µµ24E.


Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the cat. no.
Example: Cat. No. 522G-BAÄ-µ-µ-24R becomes Cat. No. 522G-BAB-µ-µ-24R. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.


  [V] 208 230…240 460…480 575…600
Common Control AC, 60 Hz H A B C
Transformer Control (See Configuration of a Basic Combination Starter Note)
120V Separate Control (without transformer) AD AD CD CD
  

µ-µ Overload Relay Code

Use to order solid-state overload relays. Do not use when ordering eutectic alloy overload relays. The cat. no. as listed is incomplete. Select two overload relay codes from E1 Plus Solid-State Three-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no. The first code will denote the high speed overload relay and the second code will denote the low speed overload relay. Example: Cat. No. 522G-BAB-µ-µ-24R becomes Cat. No. 522G-BAB-A2E-A2E-24R.