Bulletin 300 AC Contactor

Click to enlarge - 300_Family_GS


Bulletin 300


Bulletin 300 modular line of NEMA contactors, when combined with Bulletin 193 solid-state overload relays, auxiliary contacts, interlocks, suppressors, and DIN mounting rail provides the most compact and flexible starter component system available.

Standards Compliance and Certifications

Standards Compliance

UL 508
CSA C22.2, No. 14


Certifications

cULus Listed (File E41850
Guide No. NLDX, NLDX7)
CE Marked (EN 60947-4-1)


Product Selection

Feed-Through Wiring for Motor Loads

NEMA Size¬  Continuous Ampere Rating [A] Maximum Horsepower Rating
Full Load Current Must Not Exceed “Continuous Ampere Rating”
Open Type Without Enclosure
Motor Voltage
200V 230V 380…415V 460…575V Cat. No.
0 18 3 3 5 5 300-AOÄ930
1 27 7.5 7.5 10 10 300-BOÄ930
2 45 10 15 25 25 300-COÄ930
3 90 25 30 50 50 300-DOÄ930
4 135 40 50 75 100 300-EOÄ930
5 270 75 100 150 200 300-FOÄ930
  
¬ Contactor sizes 0…3 come standard with 1 N.O. auxiliary contact.
Contactor sizes 4…5 come standard with 1 N.O. and 1 N.C. auxiliary contact.

Ä Coil Voltage Code and Terminal Position (NEMA Sizes 0…2)

The cat. no. as listed is incomplete. To complete the cat. no., select a Coil Voltage Code from the table below and insert into the cat. no. Example: 120V, 60 Hz: Cat. No. 300-AOÄ930 becomes Cat. No. 300-AOD930.

  [V] 24 48 100 100… 110 110 120 200 200… 220 208 208… 240
AC, 50 Hz K Y KP D P KG L
AC, 60 Hz J X KP D KG H L
AC, 50/60 Hz KJ KY KP KD KG
DC EJ
  

  [V] 220… 230 230… 240 240 277 347 380 380… 400 400… 415 440 480 500 550 600
AC, 50 Hz F VA T N G B M C
AC, 60 Hz A T I E N B C
AC, 50/60 Hz KA KB
  

Coil Terminal Position

All contactors are delivered with the coil terminals located on the line side.

Click to enlarge - 100C_104C-68-1
Cat. No. 300-AOÄ930 Line Side


Ä Coil Voltage Code (NEMA Sizes 3…5)

Conventional Coil [V] 24 48 110 120 208 200…230 240 277 380…400 415 440 480 500 550 600
NEMA Size 3…4 AC, 50 Hz K Y D A T N B G M C
AC, 60 Hz J X D H A T N B C
  

Electronic Coil with EI Interface‡  [V] 24 42…64 100 110…130 200 208…277 380…415 440…480 500 600
NEMA Size 3…5 AC, 50/60 Hz EJ EY EP ED EG EA EN EN EN
  
‡ Signal voltage of the Bulletin 300 line electronic interface: Nominal Ue: 24V DC/Ie: 15 mA
Pick-up voltage: 13.0…30.2V DC
Drop-out voltage: -3.0…+5.0V DC

Ä Coil Voltage Code

Electronic Coil with EI InterfaceT  [V] 24 48…72 110…130 200…255
NEMA Size 3…5 DC EZJ EZY EZD EZA
  
T Signal voltage of the 300 Line electronic interface: Nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0…30.2V DC, Dropout Voltage: -3.0…+5.0V DC.

Bulletin 193-EE – Three-Phase Devices


Mounts to NEMA Contactor Size Adjustment Range [A] Cat. No.
0…1 1.0…5.0 193-EECD
3.2…16 193-EEDD
5.4…27 193-EEED
2 5.4…27 193-EEEE
9…45 193-EEFE
3…4 30…150 193-EEHF
40…200 193-EEJF
5 40…200 193-EEJG
60…300 193-EEKG
  

E3 Overload Relay


NEMA Size Adjustment Range [A] Cat. No. Cat. No.
0…1 1…5 193-EC1AD 193-EC2AD
3…15 193-EC1BD 193-EC2BD
5…25 193-EC1CD 193-EC2CD
9…45 193-EC1DD 193-EC2DD
2 9…45 193-EC1DE 193-EC2DE
18…90 193-EC1EE 193-EC2EE
3…4 28…140 ¬  193-EC1FF ¬  193-EC2FF
4 42…210 ¬  193-EC1GF ¬  193-EC2GF
5 42…210 ¬  193-EC1GG ¬  193-EC2GG
60…302 ¬  193-EC1HG ¬  193-EC2HG
  
¬ Does not include terminal lugs.

E3 and E3 Plus Solid-State Overload Relays

Panel Mount Devices for use with External Current TransformersT ‡ 

Description Adjustment Range [A]§  Cat. No.
  • 2 Inputs

  • 1 Output
  • 9…5000 193-EC1ZZ
  • 4 Inputs

  • 2 Outputs

  • External Ground Fault Sensor Input

  • PTC Thermistor Input

  • DeviceLogix
  • 9…5000 193-EC2ZZ
      
    T Current transformers supplied by customer. Refer to Specifications, Main Circuits for proper current transformer selection.
    ‡ Order panel adapter, Cat. No. 193-ECPM2, separately.
    § CT Ratio to FLA setting range correlation.

    CT Ratio FLA Setting
    Range [A]
    CT Ratio FLA Setting
    Range [A]
    CT Ratio FLA Setting
    Range [A]
    50:5 9…45 300:5 60…302 1200:5 240…1215
    100:5 18…90 500:5 84…420 2500:5 450…2250
    150:5 28…140 600:5 125…630 5000:5 1000…5000
    200:5 42…210 800:5 172…860
      

    Accessories

    Auxiliary Contacts

      Description Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a For Use With Cat. No. Bifurcated Auxiliary Contact Cat. No.
    N.O. N.C.
    Click to enlarge - 100-C_104-C-86-3 Auxiliary Contact Blocks for Front Mounting¬ 
    - 2- and 4-pole
    - Quick and easy mounting without tools
    - Electronic-compatible contacts down to
    17V, 5 mA
    - Mechanically linked performance between N.O. and N.C. poles and to the main contactor poles (except for L types)
    - Models with equal function with several terminal numbering choices
    L = Late break N.C./early make N.O.
    0 2 0…2 100-FA02 100-FAB02
    1 1 100-FA11 100-FAB11
    2 0 100-FA20 100-FAB20
    1L 1L 100-FBL11
    Click to enlarge - 100-C_104-C-86-4 0 4 100-FA04 100-FAB04
    1 3 100-FA13 100-FAB13
    2 2 100-FA22 100-FAB22
    3 1 100-FA31 100-FAB31
    4 0 100-FA40 100-FAB40
    1+1L 1+1L 100-FAL22
    Click to enlarge - 100-C_104-C-86-9 Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations¬ 
    - 1- and 2-pole
    - Two-way numbering for right or left mounting on the contactor
    - Quick and easy mounting without tools
    - Electronic-compatible contacts down to
    17V, 10 mA
    - Mirror contact performance to the main contactor poles
    L = Late break N.C./early make N.O.
    0 1 0…2 100-SB01
    1 0 100-SB10
    0 2 100-SB02
    Click to enlarge - 100-C_104-C-86-11 1 1 100-SB11
    2 0 100-SB20
    1L 1L 100-SBL11
      
    ¬ Max. number of auxiliary contacts that may be mounted:
        AC coil contactors — max. 4 N.O. contacts on the front of the contactor, 2 N.O. contacts on the side, 4 N.C. front or side, 6 total.
        DC coil contactors — max. 4 N.O. contacts on the front of the contactor or max 2 N.O. contacts on the side, 4 N.C. front or side, 4 total.

    Control Modules

      Description For Use With Cat. No. Price €
    Click to enlarge - 100-C_104-C-87-1 Pneumatic Timing Modules
    Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.
    On-Delay  
    0.3…30 s Range
    0…2 with AC coils
    100-FPTA30
     
    1.8…180 s Range 100-FPTA180  
    Off-Delay  
    0.3…30 s Range
    0…2
    100-FPTB30
     
    1.8…180 s Range 100-FPTB180  
    Click to enlarge - 100-ETA3 L_gs- Electronic Timing Modules — On-Delay
    Delay of the contactor or control relay solenoid.
    The contactor or control relay is energized at the end of the delay time.
    On-Delay  
    0.1…3 s Range
    0…2   
    100-ETA3
     
    1…30 s Range 100-ETA30  
    10…180 s Range 100-ETA180  
      
    110…240V, 50/60 Hz
    110…250V DC
       
    Click to enlarge - 100-ETB3 L_gs Electronic Timing Modules — Off-Delay
    Delay of the contactor or control relay solenoid.
    After interruption of the control signal, the contactor or control relay is de-energized at the end of the delay time.
    Off-Delay  
    0.3…3 s Range
    0…2 with AC coils   
    100-ETB3
     
    1…30 s Range 100-ETB30  
    10…180 s Range 100-ETB180  
      
    110…240V, 50/60 Hz
       
    Click to enlarge - 100-C_104-C-87-9 Electronic Timing Modules
    Delay of the contactor solenoid. Contactor K 3 (Y) is de-energized (off) and K 2 (D) is energized (on) after the end of the set Y end time. (Switching delay at 50 ms.)
    Continuous adjustment range
    High repeat accuracy
    Transition Time Y Contactor
    1…30 s Range  

    110…240V, 50/60 Hz
    0…2 with AC coils 100-ETY30  
    Click to enlarge - 100-C_104-C-87-11 Mechanical Interlocks
    For interlocking of two contactors.
    Common interlock for all Bul. 100-C contactor sizes
    Interlocking of different sizes possible
    Mechanical and electrical interlocking possible in one module by means of integrated auxiliary contacts
    9 mm dovetail connector included
    Mechanical only
    without auxiliary contacts
    0…2 100-MCA00  
    Mechanical/ electrical
    with 2 N.C. auxiliary contacts
    0…2 100-MCA02  
    Click to enlarge - 100-C_104-C-87-15 Description For Use With Voltage Range Cat. No. Price €
    Mechanical Latch
    Following contactor latching, the contactor coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66).
    Electrical or manual release
    1 N.O. + 1 N.C. auxiliary contacts
    Suitable for all Bul. 100-C contactor sizes, 9…85 A
    0…2 with AC coils 100-FL11Ä  
    Click to enlarge - 100-C_104-C-88-1 DC Interface (electronic)
    Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor/control relay.
    Control (input) voltage
    12V DC
    18…30V DC (24V nominal)
    48V DC
    Requires no additional surge suppression on the relay coils
    0…2 with AC coils 100-JE  
    Click to enlarge - 100-C_104-C-88-3 Surge Suppressors
    For limitation of coil switching transients.
    Plug-in, coil mounted.
    Suitable for all 100-C contactor sizes, 9…85 A.
    RC, varistor, and diode versions.
    RC Module
    AC operating mechanism
    0…2 with AC coils 24…48V AC, 50/60 Hz 100-FSC48  
    110…280V AC, 50/60 Hz 100-FSC280  
    380…480V AC, 50/60 Hz 100-FSC480  
    Varistor Module
    AC/DC operating mechanism
    0…2 12…55V AC/ 12…77V DC 100-FSV55  
    56…136V AC/ 78…180V DC 100-FSV136  
    137…277V AC/ 181…350V DC 100-FSV277  
    278…575V AC 100-FSV575  
      

    Ä Voltage Suffix Code

    The cat. no. as listed is incomplete. Select a voltage suffix code from the table below to complete the cat. no. Example: 120V, 60 Hz:
    Cat. No. 100-FL11Ä becomes Cat. No. 100-FL11D.


    Voltage¬  24V 48V 100V 110V 120V 230-240V 240V 277V 380-400V 400-415V 440V 480V
    50 Hz K Y KP D VA T N G B
    60 Hz J D A T N B
      
    ¬ For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

    Assembly Components

      Description For Use With Pkg. Quantity Cat. No.
    Click to enlarge - 100-C_104-C-88-7 Dovetail Connectors
    For use in contactor and starter assemblies.
    Single Connector — 0 mm Spacing
    0…2 10 100-S0
    Cat. No. 100-S0 Dovetail Connectors
    For use in contactor and starter assemblies.
    Dual Connector — 9 mm Spacing
    100-S9
    Click to enlarge - 100-C_104-C-88-8 Protective Covers
    Provides protection against unintended manual operation
    For contactors and front mounted auxiliary contacts, pneumatic timers and latches
    0…2 1 100-SCCA
    Cat. No. 100-SCCA
    Click to enlarge - 100-C_104-C-88-9 100-FA, -FB, -FC, -FP, -FL; 10 100-SCFA
    Cat. No. 100-SCFA
    Click to enlarge - 100-C_104-C-88-10 Reversing Power Wiring Kits
    For reversing connection with a solid-state or thermal overload relay
    0…1 1 105-PW37
    Cat. No. 105-PW23 2 105-PW85
    Click to enlarge - 100-C_104-C-88-11 DIN (#3) Symmetrical Rail
    35 x 7.5 x 1 m
    0…2 10 199-DR1
      

    Auxiliary Contacts

        Description Click to enlarge - 100M-66-3 Click to enlarge - 100M-66-4 Connection Diagram For Use With Cat. No. Price €
    No. of N.O. Contacts No. of N.C. Contacts
    Click to enlarge - 100-DS_GS Click to enlarge - 100-MCA00_GS Auxiliary Contacts
    Side mounted
    With IEC sequence terminal designations
    1 1 Click to enlarge - 100D-91-5 3…5
    Left/Right inside mounting
    100-DS1-11  
    1 1 Click to enlarge - 100D-91-6 3…5
    Left/Right outside mounting
    100-DS2-11  
    1 1L Click to enlarge - 100-DS1-L11_Dia 3…5
    Left/Right inside mounting
    100-DS1-L11  
    2 0 Click to enlarge - 100D-91-8 100-DS1-20  
    2 0 Click to enlarge - 100D-91-9 3…5
    Left/Right outside mounting
    100-DS2-20  
    Auxiliary Contacts
    Electronically compatible auxiliary contacts
    Ideal for use when switching low-power control circuits
    With IEC sequence terminal designations
    Contact ratings:
    AC-12, 250V, 0.1 A
    AC-15, DC-13, 3...125V, 1...100 mA
    1 1 Click to enlarge - 100D-91-10 3…5
    Left/Right inside mounting
    100-DS1-B11  
      

    Marking Systems

      Description Pkg. Qty.¬  Cat. No. Price €
    Click to enlarge - 100-C_104-C-89-2 Label Sheet
    105 self-adhesive paper labels each, 6 x 17 mm
    10 100-FMS  
    Click to enlarge - 100-C_104-C-89-3 Marking Tag Sheet
    160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
    10 100-FMP  
    Transparent Cover
    To be used with marking tag sheets
    100 100-FMC  
    Click to enlarge - 100-FMA1 Marking Tag Adapters
    To be used with marking tag
    100 100-FMA1  
    Marking Tag Adapters
    To be used with marking tag
    100 100-FMA2  
      
    ¬ Must be ordered in multiples of package quantities.

    Suppressor Modules

      Description Circuit Diagram Suppressor Rating For Use With NEMA Sizes Cat. No. Price €
    Click to enlarge - 100-DFSC48_GS Suppressor Module for Bul. 100-D Contactors
    •   For limiting surge voltage when coil circuits are interrupted
    •   Can be plugged into all Bul. 100-D contactors
    •   Supplied as standard on all conventional DC coil contactors and all electronic coil contactors (as part of the supply module or delivered with separate suppressor module)
    Click to enlarge - 100D-92-2 RC Module (AC control) for contactors with conventional coil
    21...48V, 50 Hz; 24...55V, 60 Hz
    3…4

    100-DFSC48


    95...110V, 50 Hz; 110...127V, 60 Hz 100-DFSC110  
    180...277V, 50 Hz; 208...277V, 60 Hz 100-DFSC240  
    380...550V, 50 Hz; 440...600V, 60 Hz 100-DFSC550  
    Click to enlarge - 100D-92-3 Varistor Module for contactors with conventional coil
    55V AC
    3…4



    100-DFSV55


    56...136V AC 100-DFSV136  
    137...277V AC 100-DFSV277  
    278...600V AC 100-DFSV575  
    208...277V AC¬  5 100-DFSV550  
      
    ¬ For overvoltage category IV (IEC 947 for 100-D...-EI) e.g., lightning protection requirements.

    Connecting Components

      Description Output
    Connection
    For Use With NEMA Sizes Terminal
    Connection
    Cat. No. Price €
    3…4 5
    Click to enlarge - 100-D180_VL Reversing: Input Connection
    Wye-Delta: Main-Delta connection
    50 mm2 X   Lugs, 100-DL… 100-D180-VL  
    120 mm2   X 100-D420-VL  
    Click to enlarge - 100-D180_VLTB 50 mm2 X   Terminal Blocks,
    100-DTB…
    100-D180-VLTB  
    120 mm2   X 100-D420-VLTB  
    Click to enlarge - 100-D180_VT Reversing: Output Connection
    Wye-Delta: Delta-Wye connection
    50 mm2 X   Lugs, 100-DL… 100-D180-VT  
    120 mm2   X 100-D420-VT  
    Click to enlarge - 100-D180_VTTB 50 mm2
    X   Terminal Blocks,
    100-DTB…
    100-D180-VTTB  
    120 mm2   X 100-D420-VTTB  
    Click to enlarge - 100-D420_VYTB Delta-Wye connection if 100-D95…180 is used as a Wye contactor 80 mm2 X Terminal Blocks,
    100-DTB…
    100-D420-VYTB  
    Click to enlarge - 100-D180_VYU Wye-Delta: Neutral bridge X   100-D180-VYU  
      X 100-D420-VYU  
    Click to enlarge - 100D_Acc_PowerWiringKits Power Wiring Kits (for contactors using 100-DL lug kits) NEMA Size 3…4
  • Reversing

  • Two-speed, or changeover

  • Wye-Delta/Star-Delta
  • 100-DPW180
    100-D180-VL
    100-DPY180
     
    NEMA Size 5
  • Reversing

  • Two-speed, or changeover

  • Wye-Delta/Star-Delta
  • 100-DPW420
    100-D420-VL
    100-DPY420
     
      

    Connecting Components, Continued

      Description For Use With NEMA Sizes Cat. No. Price €
    Click to enlarge - 100-DTB_GS Terminal Lugs
    Set of two
    Protection class IP2X per IEC 60529 and DIN 40 050
    3 100-DTB110  
    4, 193-EC_F, 193-EE_F 100-DTB180  
    5, 193-EC_G, 193-EF2C, 193-EE_G 100-DTB420  
    Click to enlarge - 100D-93-2 Terminal Lugs (UL/CSA), Copper Frame
    Set of three
    3, 193-EC_F, 193-EF_A 100-DL110  
    3 (Elec. Coil) 100-DLE110  
    4, 193-EC_F, 193-EE_F 100-DL180  
    5, 193-EC_G, 193-EE_G 100-DL420  
    Terminal Lugs (UL/CSA), Aluminum Frame
    Set of 3
    3 100-DLA110  
    3 (Elec. Coil) and 4 100-DLA180  
    5 100-DLA420  
    Click to enlarge - 100D-93-3 Control Circuit Terminal
    2 x 2.5 mm2
    3…4 100-DAT1  
    5 100-DAT2  
    Click to enlarge - 100-DTS_GS Terminal Shields
    Set of two
    Protection class IP10 per IEC 60529 and DIN 40 050
    For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies
    3 100-DTS110  
    3 (Elec. Coil) and 4 100-DTS180  
    5 100-DTS420  
    Click to enlarge - 100D-93-5 Terminal Covers
    Protection class IP20 per IEC 60529 and DIN 40 050
    For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies
    3…4, 193-EC_F, 193-EE_F 100-DTC180  
    5, 193-EC_G, 193-EE_G 100-DTC420  
    Click to enlarge - Backplate-17335_gs Mounting Plate
    Galvanized steel plate for starter combinations
    For direct-on-line, reversing, two-speed, wye-delta/
    star-delta, and Dahlander assemblies
    3…4 Direct-on-line 100-DMS180  
    Reversing, two-speed or changeover 100-DMU180  
    Y-D or Dahlander 100-DMY180  
    5 Direct-on-line 100-DMS420  
    Reversing, two-speed or changeover 100-DMU420  
    Y-D or Dahlander 100-DMY420  
    Mounting Plate
    For two-speed or changeover switches
    For interlocking between size 2 and sizes 3…4 contactors 100-DMU85  
      

    Interlocks

      Description Circuit Diagram For Use With NEMA Sizes Cat. No. Price €
    Click to enlarge - 100-DMA00_GS Interlock — Mechanical Only
    No additional space required
    Click to enlarge - 100-KMHC 3…5 100-DMA00  
    Click to enlarge - 100-DMD02 Interlock — Dual Electrical/Mechanical
    No additional space required
    Two N.C. auxiliary contacts
    Click to enlarge - 100D-93-11 3…5 100-DMD02  
    Interlock — Mechanical Only
    No additional space required
    Click to enlarge - 100d_interlock-diagram 3…5 100-DMD00  
    Interlock — Mechanical Only
    Provides interlocking between Bul. 100-C and Bul. 100-D contactors
    Click to enlarge - 100d_interlock-diagram 2…4 100-DMC00  
    Interlock — Dual Electrical/Mechanical
    Provides interlocking between Bul. 100-C and Bul. 100-D contactors
    Two N.C. auxiliary contacts
    Click to enlarge - 100D-93-11 2…4 100-DMC02  
      

    Approximate Dimensions

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    Contactors and Accessories

    Click to enlarge - 300_ContactorDims   Click to enlarge - 300_DINDim
      DIN Mounting Rail
    Cat. No. 199-DR1

    Mounting Position

    Click to enlarge - 300_MountingPosition


    AC Contactors

    NEMA Size a b c c1 c2 Æd d1 d2 Approx. Shipping Wt.
    kg (lbs)
    0, 1 45
    (1-25/32)
    81
    (3-3/16)
    97.5
    (4)
    92.6
    (3-49/64)
    6.5
    (17/64)
    2 - 4.5
    (2 - 3/16)
    60
    (2-23/64)
    35
    (1-25/64)
    0.49
    (1.08)
    2 72
    (2-53/64)
    122
    (4-51/64)
    117
    (4-49/64)
    111.5
    (4-35/64)
    8.5
    (21/64)
    4 - 5.4
    (4 - 7/32)
    100
    (3-15/16)
    55
    (2-11/64)
    1.45
    (3.20)
      

    Accessories

    Contactors with mm (inches)
    Auxiliary contact block for front mounting 2- or 4-pole c/c1 + 39 (c/c1 + 1-37/64)
    Auxiliary contact block for side mounting 1- or 2-pole a + 9 (a + 23/64)
    Pneumatic Timing Module   c/c1 + 58 (c/c1 + 2-23/64)
    Electronic Timing Module on coil terminal side b + 24 (b + 15/16)
    Mechanical Interlock on side of contactor a + 9 (a + 23/64)
    Mechanical Latch   c/c1 + 61 (c/c1 + 2-31/64)
    Interface Module on coil terminal side b + 9 (b + 23/64)
    Surge Suppressor on coil terminal side b + 3 (b + 1/8)
    ¬  Labeling with label sheet
    marking tag sheet with clear cover
    marking tag adapter for System V4/V5
    marking tag adapter for System Bul. 1492W
    + 0
    + 0
    + 5.5
    + 5.5
    (+ 0)
    (+ 0)
    (+ 7/32)
    (+ 7/32)
      

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    Contactors and Accessories, Continued

    Click to enlarge - CAB6_D13


    Mounting Position

    Click to enlarge - 100-d_mounting


    NEMA Size a b c c1 Æd d1 d2 Æe e1 e2 e3 e4
    3 120
    (4-23/32)
    170
    (6-11/16)
    156
    (6-9/64)
    110.5
    (4-11/32)
    5.2
    (13/64)
    145
    (5-23/32)
    100
    (3-15/16)
    M6 16
    (5/8)
    38.5
    (1-33/64)
    147
    (5-25/32)
    8
    (5/46)
    3 (elect. coil) and 4 120
    (4-23/32)
    170
    (6-11/16)
    156
    (6-9/64)
    110.5
    (4-11/32)
    5.2
    (13/64)
    145
    (5-23/32)
    100
    (3-15/16)
    M8 20
    (51/64)
    39
    (1-33/64)
    160
    (6-19/64)
    10
    (25/64)
    5 155
    (6-3/32)
    205
    (8-5/64)
    180
    (7-3/32)
    110.5
    (4-11/32)
    6.5
    (17/64)
    180
    (7-3/32)
    130
    (5-1/8)
    M10 25
    (63/64)
    48
    (1-57/64)
    193
    (7-39/64)
    12.5
    (1/2)
      

    Contactors with mm
    Auxiliary contact block ¬  100-DS1…
    100-DS2…
    a
    a + 13.5 each
    Mechanical Interlock 100-DM… a + a
    Frame terminal block 100-DTB110
    100-DTB180
    100-DTB420
    b + 7 each
    b + 7 each
    b + 8.5 each
    Label holder   c…+ 5
      
    ¬ Conventional DC coil contactors will accept only Cat. No. 100-DS2… auxiliary contacts.

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    E1 Plus Solid-State Overload Relays

    Click to enlarge - pg7-082803_40751_100-C Mounted


    NEMA Size Overload
    Cat. No.
    A
    Width
    B
    Height
    C
    Depth
    D E1 E2 F H1 H2
    0…1 193-EE__D
    193R-EE__D
    193S-EE__D
    45
    (1-25/32)
    146.6
    (5-25/32)
    101.2
    (3-63/64)
    4.5
    (3/16)
    13.9
    (35/64)
    24.5
    (31/32)
    104
    (4-3/32)
    60
    (2-23/64)
    35
    (1-3/8)
    2 193-EE__E
    193R-EE__E
    193S-EE__E
    72
    (2-53/64)
    192.3
    (7-37/64)
    120.4
    (4-3/4)
    5.4
    (7/32)
    23.8
    (15/16)
    29
    (1-9/64)
    125.5
    (4-15/16)
    100
    (3-15/16)
    55
    (2-11/64)
      

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    Panel Adapter Mounted

    Click to enlarge - pg8-082709_40751_Panel Adaptor Mounted


    Panel Adaptor
    Cat. No.
    Overload
    Cat. No.
    A
    Width
    B
    Height
    C
    Depth
    D E1 E2 F H1 H2 H3 J
    193-EPD 193-EE__D
    193R-EE__D
    193S-EE__D
    45
    (1-25/32)
    112.4
    (4-7/16)
    108.7
    (4-9/32)
    4.4
    (11/64)
    11.4
    (29/64)
    57.9
    (2-9/32)
    62.5
    (2-15/32)
    95
    (3-3/4)
    30
    (1-3/16)
    75
    (2-31/32)
    52.1
    (2-3/64)
    193-EPE 193-EE__E
    193R-EE__E
    193S-EE__E
    72
    (2-53/64)
    107.4
    (4-15/64)
    127
    (5/32)
    5.5
    (5/32)
    26.4
    (1-1/32)
    54.5
    (2-9/64)
    48.3
    (1-29/32)
    90
    (3-23/64)
    60
    (2-23/64)
    43.3
    (1-45/64)
      

    DIN Rail / Panel Adapter — Terminal Cross Sections

      Cat. No. 193-EPB ¬  Cat. No. 193-EPD ¬  Cat. No. 193-EPE
    Flexible-Stranded with Ferrule Single Conductor 1.0…4.0 mm2 2.5…16 mm2 4.0…35 mm2
    Torque 1.8 N·m 2.3 N·m 4.0 N·m
    Two Conductor 1.0…4.0 mm2 2.5…10 mm2 4.0…25 mm2
    Torque 1.8 N·m 2.3 N·m 4.0 N·m
    Coarse-Stranded/Solid Single Conductor 1.5…6.0 mm2 2.5…25 mm2 4.0…50 mm2
    Torque 1.8 N·m 2.3 N·m 4.0 N·m
    Two Conductor 1.5…6.0 mm2 2.5…16 mm2 4.0…35 mm2
    Torque 1.8 N·m 2.3 N·m 4.0 N·m
    Stranded/Solid Single Conductor 14…8 AWG 16…6 AWG 12…1 AWG
    Torque 16 lb·in 20 lb·in 35 lb·in
    Two Conductor 14…10 AWG 16…6 AWG 12…2 AWG
    Torque 16 lb·in 20 lb·in 35 lb·in
      
    ¬ For multiple conductor applications, the same size and style wire must be used.

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    Bulletin 300 Contactor with Overload Relay

    Click to enlarge - 193EC-148-1


    Overload
    Cat. No.
    NEMA Size A
    Width
    B
    Height
    B1 C
    Depth
    E1 E2
    without
    193-EIMD
    with
    193-EIMD
    193-EC__D 0…2 45
    (1-25/32)
    188.3
    (7-13/32)
    207.7
    (8-11/64)
    145.1
    (5-23/32)
    107
    (4-7/32)
    11.4
    (29/64)
    67.9
    (2-43/64)
    193-EC__E 2 72
    (2-53/64)
    236.1
    (9-19/64)
    255.5
    (10-1/16)
    173.2
    (6-13/16)
    124.6
    (4-29/32)
    11.4
    (29/64)
    89.8
    (3-17/32)
      

    Overload
    Cat. No.
    NEMA Size D1 D2 H J ÆD
    193-EC__D 0…2 60
    (2-23/64)
    35
    (1-3/8)
    104
    (4-3/32)
    2
    (5/64)
    ø4.2
    (11/64ø)
    193-EC__E 2 100
    (3-15/16)
    55
    (2-11/64)
    125.5
    (4-15/16)
    2
    (5/64)
    ø5.5
    (7/32ø)
      

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    Click to enlarge - E3_MCS_Plus


    Overload
    Cat. No.
    NEMA Size A
    Width
    B
    Height
    B1 C
    Depth
    D E1 E2
    without
    Terminal Covers
    with
    Terminal Covers
    193-EC__F 3 120
    (4-23/32)
    336.3
    (13-1/4)
    418
    (16-29/64)
    311.8
    (12-17/64)
    175.1
    (6-57/64)
    156
    (5-9/64)
    11.4
    (3/64)
    216.1
    (8-1/2)
    4 120
    (4-23/32)
    339.8
    (13-3/8)
    418
    (16-29/64)
    317.8
    (12-1/2)
    175.1
    (6-57/64)
    156
    (5-9/64)
    11.4
    (29/64)
    216.1
    (8-1/2)
    193-EC__G 5 155
    (6-1/10)
    385.8
    (15-3/16)
    487.4
    (19-29/64)
    360.8
    (14-1/5)
    198.9
    (7-53/64)
    180
    (7-3/32)
    11.4
    (29/64)
    255
    (10-3/64)
      

    Overload
    Cat. No.
    NEMA Size F G H J K L M
    193-EC__F 3 12.5
    (1/2)
    100
    (3-15/16)
    145
    (5-23/32)
    135
    (5-5/46)
    22.3
    (7/8)
    180.9
    (7-1/8)
    8 - 5.6
    (8 - 7/32)
    4 16
    (5/8)
    100
    (3-15/16)
    145
    (5-23/32)
    135
    (5-5/46)
    22.3
    (7/8)
    180.9
    (7-1/8)
    8 - 5.6
    (8 - 7/32)
    193-EC__G 5 21
    (53/64)
    130
    (5-1/8)
    180
    (7-3/32)
    140
    (5-1/2)
    23.5
    (15/16)
    204.7
    (8-1/16)
    8 - 6.5
    (8 - 17/64)
      

    Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.


    Panel Mount Adapters

    (For Use With Cat. No. 193-EC__D, 193- EC_ZZ)

    Click to enlarge - 193EC-149-2


    (For Use With Cat. No. 193-EC__E)

    Click to enlarge - 193EC-149-3