Bulletin 1494D Fixed-Depth Flange-Mounted Circuit Breakers
| Product Overview |
|
Bulletin 1494D — Fixed-Depth Flange-Mounted
Circuit Breaker Operating Mechanism
Industrial rated circuit breaker operating mechansim pre-assembled on a mounting bracket for use in flange constructed enclosures.
Circuit breaker operating mechanisms for use with Cutler-Hammer circuit breakers in a fixed depth enclosure.
- 3-pole, 600V AC rating
- 150…1200 A frame sizes
- Accessories — Field installed
- Can be used with enclosure Types 1, 12
- Lockable handle
- Available only for right-hand flange operation
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA C22.2, No. 14
Certifications
UL Recognized (File No. E3125, Guide No. NLDX2)
CSA Certified (File No. LR1234)
Product Selection
| Build a Catalog Number |
Circuit Breaker Operating Mechanism
The device is complete, and includes a handle, operating mechanism, and slide/bail mechanism all pre-assembled on a mounting bracket.
| 3-Pole Circuit Breaker★ | Operator | Slide or Bail | ||
| Brand | Frame Size [A] |
Frame Designation | Cat. No. | Cat. No. |
| Cutler-Hammer | 150 | EHD, FD, FDB, FDC, HFD, HMCP | 1494D-N4 | 1494D-N40 |
| 250 | JD, JDB, JDC, HJD, HMCP | 1494D-N5 | 1494D-N50 | |
| 400 | KD, KDB, KDC, HKD, HMCP | 1494D-N60 | ||
| 600 | LD, HLD, LDC, LA, HLA, LC, HLC | 1494D-N3 | 1494D-N31 | |
| 800 | MA, MDL, HMDL, HMA, MC, ND, HND, NDC | 1494D-N41 | ||
| 1200 | NB Tri-Pac | 1494D-N41T | ||
| 1200 | ND, HND, NDC, NB, HNB, NC, HNC | 1494D-N43 | ||
| ★ Circuit breakers to be provided by customer. | ||||
Accessories
Specifications
Bulletin 1494C, 1494F, 1494G, 1494R, 1494V Disconnect Switches
| Disconnect Switch Electrical Ratings | ||||||||
| Switch Size | 30 A | 60 A | 100 A | 200 A | 400 A | 600 A | ||
| Rated insulation voltage Ui (UL) IEC | (600) 660V | |||||||
| Ratings UL/CSA/NEMA |
Hp | 230V/60 Hz 460V/60 Hz 575V/60 Hz |
7.5 15 20 |
15 30 50 |
30 60 75 |
60 125 150 |
125 250 350 |
200 400 500 |
| 250V DC | 5 | 10 | 20 | 40 | 50 | 50 | ||
| Continuous Current |
600V AC 250V DC |
30 | 60 | 100 | 200 | 400 | 600 | |
| Ratings IEC Applications |
Maximum kW (AC23) |
220V/50 Hz 440V/50 Hz 550V/50 Hz |
5.5 11 15 |
11 22 37 |
22 45 55 |
48 90 110 |
90 185 257 |
150 295 375 |
| Auxiliary Contact Electical Ratings | ||||||||
| NEMA/EEMAC | B600, P300 | |||||||
| IEC Ratings | Ui 660V | Ith 10 A | ||||||
ACII Ux |
12…120V 220…240V 380…400V 500…600V |
Ie |
6 A 3 A 1.5 A 1.2 A |
|||||
| Low level switching | 5 mA @ 12V DC | |||||||
| Mechanical | ||||||||
| Degree of protection | Operating handles | Non-metallic Type 1, 3R, 4, 4X, 12, Painted Type 1, 3R, 4, 12 Stainless steel Type 4, 4X |
||||||
| Mechanical life (Typical) | 20 000 operations (30…200 A) 10 000 operations (400…600 A) |
|||||||
| Switching frequency (operations/hr) | 30, 60, 100, and 200 A sizes — 300 max. 400 and 600 A sizes — 240 max. |
|||||||
| Environmental | ||||||||
| Temperature | Operating | -35…+40 °C (-31…+104 °F) | ||||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||||
| Altitude (per IEC 947-5) | 2000 m per IEC 337-1 | |||||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F) | |||||||
| Design Specification/Test Requirements | ||||||||
| Dielectric strength | 2200V for 1 minute | |||||||
| Electrical life | 6000 operations at rated current | |||||||
| Short Circuit Withstand Capability | 10 000 A: unfused 10 000 A: with Class H fuses 200 000 A: with Class J or Class R fuses |
|||||||
| Construction | ||||||||
| Switch body material | Phenolic | |||||||
| Contact material | Copper, tin-plated | |||||||
| Terminals | 30 A 60 A 100 A 200 A 400 A 600 A |
#10 - 32 screw and self-lifting pressure plate 1/4 in. - 28 screw-lug, copper 5/16 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper 1/2 in. - 13 screw-lug, copper |
||||||
| All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire. | ||||||||
| Conductor Size (mm2) | 30 A 60 A 100 A 200 A 400 A 600 A |
#14…8 AWG (1.5…10 mm2) #14…4 AWG (2.5…16 mm2) #8…1/0 AWG (10…50 mm2) #6…4/0 AWG (16…95 mm2) 2 of #1/0 AWG…250 MCM (2 per lug) 2 of 185 mm2…250 MCM or (1) #4 AWG…500 MCM 2 of #1/0 AWG…350 MCM (2 per lug) 2 of 185 mm2…350 MCM or (1) #4 AWG…500 MCM |
||||||
| Recommended Torque | 30 A 60 A 100 A 200 A 400 A 600 A |
Conductor into Lug 20 lbin 45 lbin 150 lbin 275 lbin 325 lbin 325 lbin |
Lug to Terminal 20 lbin 50 lbin 90 lbin 175 lbin 175 lbin 275 lbin |
|||||
| Switches, Mechanisms, and Accessory Kits | Zinc-plated steel, RoHS Compliant finish | |||||||
Bulletin 1494H, 1494HL Disconnect Switches
| Disconnect Switch Electrical Ratings | ||||||
| Switch Size | 30 A | 60 A | 100 A | 200 A | ||
| Rated insulation voltage Ui (UL) IEC | (600) 660V | |||||
| Ratings UL/CSA/NEMA |
Hp | 230V/60 Hz 460V/60 Hz 575V/60 Hz |
10 20 30 |
20 50 60 |
40 75 100 |
60 125 150 |
| 250V DC | 5 | 10 | 20 | 40 | ||
| Continuous Current |
600V AC 250V DC |
30 | 60 | 100 | 200 | |
| Auxiliary Contact Electical Ratings | ||||||
| Continuous Current | 10 A | 15 A | ||||
| Pole Configuration | DPDT | DPDT | ||||
| Mechanical | ||||||
| Degree of protection | Operating handles | Painted Type 1, 3R, 12 | ||||
| Mechanical life (Typical) | 10 000 operations | |||||
| Switching frequency (operations/hr) | 300 maximum | |||||
| Environmental | ||||||
| Temperature | Operating | -35…+40 °C (-31…+104 °F) | ||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||
| Altitude (per IEC 947-5) | 2000 m per IEC 337-1 | |||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F) | |||||
| Design Specification/Test Requirements | ||||||
| Dielectric strength | 2200V for 1 minute | |||||
| Electrical life | 6000 operations at rated current | |||||
| Short Circuit Withstand Capability | 10 000 A: unfused 10 000 A: with Class H fuses 200 000 A: with Class J or Class R fuses (30…100 A) 100 000 A: with Class J or Class R fuses (200 A) |
|||||
| Construction | ||||||
| Switch body material | Phenolic | |||||
| Contact material | Copper, tin-plated | |||||
| Terminals | 30 A 60 A 100 A 200 A |
#10 - 32 screw and self-lifting pressure plate 1/4 in. - 28 screw-lug, copper 5/16 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper |
||||
| All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire. | ||||||
| Conductor Size (mm2) | 30 A 60 A 100 A 200 A |
#14…8 AWG #12…2 AWG #10…1/0 AWG #2…250 MCM AWG |
||||
| Recommended Torque | 30 A 60 A 100 A 200 A |
Conductor into Lug 36…40 lbin 35…45 lbin 35…50 lbin 275 lbin |
||||
| Mechanisms | Zinc-plated steel, bronze chromate finish | |||||
Bulletin 1494D, 1494V Circuit Breakers
| Electrical Ratings | ||||||||
| Frame Size | 125 A | 150 A | 250 A | 400 A | 600 A | 800 A | 1200 A | |
| Auxiliary Contacts | ||||||||
| 1494V, 1494D | ||||||||
| NEMA/EEMAC | B600, P300 | |||||||
| IEC Ratings | ACII Ux |
12…120V 220…240V 380…400V 500…600V |
Ie |
6 A 3 A 1.5 A 1.2 A |
||||
| Maximum Number of Auxiliary Contacts | 2 | |||||||
| Mechanical Data | ||||||||
| Mechanical Life (Typical) | 10 000 | |||||||
| Construction | ||||||||
| Mechanisms | Zinc-plated steel | |||||||
| Environmental Data | ||||||||
| Ambient Temperature★ | Operating | -20…+40 °C (-4…+104 °F) | ||||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||||
| Altitude (per IEC 947-5) | 2000 m per IEC 337-1 | |||||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F) | |||||||
| ★ Refer to circuit breaker specifications for other limitations. | ||||||||
Bulletin 1491 Fuse Blocks
| Electrical | ||||||
| UL Fuse Type | Class H | Class J | Class R | Class C | Class CC | |
| Maximum Fuse Cartridge Size | 30…600 A | 30…600 A | 30…600 A | 30…600 A | 30 A | |
| Maximum Voltage | AC | 600V | 600V | 600V | 600V | 600V |
| DC | 250V | 250V | 250V | 250V | 250V | |
| Thermal Current Rating | 30…600 A | 30…600 A | 30…600 A | 30…600 A | 30 A | |
| Maximum Short Circuit Prospective Fault Current | 10 kA | 200 kA | 200 kA | 100 kA | 200 kA | |
| Construction | ||||||
| Fuse Clips | Tin-plated copper | |||||
| Terminals | Tin-plated copper | |||||
| Fuse Block Base | Phenolic or porcelain | |||||
| Environmental | ||||||
| Ambient Temperature | Open | -20…+55 °C (-4…+131 °F) | ||||
| Enclosed | -20…+40 °C (-4…+104 °F) | |||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||
| Altitude (per IEC 947-5) | 2000 m | |||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F) | |||||
Approximate Dimensions
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494V
|
|
|
Disconnect Switches★
| NEMA Size [A] |
A | B | C | D | E | F | Switch Mounting Hole Diameter | |
| Max. | Min. | Max. | ||||||
| 30 | 6-19/64 (160) |
7-31/32 (202) |
8-1/2 (216) |
21-5/8 (549) |
2-3/4 (69.9) |
7-9/16 (192) |
3-7/8 (98.5) |
7/32 in. |
| 60 | 6-19/64 (160) |
8-15/32 (215) |
8-1/2 (216) |
21-5/8 (549) |
2-9/16 (65.1) |
7-9/16 (192) |
3-7/8 (98.5) |
7/32 in. |
| 100 | 6-19/64 (160) |
9-1/8 (231.8) |
8-1/2 (216) |
21-5/8 (549) |
3-37/64 (90.9) |
7-9/16 (192) |
3-7/8 (98.5) |
7/32 in. |
| 200 | 8-5/64 (205.2) |
15-9/64 (384.5) |
9-1/2 (241.3) |
21-5/8 (549) |
6-35/64 (166.3) |
8-25/32 (223) |
4-21/32 (118) |
19/64 in. |
| 400 | 11 (279.4) |
18-7/32 (462.7) |
10-1/2 (266.7) |
21-5/8 (549) |
8 (203.2) |
10 (254) |
5-1/2 (139.7) |
11/32 in. |
| 600 | 15-23/32 (399.2) |
17-19/32 (446.8)§ |
10-1/2 (266.7) |
21-5/8 (549) |
12 (304.8) |
11-27/32 (300.8) |
8-51/64 (223.3) |
11/32 in. |
| ★ Approximate dimensions are for reference only. | ||||||||
| This approximate dimension will vary by fuse class and size. | ||||||||
| § Approximate dimension with Class J fuses. | ||||||||
Circuit Breakers♣
| Frame | A | C | D | E | F | |
| Min. | Max. | |||||
| 125A 140U-H, 140M-H, EF, HMCPE 150A 140U-I, 140M-I EHD, FD, FDB, FDC, HFD, HMCP |
6 (152.4) |
6-3/4 (171.5) |
23 (584.2) |
6 (152.4) |
5-7/16 (138.1) |
5 (127) |
| 250A 140U-J, 140M-J 250A JD, JDB, JDC, HJD, HMCP |
11-1/4 (285.8) |
7-7/8 (200.0) |
22-9/16 (573.1) |
10 (254) |
5-23/32 (145.2) |
9-23/32 (246.8) |
| 400 A 140U-K, 140M-K KD, KDB, KDC, HKD, HMCP 600 A 140U-L |
11-3/8 (228.9) |
7-7/8 (200.0) |
22-9/16 (573.1) |
12 (304.8) |
7-1/8 (181.0) |
9-21/32 (245.3) |
| ♣ Approximate dimensions are for reference only. | ||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494C
|
Disconnect Switches
| NEMA Size [A] |
AA | BB | CC | DD | EE Mounting Plate Hole Diameter |
FF Minimum Bevel Diameter |
| 30 | 2-1/4 (57.2) |
5-1/4 (133.4) |
2-1/4 (57.2) |
— | 11/64 (4.37) |
12 (304.8) |
| 60 | 2-1/4 (57.2) |
5-1/4 (133.4) |
2-1/4 (57.2) |
— | 11/64 (4.37) |
12 (304.8) |
| 100 | 2-1/4 (57.2) |
5-1/4 (133.4) |
2-1/4 (57.2) |
— | 11/64 (4.37) |
12 (304.8) |
| 200 | 2 (50.8) |
8-1/4 (209.6) |
4-1/4 (108) |
1-1/8 (28.6) |
7/32 (5.56) |
16 (406.4) |
| 400 | 2 (50.8) |
11 (279.4) |
4-3/4 (120.7) |
1-3/8 (34.9) |
9/32 (7.14) |
16 (406.4) |
| 600 | 8-1/4 (209.6) |
15 (381) |
8-1/4 (209.6) |
— | — | 16 (406.4) |
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494F Disconnect Switches
Non-Fusible Disconnect Switch
|
Fusible Disconnect Switch
|
| Switch Size [A] | A | B | C | D | E | F | G | H | J | K | L | M | N | P | Q | R |
| 30 | 9-3/16 (233.4) |
4-5/16 (109.5) |
1-1/8 (28.6) |
6 (152.4) |
3/8 (9.5) |
1-9/16 (39.7) |
10-1/2 (266.7) |
8-1/2 (215.9) |
6-7/8 (174.6) |
8 (203.2) |
8-1/2 (215.9) |
15/16 (23.8) |
3-21/32 (92.9) |
7-5/16 (185.7) |
3 (76.2) |
5-7/16 (138.1) |
| 60 | 9-3/16 (233.4) |
4-5/16 (109.5) |
1-1/8 (28.6) |
6 (152.4) |
3/8 (9.5) |
1-9/16 (39.7) |
10-1/2 (266.7) |
8-1/2 (215.9) |
6-7/8 (174.6) |
8 (203.2) |
8-1/2 (215.9) |
15/16 (23.8) |
3-21/32 (92.9) |
7-5/16 (185.7) |
3 (76.2) |
5-7/16 (138.1) |
| 100 | 9-3/16 (233.4) |
4-5/16 (109.5) |
1-1/8 (28.6) |
6 (152.4) |
3/8 (9.5) |
1-9/16 (39.7) |
10-1/2 (266.7) |
9-3/4 (247.7) |
8-1/8 (206.4) |
8 (203.2) |
8-1/2 (215.9) |
15/16 (23.8) |
3-21/32 (92.9) |
7-5/16 (185.7) |
3 (76.2) |
5-7/16 (138.1) |
| 200 | 9-5/8 (244.5) |
4-3/4 (120.7) |
1-5/32 (29.4) |
8-3/16 (208) |
7/16 (11.1) |
2 (50.8) |
10-29/32 (277) |
9-3/4 (247.7) |
8-1/8 (206.4) |
8 (203.2) |
8-1/2 (215.9) |
1-5/16 (33.3) |
3-3/4 (95.3) |
7-1/2 (190.5) |
3 (76.2) |
5-7/16 (138.1) |
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494F Disconnect Switches Vault Hardware Latching (Non Pre-drilled Enclosures)
|
| Vault Hardware Kits★ | Switch Size [A] | A | B | C (Min.) |
D | E (Min.) |
F | G (Min.) |
H (Min.) |
J (Min.) |
K | L | M | N |
| Small and Intermediate Enclosures | ||||||||||||||
| 1494F-L1 1494F-L2 1494F-L3 |
30 | 3-7/8 (98.4) |
3/8 (9.5) |
3-1/16 (77.8) |
2-1/8 (54) |
4-1/2 (114.3) |
3-13/16 (96.8) |
13 (330.2) |
8-1/8 (206.4) |
5 (127) |
1/2 (12.7) |
1/4 (6.4) |
11/16 (17.5) |
1/2 (12.7) |
| 60 | 14 (355.6) |
|||||||||||||
| 100 | 18-7/8 (479.4) |
|||||||||||||
| 200 | 23-25/32 (604) |
|||||||||||||
| Large Enclosures | ||||||||||||||
| 1494F-L4 | 30 | 4 (101.6) |
1/2 (12.7) |
3-3/4 (95.3) |
2-1/8 (54) |
5 (127) |
3-13/16 (96.8) |
13-1/8 (333.4) |
9-13/16 (249.2) |
6 (152.4) |
5/8 (15.9) |
5/16 (7.9) |
1-1/4 (31.8) |
3/4 (19.1) |
| 60 | 13-5/8 (346.1) |
|||||||||||||
| 100 | 18-1/2 (469.9) |
|||||||||||||
| 200 | 23-13/32 (594.5) |
|||||||||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494D Circuit Breakers♣
|
|
| Cutler-Hammer Frame | A | C | D | E | F | |
| Min. | Max. | |||||
| 150 A — EHD, FD, FDB, FDC, HFD, HMCP | 7-13/16 (198.4) | 6-3/8 (161.9) | — | 6 (152.4) | 5-5/8 (142.9) | 6-7/16 (163.5) |
| 250 A — JD, JDB, JDC, HJD, HMCP | 11-1/2 (292.1) | 8-3/8 (212.7) | — | 8 (203.2) | 5-13/16 (147.6) | 9-7/16 (239.7) |
| 400 A — KD, KDB, KDC, HKD, HMCP | 11-1/2 (292.1) | 8-3/8 (212.7) | — | 12 (304.8) | 6-7/8 (174.6) | 9-7/16 (239.7) |
| 600 A — LD, HLD, LDC, LA, HLA, LC, HLC | 11-3/8 (288.9) | 9-1/2 (241.3) | — | 8 (203.2) | 12 (304.8) | 10-17/32 (267.5) |
| 800 A — MA, MDL, HMDL, HMA, MC, ND, HND, NDC | 16 (406.4) | 9-1/2 (241.3) | — | 10 (254) | 12-5/16 (312.7) | 15-3/32 (183.4) |
| 1200 A — NB TRI-PAK | 22 (558.8) | 9-1/2 (241.3) | — | 10 (254) | 12-5/16 (312.7) | 21-3/32 (535.8) |
| 1200 A — HNC, ND, HND, NDC, NB, HNB, NC, HNC | 16 (406.4) | 9-1/2 (241.3) | — | 12 (304.8) | 12-5/16 (312.7) | 25-3/32 (183.4) |
| ♣ Approximate dimensions are for reference only. | ||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches
Type 3R/4/12 (Enclosure Code "F") Painted Metal Enclosures
|
| Size [A] | Fuse Style★ |
Number of Poles |
Bulletin No. |
Approximate Dimensions in Inches (Millimeters) | Approx. Shipping Weight [lb (kg)] |
||||||||
| A Height |
B Width |
C Depth |
D Mounting |
E Mounting |
F Mounting |
G Handle Depth |
H | J | |||||
| 30 | A | 2 or 3 | 1494G | 13-5/16 (338) |
10-1/2 (267) |
8-1/4 (210) |
14-11/16 (373) |
| 5-1/4 (133) |
5-9/16 (141) |
15-21/32 (398) |
11/32 (9) |
20 (9.07) |
| 60 | |||||||||||||
| 30 | B | 2 or 3 | 1494G | 20 (509) |
10-1/2 (267) |
10-3/16 (259) |
21-7/16 (545) |
| 5-1/4 (133) |
5-9/16 (141) |
22-13/32 (569) |
11/32 (9) |
30 (13.6) |
| 60 | |||||||||||||
| 100 | A | ||||||||||||
| 30 | C | 6 | 1494G | 27-1/2 (698) |
10-1/2 (267) |
8-1/4 (210) |
28-7/8 (733) |
| 5-1/4 (133) |
5-9/16 (141) |
29-7/8 (759) |
13/16 (21) |
60 (27.21) |
| D | |||||||||||||
| 60 | C | ||||||||||||
| D | |||||||||||||
| 30 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 30 | A | 2 or 3 | 1494GX | 30 (762) |
20-1/2 (521) |
10-3/16 (259) |
31-3/8 (797) |
15-1/4 (387) |
15-1/4 (387) |
5-9/16 (141) |
32-3/8 (822) |
13/16 (21) |
90 (40.82) |
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 100 | D | 6 | 1494G | ||||||||||
| 100 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 100 | B | 2 or 3 | 1494G | 31-1/2 (800) |
10-1/2 (267) |
10-3/32 (257) |
32-7/8 (835) |
| 5-1/4 (133) |
5-9/16 (141) |
33-27/32 (860) |
11/32 (9) |
70 (31.73) |
| C | 6 | ||||||||||||
| 200 | A | 2 or 3 | |||||||||||
| B | |||||||||||||
| 100 | A | 2 or 3 | 1494GX | 50 (1270) |
22 (559) |
11-1/2 (292) |
51-3/8 (1305) |
15-1/4 (387) |
15-1/4 (387) |
5-9/16 (141) |
52-11/32 (1330) |
11/32 (9) |
200 (90.7) |
| B | |||||||||||||
| 200 | C | 6 | 1494G | ||||||||||
| D | |||||||||||||
| 200 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 400 | A | 2 or 3 | 1494G | 50 (1270) |
22 (559) |
11-1/2 (292) |
51-3/8 (1305) |
15-1/4 (387) |
15-1/4 (387) |
7-5/8 (194) |
52-11/32 (1330) |
11/32 (9) |
200 (90.7) |
| 600 | A | ||||||||||||
| 400 | B | 2 or 3 | 1494G | 56 (1422) |
30-1/2 (775) |
13-51/64 (350) |
57-5/8 (1464) |
20 (508) |
25-1/4 (641) |
7-5/8 (194) |
62-5/8 (1590) |
1 (25.4) |
300 (136.05) |
| 600 | B | ||||||||||||
| ★ A = Non-Fusible, Fusible 250V - Class H/R, Fusible 600V - Class J B = Fusible 600V - Class H/R C = Non-fusible D = Fusible 250V - Class H/R, Fusible 600V - Class J |
|||||||||||||
| These enclosures have one top mounting hole located on the center line. All other enclosures have two top mounting holes located as shown. | |||||||||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches
Type 4/4X (Enclosure Code "C") Stainless Steel Enclosure
|
| Size [A] | Fuse Style★ |
Number of Poles |
Bulletin No. |
Approximate Dimensions in Inches (Millimeters) | Approx. Shipping Weight [lb (kg)] |
||||||||
| A Height |
B Width |
C Depth |
D Mounting |
E Mounting |
F Mounting |
G Handle Depth |
H | J | |||||
| 30 | A | 2 or 3 | 1494G | 13-5/16 (338) |
10-1/2 (267) |
8-9/16 (217) |
14-11/16 (373) |
| 5-1/4 (133) |
5-9/16 (141) |
15-21/32 (398) |
13/16 (21) |
20 (9.07) |
| 60 | |||||||||||||
| 30 | B | 2 or 3 | 1494G | 27-1/2 (698) |
10-1/2 (267) |
8-1/4 (210) |
28-7/8 (733) |
| 7 (178) |
5-9/16 (141) |
29-3/4 (756) |
13/16 (21) |
60 (27.21) |
| C | 6 | ||||||||||||
| D | |||||||||||||
| 60 | B | 2 or 3 | |||||||||||
| C | 6 | ||||||||||||
| D | |||||||||||||
| 30 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 30 | A | 2 or 3 | 1494GX | 30 (762) |
20-1/2 (521) |
9-7/8 (251) |
31-3/8 (797) |
17 (432) |
17 (432) |
5-9/16 (141) |
32-1/4 (819) |
13/16 (21) |
90 (40.82) |
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 100 | A | 2 or 3 | 1494G | ||||||||||
| B | |||||||||||||
| C | 6 | ||||||||||||
| D | |||||||||||||
| 100 | A | 2 or 3 | 1494GX | 50 (1270) |
22 (559) |
11-3/16 (284) |
51-3/8 (1305) |
18-1/2 (470) |
18-1/2 (470) |
5-9/16 (141) |
52-1/4 (1327) |
13/16 (21) |
200 (90.7) |
| B | |||||||||||||
| 200 | A | 2 or 3 | 1494G | ||||||||||
| B | |||||||||||||
| C | 6 | ||||||||||||
| D | |||||||||||||
| 400 | A | 2 or 3 | 1494G | 56 (1422) |
30-1/2 (775) |
13-51/64 (350) |
57-5/8 (1464) |
20 (508) |
25-1/4 (641) |
7-5/8 (194) |
58-5/8 (1489) |
1 (25.4) |
300 (136.05) |
| B | |||||||||||||
| 600 | A | ||||||||||||
| B | |||||||||||||
| ★ A = Non-Fusible, Fusible 250V - Class H/R, Fusible 600V - Class J B = Fusible 600V - Class H/R C = Non-fusible D = Fusible 250V - Class H/R, Fusible 600V - Class J |
|||||||||||||
| These enclosures have one top mounting hole located on the center line. All other enclosures have two top mounting holes located as shown. | |||||||||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494H Heavy Duty Safety Switches
Type 1 (Enclosure Code "A") General Purpose Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
Knockout Fig. # |
| 30 | 240V | 10-9/32 (261.1) | 6-3/8 (162.1) | 3-5/16 (84.1) | 7-1/8 (181) | 1 |
| 600V | 12-19/32 (319.8) | 8-3/8 (212.9) | 4 (101.6) | 9-1/2 (241.3) | 2 | |
| Non-fusible | 10-3/8 (263.7) | 8-3/8 (212.9) | 4 (101.6) | 9-1/4 (235) | 3 | |
| 60 | 240V | 17-19/32 (446.8) | 9-3/8 (238.3) | 5 (127) | 10-3/64 (255.3) | 4 |
| 600V | 21-11/32 (542) | 5 | ||||
| Non-fusible | 17-19/32 (446.8) | 4 | ||||
| 100 | 240V | 21-11/32 (542) | 9-3/8 (238.3) | 5 (127) | 10-3/64 (255.3) | 5 |
| 600V | 22-11/32 (567.4) | 4 | ||||
| Non-fusible | 17-19/32 (446.8) | 4 | ||||
| 200 | 240V | 31-5/8 (803.3) | 13-7/16 (341.4) | 5-1/4 (133.4) | 14-7/16 (366) | 6 |
| 600V | ||||||
| Non-fusible | ||||||
Knockouts — Conduit Size
|
|
|
||
| Fig. 1 | Fig. 2 | Fig. 3 | ||
|
|
|
||
| Fig. 4 | Fig. 5 | Fig. 6 | ||
| Switch Size [A] | Fuse Style | Knockouts | ||||
| A | B | C | D | E | ||
| 30 | 240V | 9/32 (7.1) | 1/2 x 3/4 (12.7 x 19.1) |
3/8 x 1/2 x 3/4 x 1 (9.5 x 12.7 x 19.1 x 25.4) |
— | — |
| 600V | 1/2 x 3/4 x 1 (12.7 x 19.1 x 25.4) |
1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
|||
| Non-fusible | ||||||
| 60 | 240V | 9/32 (7.1) | 1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
1 x 1-1/4 x 1-1/2 x 2 (25.4 x 31.8 x 38.1 x 50.8) |
— |
| 600V | ||||||
| Non-fusible | ||||||
| 100 | 240V | 9/32 (7.1) | 1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
1 x 1-1/4 x 1-1/2 x 2 (25.4 x 31.8 x 38.1 x 50.8) |
— |
| 600V | ||||||
| Non-fusible | ||||||
| 200 | 240V | 1 x 1-1/2 x 2 x 2-1/2 (25.4 x 38.1 x 50.8 x 63.5) |
9/32 (7.1) | 1/2 (12.7) |
— | — |
| 600V | ||||||
| Non-fusible | ||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494H Heavy Duty Safety Switches
Type 3R (Enclosure Code "N") Rain-Proof Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
Knockout Fig. # |
| 30 | 240V | 10-5/8 (269.9) | 6-3/8 (162.1) | 3-5/16 (84.1) | 7-1/8 (181) | 7 |
| 600V | 13-13/64 (335.3) | 8-3/8 (212.9) | 4 (101.6) | 9-13/32 (239) | 8 | |
| Non-fusible | 13-13/64 (335.3) | 8-3/8 (212.9) | 4 (101.6) | 9-13/32 (239) | 8 | |
| 60 | 240V | 17-7/16 (443) | 9-3/8 (238.3) | 5 (127) | 10-3/64 (255.3) | 9 |
| 600V | 22-3/16 (563.6) | 10-1/2 (267) | ||||
| Non-fusible | 17-7/16 (443) | 10-3/64 (255.3) | ||||
| 100 | 240V | 22-3/16 (563.6) | 9-3/8 (238.3) | 5 (127) | 10-1/2 (267) | 9 |
| 600V | 22-3/16 (563.6) | |||||
| Non-fusible | 17-7/16 (443) | 10-3/64 (255.3) | ||||
| 200 | 240V | 31-7/16 (798.6) | 13-3/8 (339.9) | 5-15/32 (138.9) | 14-1/8 (361.9) | 10 |
| 600V | ||||||
| Non-fusible | ||||||
Knockouts — Conduit Size
|
|
|
|
|||
| Fig. 7 | Fig. 8 | Fig. 9 | Fig. 10 |
| Switch Size [A] | Fuse Style | Knockouts | |||
| A | B | C | D | ||
| 30 | 240V | 9/32 (7.1) | 1/2 x 3/4 (12.7 x 19.1) |
3/8 x 1/2 x 3/4 x 1 (9.5 x 12.7 x 19.1 x 25.4) |
— |
| 600V | 1/2 x 3/4 x 1 (12.7 x 19.1 x 25.4) |
1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
||
| Non-fusible | |||||
| 60 | 240V | 9/32 (7.1) | 1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
1 x 1-1/4 x 1-1/2 x 2 (25.4 x 31.8 x 38.1 x 50.8) |
| 600V | |||||
| Non-fusible | |||||
| 100 | 240V | 9/32 (7.1) | 1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
1 x 1-1/4 x 1-1/2 x 2 (25.4 x 31.8 x 38.1 x 50.8) |
| 600V | |||||
| Non-fusible | |||||
| 200 | 240V | 1 x 1-1/2 x 2 x 2-1/2 (25.4 x 38.1 x 50.8 x 63.5) |
9/32 (7.1) | 1/2 (12.7) |
— |
| 600V | — | ||||
| Non-fusible | — | ||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494H Heavy Duty Safety Switches
Type 12 (Enclosure Code "F") Dust-Tight Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
| 30 | 240V | 11-3/8 (288.9) | 7-3/8 (187.3) | 5-1/16 (128.6) | 8-1/8 (206.4) |
| 600V | 13-3/8 (339.7) | 9-3/8 (238.1) | 5-5/16 (134.9) | 10-1/4 (260.4) | |
| Non-fusible | 5-1/16 (128.6) | ||||
| 60 | 240V | 19-3/8 (492.1) | 9-3/8 (238.1) | 5-1/16 (128.6) | 10-1/4 (260.4) |
| 600V | 5-5/16 (134.9) | ||||
| Non-fusible | 5-1/16 (128.6) | ||||
| 100 | 240V | 25-3/8 (644.5) | 13-1/2 (342.9) | 5-1/16 (128.6) | 14-1/4 (362) |
| 600V | 5-5/16 (134.9) | ||||
| Non-fusible | |||||
| 200 | 240V | 35-1/8 (892.2) | 13-1/2 (342.9) | 5-5/16 (134.9) | 15-1/4 (387.4) |
| 600V | 14-1/2 (368.3) | ||||
| Non-fusible | |||||
Bulletin 1494HL General Duty Safety Switches
Type 1 (Enclosure Code "A") General Purpose Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
Knockout Fig. # |
| 30 | 240V | 10-9/32 (261.1) | 6-1/2 (165.1) | 3-5/16 (84.1) | 6-29/32 (175.3) | 1 |
| 60 | 13-27/32 (351.5) | 8-1/2 (215.9) | 4 (101.6) | 8-7/8 (225.6) | 2 | |
| 100 | 21-11/32 (542) | 9-1/2 (241.3) | 5 (127) | 9-7/8 (251) | 3 | |
| 200 | 29-1/8 (739.6) | 13-7/16 (341.4) | 5-5/16 (134.9) | 13-15/16 (354.1) | 4 | |
Knockouts — Conduit Size
|
|
|
|
|||
| Fig. 1 | Fig. 2 | Fig. 3 | Fig. 4 |
| Switch Size [A] | Knockouts | ||||
| A | B | C | D | E | |
| 30 | 9/32 (7.1) | 1/2 x 3/4 (12.7 x 19.1) |
3/8 x 1/2 x 3/4 x 1 (9.5 x 12.7 x 19.1 x 25.4) |
— | — |
| 60 | 9/32 (7.1) | 1/2 x 3/4 (12.7 x 19.1) |
1/2 x 3/4 x 1 (12.7 x 19.1 x 25.4) |
1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
| 100 | 9/32 (7.1) | 1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |
1 x 1-1/4 x 1-1/2 x 2 (25.4 x 31.8 x 38.1 x 50.8) |
— |
| 200 | 1/2 (12.7) | 1 x 1-1/2 x 2 x 2-1/2 (25.4 x 38.1 x 50.8 x 63.5) |
9/32 (7.1) | — | — |
Type 3R (Enclosure Code "N") Rain-Proof Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
Knockout Fig. # |
| 30 | 240V | 10-1/32 (254.8) | 6-3/8 (162.1) | 3-5/16 (84.1) | 7-1/8 (180.8) | 5 |
| 60 | 13-15/16 (353.8) | 8-3/8 (212.9) | 3-7/8 (225.6) | 9-3/32 (230.9) | 6 | |
| 100 | 21-7/16 (544.3) | 9-3/8 (238.3) | 5 (127) | 9-61/64 (252.7) | 7 | |
| 200 | 28-15/16 (735.1) | 13-3/8 (339.9) | 5-5/16 (134.9) | 14-1/16 (357.1) | 8 | |
Knockouts — Conduit Size
|
|
|
|
|||
| Fig. 5 | Fig. 6 | Fig. 7 | Fig. 8 |
| Switch Size [A] | Knockouts | |||
| A | B | C | D | |
| 30 | 9/32 (7.1) | 1/2 x 3/4 (12.7 x 19.1) |
3/8 x 1/2 x 3/4 x 1 (9.5 x 12.7 x 19.1 x 25.4) |
— |
| 60 | 9/32 (7.1) | 1/2 x 3/4 x 1 (12.7 x 19.1 x 25.4) |
1/2 x 3/4 x 1 x 1-1/4 (12.7 x 19.1 x 25.4 x 31.8) |
3/4 x 1 x 1-1/4 x 1-1/2 (19.1 x 25.4 x 31.8 x 38.1) |