Bulletin 1232X Pump Control Panels
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Combination Starter | Product Selection | Modifications for Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
| Build a Catalog Number |
| Heater Elements — Starters with eutectic alloy overload relays require 3 heater elements. Located on Eutectic Alloy Overload Relay Heater Elements. | ||||||||
| NEMA Size |
Continuous Ampere Rating [A] | Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Line Voltage [V] |
Fuse Clip Rating Amperes [A] Fuses not included. Select per NEC |
Type 3R Rainproof with Extra Panel Space |
|||
| Motor Voltage | ||||||||
| 60 Hz | 60 Hz | 50 Hz | 60 Hz | |||||
| 200V | 230V | 380…415V | 460…575V | Cat. No. | ||||
| 1 | 27 | 7-1/2 | 7-1/2 | — | — | 208…240 | 30 | 1232X-BNÄ-µ-24R |
| — | — | 10 | 10 | 480…600 | 30 | 1232X-BNÄ-µ-24R | ||
| 7-1/2 | 7-1/2 | — | — | 208…240 | 60 | 1232X-BNÄ-µ-25R | ||
| — | — | 10 | 10 | 480…600 | 60 | 1232X-BNÄ-µ-25R | ||
| 2 | 45 | 10 | 15 | — | — | 208…240 | 60 | 1232X-CNÄ-µ-25R |
| — | — | 25 | 25 | 480…600 | 60 | 1232X-CNÄ-µ-25R | ||
| 10 | 15 | — | — | 208…240 | 100 | 1232X-CNÄ-µ-26J | ||
| — | — | 25 | 25 | 480…600 | 100 | 1232X-CNÄ-µ-26J | ||
| 3 | 90 | 25 | 30 | — | — | 208…240 | 100 | 1232X-DNÄ-µ-26R |
| — | — | 50 | 50 | 480…600 | 100 | 1232X-DNÄ-µ-26R | ||
| 25 | 30 | — | — | 208…240 | 200 | 1232X-DNÄ-µ-27J | ||
| — | — | 50 | 50 | 480…600 | 200 | 1232X-DNÄ-µ-27J | ||
| 4 | 135 | 40 | 50 | — | — | 208…240 | 200 | 1232X-ENÄ-µ-27R |
| — | — | 75 | 100 | 480…600 | 200 | 1232X-ENÄ-µ-27R | ||
| 40 | 50 | — | — | 208…240 | 400 | 1232X-ENÄ-µ-28J | ||
| — | — | 75 | 100 | 480…600 | 400 | 1232X-ENÄ-µ-28J | ||
| 5 | 270 | 75 | 100 | — | — | 208…240 | 400 | 1232X-FNÄ-µ-28R |
| — | — | 150 | 200 | 480…600 | 400 | 1232X-FNÄ-µ-28R | ||
| 6 | 540 | 150 | 200 | 300 | 400 | 208…600 | 600⋆ | 1232X-GNÄ-µ-29R |
| 7 | 810 | — | 300 | 500 | 600 | 240…600 | 1200 | 1232X-HNÄ-µ-25L |
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no.
Example: Cat. No. 1232X-BNÄ-µ-24 becomes Cat. No. 1232X-BNA-µ-24. For other voltages, consult your local Rockwell Automation sales office or Allen‑Bradley distributor.
| [V] | 208 | 230…240 | 460…480 | 575…600 | ||
| Common Control | AC, 60 Hz | H | A | B | C | |
| Transformer Control (See Configuration of a Basic Combination Starter Note) | ||||||
| 120V Separate Control (without transformer) | AD | AD | CD | CD | ||
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Three-Phase Overload Relay (Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no.
Example: Cat. No. 1232X-BNA-µ-24 becomes Cat. No. 1232X-BNA-A2E-24.
⋆ For 230V and 460V Hp ratings, limit the maximum fuse sizing to 125% of motor full load current.