Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Contactors, Starters, and Overload Relays > Reduced Voltage Starters, Combination Starters, and Pump Control Panels > Bulletin 532 & 1282 Part Winding Combination Starters and Pump Panels
Bulletin 532 & 1282 Part Winding Combination Starters and Pump Panels
| Introduction | Standards Compliance and Certifications | Configuration of a Basic Starter | Product Selection | Modifications for Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
| Heater Elements — Starters with eutectic alloy overload relays require 6 overload heater elements. Located on Eutectic Alloy Overload Relay Heater Elements. | |||||||||
| NEMA Size | Continuous Ampere Rating [A] | Maximum Horsepower Rating Full Load Current Must Not Exceed Continuous Ampere Rating |
Type 1 General Purpose¬ |
Type 3R/4/12 Rainproof, watertight, dusttight¬ |
Type 3R Rainproof with extra panel space¬ |
||||
| Motor Voltage | Fuse Rating [A] | ||||||||
| 200V | 230V | 460V | 575V | Cat. No. | Cat. No. | Cat. No. | |||
| 1PW | 54 | — | — | 15 | 15 | 30 | 532-LAÄ-µ-µ-24R | 532-LFÄ-µ-µ-24R | 1282-LNÄ-µ-µ-24R |
| 10 | 10 | — | — | 60 | 532-LAÄ-µ-µ-25R | 532-LFÄ-µ-µ-25R | 1282-LNÄ-µ-µ-25R | ||
| 2PW | 90 | — | — | — | 20 | 30 | 532-MAÄ-µ-µ-24R | 532-MFÄ-µ-µ-24R | 1282-MNÄ-µ-µ-24R |
| — | 15 | 30 | 40 | 60 | 532-MAÄ-µ-µ-25R | 532-MFÄ-µ-µ-25R | 1282-MNÄ-µ-µ-25R | ||
| 20 | 25 | 40 | — | 100 | 532-MAÄ-µ-µ-26J | 532-MFÄ-µ-µ-26J | 1282-MNÄ-µ-µ-26J | ||
| 3PW | 180 | — | — | 50 | 60 | 100 | 532-PAÄ-µ-µ-26R | 532-PFÄ-µ-µ-26R | 1282-PNÄ-µ-µ-26R |
| 40 | 50 | 75 | 75 | 200 | 532-PAÄ-µ-µ-27J | 532-PFÄ-µ-µ-27J | 1282-PNÄ-µ-µ-27J | ||
| 4PW | 270 | 50 | — | 100 | 150 | 200 | 532-SAÄ-µ-µ-27R | 532-SFÄ-µ-µ-27R | 1282-SNÄ-µ-µ-27R |
| 75 | 75 | 150 | — | 400 | 532-SAÄ-µ-µ-28J | 532-SFÄ-µ-µ-28J | 1282-SNÄ-µ-µ-28J | ||
| 5PW | 540 | 100 | 100 | 200 | 300 | 400 | 532-UAÄ-µ-µ-28R | 532-UFÄ-µ-µ-28R | 1282-UNÄ-µ-µ-28R |
| 150 | 150 | 350 | 350 | 600 | 532-UAÄ-µ-µ-29J | 532-UFÄ-µ-µ-29J | 1282-UNÄ-µ-µ-29J | ||
Ä Coil Voltage Code
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example:
Cat. No. 1282-LNÄ-µ-µ-24R becomes Cat. No. 1282-LNB-µ-µ-24R. For other voltages, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
| [V] | 208 | 230...240 | 460...480 | 575...600 | |
| Common Control | AC, 60 Hz | H | A | B | C |
| Transformer Control (See ¬ Note: ) | |||||
| 120V Separate Control (without transformer) | AD | AD | CD | CD | |
µ Overload Relay Code
Use to order solid-state overload relay. Do not use when ordering eutectic alloy overload relay. The cat. no. as listed is incomplete. Select an overload relay code from E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset) to complete the cat. no. Example: Cat. No. 1282-LNB-µ-µ-24R becomes
Cat. No. 1282-LNB-A2D-A2D-24R.
¬ Non-Fusible Disconnect Type
Cat. nos. listed above include a fusible disconnect switch with Class R or J fuse clips. To order a non-fusible disconnect switch, eliminate the fuse clip code from the cat. no. Example: Cat. No. 532-MFB-24R becomes Cat. No. 532-MFB.