Reduced Voltage Starters, Combination Starters, and Pump Control Panels

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Contactors, Starters, and Overload Relays > Reduced Voltage Starters, Combination Starters, and Pump Control Panels > Bulletin 540 Wye-Delta Starters

Bulletin 540 Wye-Delta Starters

Introduction Standards Compliance and Certifications Configuration of a Basic Starter Product Selection Modifications for Combination Devices
Accessories Specifications Full Load Motor Currents Approximate Dimensions Renewal Parts
Product Selection

Heater Elements — Starters with eutectic alloy overload relays require 3 overload heater elements. Located on Eutectic Alloy Overload Relay Heater Elements.
NEMA Size Continuous Ampere Rating [A] Maximum Horsepower Rating
Full Load Current
Must Not Exceed
“Continuous Ampere Rating”
Type 1
General Purpose
Type 3R/4/12
Rainproof, watertight, dusttight
Motor Voltage Open Circuit
Transition
Open Circuit
Transition
200V 230V 460…
575V
Cat. No. Cat. No.
1YD 47 10 10 10…15 540-LAÄ-µ 540-LFÄ-µ
2YD 78 15…20 15…25 20…40 540-MAÄ-µ 540-MFÄ-µ
3YD 156 25…40 30…50 50…75 540-PAÄ-µ 540-PFÄ-µ
4YD 233 50…60 60…75 100…150 540-SAÄ-µ 540-SFÄ-µ
5YD 467 75…150 100…150 200…300 540-UAÄ-µ 540-UFÄ-µ
  

Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 540-LAÄ-µ becomes Cat. No. 540-LAB-µ. For other voltages, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.

[V] 208 230…240 460…480 575…600
Common Control AC,
60 Hz
H A B C
Transformer Control (See ¬ Note: )
120V Separate Control (without transformer) HD AD BD CD
  

µ Overload Relay Code

Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset)
to complete the cat. no. Example: Cat. No. 540-LAB-µ becomes Cat. No. 540-LAB-A2D.