Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Contactors, Starters, and Overload Relays > Reduced Voltage Starters, Combination Starters, and Pump Control Panels > Bulletin 570 Autotransformer Starters
Bulletin 570 Autotransformer Starters
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Starter | Product Selection | Modifications for Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
Electrical Ratings
| NEMA Size |
Load Voltage [V] |
Continuous Current Rating [A] |
Service Limit Current Rating [A]¬ |
Maximum Hp Rating (Non-plugging and non-jogging duty) |
Maximum Hp Rating (Plugging and jogging duty)T |
Transformer Primary Switching kVa Rating (Inrush Current £ 20 times Continuous Current) |
Transformer Primary Switching kVa Rating (Inrush Current = 20 to 40 times Continuous Current) |
Capacitor Switching kVAR |
Maximum Circuit Closing Inrush Current [A] Peak Including Offset |
||||
| 1Æ | 3Æ | 1Æ | 3Æ | 1Æ | 3Æ | 1Æ | 3Æ | 3Æ | 3Æ | ||||
| 00 | 115 200 230 380 460 575 |
9 | 11 | 1/3 — 1 — — — |
— 1-1/2 1-1/2 1-1/2 2 2 |
1/4 — 1/2 — — — |
— 1 1 1 1-1/2 1-1/2 |
— — — — — — |
— — — — — — |
— — — — — — |
— — — — — — |
— — — — — — |
87 |
| 0 | 115 200 230 380 460 575 |
18 | 21 | 1 — 2 — — — |
— 3 3 5 5 5 |
1/2 — 1 — — — |
— 1-1/2 1-1/2 1-1/2 2 2 |
0.6 — 1.2 — 2.4 3 |
— 1.8 2.1 — 4.2 5.2 |
0.3 — 0.6 — 1.2 1.5 |
— 0.9 1 — 2.1 2.6 |
— — — — — — |
140 |
| 1 | 115 200 230 380 460 575 |
27 | 32 | 2 — 3 — — — |
— 7-1/2 7-1/2 10 10 10 |
1 — 2 — — — |
— 3 3 5 5 5 |
1.2 — 2.4 — 4.9 6.2 |
— 3.6 4.3 — 8.5 11 |
0.6 — 1.2 — 2.5 3.1 |
— 1.8 2.1 — 4.3 5.3 |
— — 6 — 13.5 17 |
288 |
| 1P | 115 230 |
36 | 42 | 3 5 |
— — |
1-1/2 3 |
— — |
— — |
— — |
— — |
— — |
— — |
— — |
| 2 | 115 200 230 380 460 575 |
45 | 52 | 3 — 7-1/2 — — — |
— 10 15 25 25 25 |
2 — 5 — — — |
— 7-1/2 10 15 15 15 |
2.1 — 4.1 — 8.3 10 |
— 6.3 7.2 — 14 18 |
1 — 2.1 — 4.2 5.2 |
— 3.1 3.6 — 7.2 8.9 |
— — 12 — 25 31 |
483 |
| 3 | 115 200 230 380 460 575 |
90 | 104 | 7-1/2 — 15 — — — |
— 25 30 50 50 50 |
7-1/2 — 15 — — — |
— 15 20 30 30 30 |
4.1 — 8.1 — 16 20 |
— 12 14 — 28 35 |
2 — 4.1 — 8.1 10 |
— 6.1 7.0 — 14 18 |
— — 27 — 53 67 |
947 |
| 4 | 115 200 230 380 460 575 |
135 | 156 | — — — — — — |
— 40 50 75 100 100 |
— — — — — — |
— 25 30 50 60 60 |
6.8 — 14 — 27 34 |
— 20 23 — 47 59 |
3.4 — 6.8 — 14 17 |
— 10 12 — 23 29 |
— — 40 — 80 100 |
1581 |
| 5 | 115 200 230 380 460 575 |
270 | 311 | — — — — — — |
— 75 100 150 200 200 |
— — — — — — |
— 60 75 125 150 150 |
14 — 27 — 54 68 |
— 41 47 — 94 117 |
6.8 — 14 — 27 34 |
— 20 24 — 47 59 |
— — 80 — 160 200 |
3163 |
| 6 | 115 200 230 380 460 575 |
540 | 621 | — — — — — — |
— 150 200 300 400 400 |
— — — — — — |
— 125 150 250 300 300 |
27 — 54 — 108 135 |
— 81 94 — 188 234 |
14 — 27 — 54 68 |
— 41 47 — 94 117 |
— — 160 — 320 400 |
6326 |
| 7 | 230 460 575 |
810 | 932 | — — — |
300 600 600 |
— — — |
— — — |
— — — |
— — — |
— — — |
— — — |
240 480 600 |
9470 |
| 8 | 230 460 575 |
1215 | 1400 | — — — |
450 900 900 |
— — — |
— — — |
— — — |
— — — |
— — — |
— — — |
360 720 900 |
14205 |
| 9 | 230 460 575 |
2250 | 2590 | — — — |
800 1600 1600 |
— — — |
— — — |
— — — |
— — — |
— — — |
— — — |
665 1325 1670 |
25380 |
| ¬ Service-Limit Current Ratings — The service-limit current ratings shown represent the maximum rms current, in amperes, which the controller shall be permitted to carry for protracted periods in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed those obtained by testing the controller at its continuous current rating. The current rating of overload relays or the trip current of other motor protective devices used shall not exceed the service-limit current rating of the controller. | |||||||||||||
| T Plugging or Jogging Service — The listed horsepower ratings are recommended for those applications requiring repeated interruption of stalled motor current encountered in rapid motor reversal in excess of five openings or closings per minute and shall not be more than ten in a ten minute period. | |||||||||||||
| If maximum available current (at capacitor terminals) is greater than 3000 A, please contact your local Rockwell Automation sales office, Allen-Bradley distributor, or NEMA ICS-2 Standard. | |||||||||||||
Mechanical Ratings
| NEMA Size |
Mechanical Life (Millions of Operations) |
Maximum Number of Auxiliary Contacts |
Operating Time [ms] | |
| Pick-up (Average) | Drop-out (Average) | |||
| 0 | 10 | 8 | 21 | 16 |
| 1 | 10 | 8 | 22 | 14 |
| 1P | 10 | 8 | 22 | 14 |
| 2 | 10 | 8 | 27 | 13 |
| 3 | 5 | 8 | 37 | 20 |
| 4 | 5 | 8 | 27 | 20 |
| 5 | 5 | 8 | 25 | 18 |
| 6 | 5 | 4 | 25…79 | 10…22 |
| 7 | — | 8 | 88 | 40 |
| 8 | — | 8 | 88 | 45 |
| 9 | — | 8 | 118 | 84 |
| 00 | 10 | 5 | 20 | 16 |
Construction
Environmental
| NEMA Size |
Operating Temperature Range | Altitude | Corrosion-Resistance | Operating Position |
| 0 | Starters with eutectic alloy Overload relay 13…+149 °F (25…+65 °C) Starters with SMP Overload relay 13…+131 °F (25…+55 °C) (provided condensation is prevented) |
10 000 feet before derating | All metal parts are treated for corrosion-resistance |
Vertical |
| 1 | ||||
| 1P | ||||
| 2 | ||||
| 3 | ||||
| 4 | ||||
| 5 | ||||
| 6 | Horizontal | |||
| 7 | Vertical | |||
| 8 | ||||
| 9 | ||||
| 00 | Horizontal | |||
Short Circuit Rating
Combination contactors and starters with disconnect switch: Bulletin 502, 506, 512, 522E, 522F, 522G, and 1232X
| Combination Contactors and Starters with Disconnect Switch: Bulletin 502, 506, 512, 522E, 522F, 522G, and 1232X | |||
| NEMA Size | Fuse Type | Available Short Circuit Amperes RMS Symmetrical [A] | Maximum Voltage [V] |
| 0…3 | H, K | 5000 | 600 |
| 4…5 | H, K | 10 000 | |
| 0…5 | J, R | 100 000 | |
| 6 | L | 18 000 | |
| 7 | L | 18 000 | |
| Combination Lighting Contactors with Disconnect Switch: Bulletin 502L | |||
| Lighting Contactor Rating [A] | Fuse Type | Available Short Circuit Amperes RMS Symmetrical [A] | Maximum Voltage [V] |
| 20…100 | H, K | 5000 | 600 |
| 200…300 | H, K | 10 000 | |
| 20…300 | J, R | 100 000 | |
| Combination Contactors and Starters with Circuit Breaker: Bulletin 503, 507, 513, 523E, 523F, 523G, and 1233X | |||
| Enclosure Type | NEMA Size | Available Short Circuit Amperes RMS Symmetrical [A] | Maximum Voltage [V] |
| 1, 3R, 3R/4/12, 4/4X (stainless) | 0…5 | 65 000 | 480 |
| 4/4X (non-metallic) | 0…5 | 22 000 | |
| Unilock 3R, 7, & 9 | 0…5 | 65 000 | |
| Bolted 3R, 7, & 9 | 0…2 | 65 000 | |
| 1, 3R, 3R/4/12, 4/4X (stainless) | 0…5 | 25 000 | 600 |
| 4/4X (non-metallic) | 0…3 | 5000 | |
| 4/4X (non-metallic) | 4…5 | 10 000 | |
| Unilock 3R, 7, & 9 | 0…3 | 5000 | |
| Unilock 3R, 7, & 9 | 4…5 | 10 000 | |
| Bolted 3R, 7, & 9 | 0…2 | 5000 | |
| 3R, 3R/4/12 | 6…7 | 10 000 | |
| Combination Lighting Contactors with Circuit Breaker: Bulletin 503L | |||
| Enclosure Type | Lighting Contactor Rating [A] | Available Short Circuit Amperes RMS Symmetrical [A] | Maximum Voltage [V] |
| 1, 3R, 3R/4/12, 4/4X (stainless) | 20…300 | 65 000 | 480 |
| 4/4X (non-metallic) | 20…300 | 22 000 | |
| Unilock 3R, 7, & 9 | 20…300 | 65 000 | |
| Bolted 3R, 7, & 9 | 20…300 | 65 000 | |
| 1, 3R, 3R/4/12, 4/4X (stainless) | 20…300 | 25 000 | 600 |
| 4/4X (non-metallic) | 20…100 | 5000 | |
| 4/4X (non-metallic) | 20…300 | 10 000 | |
| Unilock 3R, 7, & 9 | 20…100 | 5000 | |
| Unilock 3R, 7, & 9 | 20…300 | 10 000 | |
| Bolted 3R, 7, & 9 | 20…300 | 5000 | |
AC Coil Data
| NEMA Size | Operating Volt Amperes Burden [VA] | Heat Dissipation [W] | Coil Operating Limits | |
| 60 Hz Coils | ||||
| Inrush | Sealed | |||
| 00 | 70 | 8 | 2.7 | 85…110% |
| 0 | 192 | 29 | 5.9 | |
| 1 & 1P | 192 | 29 | 5.9 | |
| 2 (2…3 poles) | 240 | 29 | 5.9 | |
| 2 (4…5 poles) | 315 | 38 | 5.9 | |
| 3 (2…3 poles) | 660 | 45 | 10 | |
| 3 (4…5 poles) | 840 | 58 | 10 | |
| 4 (2…3 poles) | 1225 | 69 | 14.8 | |
| 4 (4…5 poles) | 1490 | 96 | 14.8 | |
| 5 (Series L) | 1490 | 96 | 19.8 | |
| 6¬ | 4860 | 254 | 65.7 | |
| 6 (Interposing relay) | 52.44 | 3.96 | — | |
| 7T | Economized DC Coil | — | ||
| 7 (Interposing relay) | 74.40 | 9.84 | — | |
| 8 | Economized DC Coil | — | ||
| 8 (Interposing relay) | 74.40 | 9.84 | — | |
| 9§ | Economized DC Coil | — | ||
| 9 (Interposing relay) | 144 | 19.20 | — | |
| ¬ This rating is for the size 6 contactor coil only. All starters are shipped with an interposing relay as standard. | ||||
| T Size 7 starters are shipped with a 250 VA control circuit transformer and an interposing relay with a 120V coil. Voltage is then rectified to DC for the contactor coil. | ||||
| Size 8 starters are shipped with a 350 VA control circuit transformer and an interposing relay with a 120V coil. Voltage is then rectified to DC for the contactor coil. | ||||
| § Size 9 starters are shipped with a 750 VA control circuit transformer and an interposing relay with a 120V coil. Voltage is then rectified to DC for the contactor coil. | ||||
Auxiliary Contacts (NEMA A600 and P300) — Bulletin 595, 596
| Maximum AC Contact Rating Per Pole | ||||||
| AC Rating Designation |
Maximum Voltage 60 or 50 Hz |
[A] | Continuous Carrying Current [A] |
[VA] | ||
| Make | Break | Make | Break | |||
| A600 | 120 | 60 | 6 | 10 | 7200 | 720 |
| 240 | 30 | 3 | 10 | 7200 | 720 | |
| 480 | 15 | 1.5 | 10 | 7200 | 720 | |
| 600 | 12 | 1.2 | 10 | 7200 | 720 | |
| Maximum DC Contact Rating Per Pole for 595, 596 Auxiliary Contacts (Maximum Continuous Carrying Current is 5 A) | ||||||
| DC Rating Designation |
125V DC | 250V DC | 600V DC | |||
| P300 | 0.55 A | 0.55 A (Requires 2 Contacts in Series) |
— | |||
| 1.1 A (Requires 2 Contacts in Series) |
||||||
Load-Life Curves
Bulletin 500 Line contactors and starters are designed to provide superior performance in a variety of applications. These load-life curves are based on Rockwell Automation tests according to the requirements defined in IEC 947-4. Actual contact life may vary based on the application, duty cycle, and environmental conditions from that indicated by the curves.
To find the contactors estimated electrical life, follow these guidelines:
- Choose the appropriate graph that most closely approximates the utilization category of the application.
- Locate the intersection of the life-load curve of the appropriate contactor with the applications operational current (Ie) found on the horizontal axis.
- Read the estimated contact life in millions of operations along the vertical axis.
Contact Life for Mixed Utilization Categories AC3 and AC4
In many applications, the utilization category cannot be defined as either purely AC3 or AC4. In those applications, the electrical life of the contactor can be estimated from the following equation:
|
Utilization Categories
Category Typical Duty
AC3 Starting of squirrel cage motors and switching off only after the motor is up to speed.
AC4 Starting of squirrel cage motors with inching and plugging duty.
Bulletin 500 Load/ Life Curves — AC3 and AC4
|
|
