Reduced Voltage Starters, Combination Starters, and Pump Control Panels

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Contactors, Starters, and Overload Relays > Reduced Voltage Starters, Combination Starters, and Pump Control Panels > Catalog Number Explanation

Catalog Number Explanation

Configuration of a Basic Starter

The information below is for reference purposes. Not all combinations will produce a valid cat. no. Refer to the tables on the following pages for product selection.

Example Catalog Number

530    L    A    B A2D 1 90
a    b    c    d    e    f      

a
Bulletin Number
Code Description
530 Part winding reduced voltage starter
532 Part winding reduced voltage combination starter with disconnect switch
533 Part winding reduced voltage combination starter with circuit bBreaker
540 Wye delta reduced voltage starter
542 Wye delta reduced voltage combination starter with disconnect switch
543 Wye delta reduced voltage combination starter with circuit breaker
570 Autotransformer reduced voltage starter
572 Autotransformer reduced voltage combination starter with disconnect switch
573 Autotransformer reduced voltage combination starter with circuit breaker
1242 Wye delta reduced voltage pump panel with disconnect switch
1243 Wye delta reduced voltage pump panel with circuit breaker
1272 Autotransformer reduced voltage pump panel with disconnect switch
1273 Autotransformer reduced voltage pump panel with circuit breaker
1282 Part winding reduced voltage pump panel with disconnect switch
1283 Part winding reduced voltage pump panel with circuit breaker

b
Starter Size
Suffix Code NEMA Size
C 2
D 3
E 4
F 5
G 6
L 1YD or 1PW
M 2YD or 2PW
P 3YD or 3PW
S 4YD or 4PW
U 5YD or 5PW

c
Enclosure Code
Code Type
A Type 1: general purpose painted enclosure with screw fasteners, external overload relay reset
F Type 3/4/12: rainproof, watertight, dusttight, painted metal enclosure with screw fasteners, external overload relay reset
N Type 3R: rainproof, painted metal extra capacity enclosure with screw fasteners, external overload relay reset

d
Coil Voltage
Votlage Code Description Line
Voltage [V]
Coil
Voltage [V]
H Common Control (without a transformer) 208 208
A 240 240
B 480 480
C 600 600
H Transformer Control¬  208 120
A 240 120
B 280 120
C 600 120
HD Separate Control (without a transformer) 208 120
AD 240 120
BD 480 120
CD 600 120

e
Overload Relay
Code Type
None Eutectic Alloy
See E1 Plus Solid-State Overload Relay
(Selectable Class 10, 20, or 30) (Automatic/Manual Reset)
Solid-State

f
Options
See For Use on Bulletins 502, 502L, 503, 503L, 506, 506X, 507, 507X, 512, 512H, 512M, 512V, 513, 513H, 513M, 513V, 522, 522E, 522F, 522G, 523, 523E, 523F, 523G, 530, 532, 533, 540, 542, 543, 570, 572, 573, 1242, 1243, 1272, 1273, 1232X, 1232V, 1233X, and 1233V, Continued

¬ Note:When selecting a factory-installed control circuit transformer, use the transformer control coil voltage code to denote the transformer primary voltage. The transformer secondary voltage and starter coil will both be 120V AC by default. Example: Cat. No. 532-LAB-6P-24R will have a transformer with a 480V primary voltage, 120V secondary voltage, and a 120V starter coil voltage.