Bulletin 540 Wye-Delta Starters
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Starter | Product Selection | Modifications for Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
| Heater Elements — Starters with eutectic alloy overload relays require 3 overload heater elements. Located on Eutectic Alloy Overload Relay Heater Elements. | ||||||
| NEMA Size | Continuous Ampere Rating [A] | Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Type 1 General Purpose |
Type 3R/4/12 Rainproof, watertight, dusttight |
||
| Motor Voltage | Open Circuit Transition |
Open Circuit Transition |
||||
| 200V | 230V | 460… 575V |
Cat. No. | Cat. No. | ||
| 1YD | 47 | 10 | 10 | 10…15 | 540-LAÄ-µ | 540-LFÄ-µ |
| 2YD | 78 | 15…20 | 15…25 | 20…40 | 540-MAÄ-µ | 540-MFÄ-µ |
| 3YD | 156 | 25…40 | 30…50 | 50…75 | 540-PAÄ-µ | 540-PFÄ-µ |
| 4YD | 233 | 50…60 | 60…75 | 100…150 | 540-SAÄ-µ | 540-SFÄ-µ |
| 5YD | 467 | 75…150 | 100…150 | 200…300 | 540-UAÄ-µ | 540-UFÄ-µ |
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 540-LAÄ-µ becomes Cat. No. 540-LAB-µ. For other voltages, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
| [V] | 208 | 230…240 | 460…480 | 575…600 | |
| Common Control | AC, 60 Hz |
H | A | B | C |
| Transformer Control (See ¬ Note: ) | |||||
| 120V Separate Control (without transformer) | HD | AD | BD | CD | |
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no. Example: Cat. No. 540-LAB-µ becomes Cat. No. 540-LAB-A2D.