Bulletin 1494V Variable Depth Flange-Mounted Remote or Dual Type Operating Mechanisms
|
|
|
| Remote Drive Operating Mechanism |
Main Drive Dual Operating Mechanism (Includes Operating Handle) |
Bulletin 1494V — Variable-Depth Flange-Mounted
Operating Mechanisms
Operating mechanism for remote or dual operation of disconnect switches or circuit breakers.
- Remote: 30…600 A disconnect switches
- Fusible or non-fusible
- Remote: 150…400 A frame circuit breakers
- Dual: 30…100 A disconnect switches
- Dual: 150 A frame circuit breaker
- Can be used with enclosure Types 1, 3R, 4, 12
- Lockable handle
Description
Remote Operating Mechansims — Allows the handle to be mounted above or below the disconnect switch or circuit breaker.
Dual Operating Mechanisms — Permits the control of (2) disconnect switches or circuit breakers utilizing a common handle.
Operation — Both the remote and dual operating mechanisms consist of (2) components: a main drive mechanism (which includes the handle) and a remote drive mechanism. To obtain a functional device, these components must be properly combined with a connecting link (supplied by the customer), disconnecting means and connecting rod.
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA C22.2, No. 14
Certifications
UL Recognized (File No. E3125, Guide No. NLDX2)
CSA Certified (File No. LR1234)
Product Selection
Remote or Dual Operated Mechanisms — Separate Components
| Type of Mechanism |
Enclosure Type |
Size [A] | Frame Designation | Brand | Mounting | Cat. No.¬ | |
| Disconnect Switch | Circuit Breaker | ||||||
| Remote | Type 1, 3R, 12 | 30, 60, 100, 200 | — | — | — | Right | 1494V-H5 |
| Left | 1494V-HL5 | ||||||
| 400, 600 | — | — | — | Right | 1494V-H8 | ||
| Left | 1494V-HL8 | ||||||
| — | 150, 250, 400 | EHD, FD, FDB, FDC, HFD, HMCP, JD, JDB, JDC, HJD, KD, KDB, KDC, HKD | Cutler-Hammer | Right | 1494V-H10 | ||
| Left | 1494V-HL10 | ||||||
| Type 4 | 30, 60, 100, 200 | — | — | — | Right | 1494V-W5 | |
| Left | 1494V-WL5 | ||||||
| 400, 600 | — | — | — | Right | 1494V-W8 | ||
| Left | 1494V-WL8 | ||||||
| — | 150, 250, 400 | EHD, FD, FDB, FDC, HFD, HMCP, JD, JDB, JDC, HJD, KD, KDB, KDC, HKD | Cutler-Hammer | Right | 1494V-W10 | ||
| Left | 1494V-WL10 | ||||||
| Dual | Type 1, 3R, 12 | (2) 30 A, (2) 60 A, (2) 100 A, or any combination of (2) 30…100 A Switches | — | — | — | Right | 1494V-H50 |
| Left | 1494V-HL50 | ||||||
| — | Two 150 A | EHD, FD, FDB, FDC, HFD, HMCP | Cutler-Hammer | Right | 1494V-H95 | ||
| Left | 1494V-HL95 | ||||||
| Type 4 | (2) 30 A, (2) 60 A, (2) 100 A, or any combination of (2) 30…100 A Switches | — | — | — | Right | 1494V-W50 | |
| Left | 1494V-WL50 | ||||||
| — | Two 150 A | EHD, FD, FDB, FDC, HFD, HMCP | Cutler-Hammer | Right | 1494V-W95 | ||
| Left | 1494V-WL95 | ||||||
| ¬ Includes main and remote drive mechanisms. Does not include rectangular bar stock 1/4 x 5/8 in. (6.35 x 15.8 mm) connecting bar between disconnecting means and connecting rod, to be supplied by user. | |||||||
Accessories
Specifications
Bulletin 1494C, 1494F, 1494G, 1494M, 1494R, 1494V Disconnect Switches
| Disconnect Switch Electrical Ratings | ||||||||
| Switch Size | 30 A | 60 A | 100 A | 200 A | 400 A | 600 A | ||
| Rated insulation voltage Ui (UL) IEC | (600) 660V | |||||||
| Ratings UL/CSA/NEMA |
HP | 230V/60 Hz 460V/60 Hz 575V/60 Hz |
7.5 15 20 |
15 30 50 |
30 60 75 |
60 125 150 |
125 250 350 |
200 400 500 |
| 250V DC | 5 | 10 | 20 | 40 | 50 | 50 | ||
| Continuous Current |
600V AC 250V DC |
30 | 60 | 100 | 200 | 400 | 600 | |
| Auxiliary Contact Electical Ratings | ||||||||
| NEMA/EEMAC | B600, P300 | |||||||
| IEC Ratings | Ui 660V | Ith 10 A | ||||||
ACII Ux |
12…120V 220…240V 380…400V 500…600V |
Ie |
6 A 3 A 1.5 A 1.2 A |
|||||
| Mechanical | ||||||||
| Degree of protection | Operating handles | Molded Type 1, 3R, 4, 4X, 12, Painted Type 1, 3R, 4, 12 Stainless Steel Type 4, 4X |
||||||
| Mechanical life (Typical) | 20 000 operations (30…200 A) 10 000 operations (400…600 A) | |||||||
| Switching frequency (operations/hr) | 30, 60, 100, and 200 A sizes — 300 maximum400 and 600 A size — 240 Maximum | |||||||
| Environmental | ||||||||
| Temperature | Operating | -35…+40 °C (-31…+104 °F) | ||||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||||
| Altitude (per IEC 947-5) | 2000m per IEC 337-1 | |||||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C and 50% at 40 °C | |||||||
| Design Specification/Test Requirements | ||||||||
| Dielectric strength | 2200V for 1 minute | |||||||
| Electrical life | 6000 operations at rated current | |||||||
| Short Circuit Withstand Capability | 10 000 A: unfused 10 000 A: with Class H fuses 200 000 A: with Class J or Class R fuses | |||||||
| Construction | ||||||||
| Switch body material | Phenolic | |||||||
| Contact material | Copper, tin-plated | |||||||
| Terminals | 30 A 60 A 100 A 200 A 400 A 600 A |
#10 - 32 screw and self-lifting pressure plate 1/4 in. - 28 screw-lug, copper 5/16 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper 1/2 in. - 13 screw-lug, copper |
||||||
| All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire. | ||||||||
| Conductor Size (mm2) | 30 A 60 A 100 A 200 A 400 A 600 A |
#14…8 AWG (1.5…10 mm2) #14…4 AWG (2.5…16 mm2) #8…1/0 AWG (10…50 mm2) #6…4/0 AWG (16…95 mm2) 2 of #1/0 AWG…250 MCM (2 per lug) 2 of 185 mm2…250 MCM 2 of #1/0 AWG…350 MCM (2 per lug) 2 of 185 mm2…350 MCM |
||||||
| Recommended Torque | 30 A 60 A 100 A 200 A 400 A 600 A |
Conductor into Lug 20 lbin 45 lbin 150 lbin 275 lbin 325 lbin 325 lbin |
Lug to Terminal 20 lbin 50 lbin 90 lbin 175 lbin 275 lbin 275 lbin |
|||||
| Mechanisms | Zinc-plated steel, RoHS Compliant finish | |||||||
Bulletin 1494H Disconnect Switches
| Disconnect Switch Electrical Ratings | ||||||
| Switch Size | 30 A | 60 A | 100 A | 200 A | ||
| Rated insulation voltage Ui (UL) IEC | (600) 660V | |||||
| Ratings UL/CSA/NEMA |
Hp | 230V/60 Hz 460V/60 Hz 575V/60 Hz |
10 20 30 |
20 50 60 |
40 75 100 |
60 125 150 |
| 250V DC | 5 | 10 | 20 | 40 | ||
| Continuous Current |
600V AC 250V DC |
30 | 60 | 100 | 200 | |
| Auxiliary Contact Electical Ratings | ||||||
| Continuous Current | 10 A | 15 A | ||||
| Pole Configuration | DPDT | DPDT | ||||
| Mechanical | ||||||
| Degree of protection | Operating handles | Painted Type 1, 3R, 12 | ||||
| Mechanical life (Typical) | 10 000 operations | |||||
| Switching frequency (operations/hr) | 300 maximum | |||||
| Environmental | ||||||
| Temperature | Operating | -35…+40 °C (-31…+104 °F) | ||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||
| Altitude (per IEC 947-5) | 2000m per IEC 337-1 | |||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C and 50% at 40 °C | |||||
| Design Specification/Test Requirements | ||||||
| Dielectric strength | 2200V for 1 minute | |||||
| Electrical life | 6000 operations at rated current | |||||
| Short Circuit Withstand Capability | 10 000 A: unfused 10 000 A: with Class H fuses 200 000 A: with Class J or Class R fuses (30…100 A) 100 000 A: with Class J or Class R fuses (200 A) |
|||||
| Construction | ||||||
| Switch body material | Phenolic | |||||
| Contact material | Copper, tin-plated | |||||
| Terminals | 30 A 60 A 100 A 200 A |
#10 - 32 screw and self-lifting pressure plate 1/4 in. - 28 screw-lug, copper 5/16 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper |
||||
| All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire. | ||||||
| Conductor Size (mm2) | 30 A 60 A 100 A 200 A |
#14…8 AWG #12…2 AWG #10…1/0 AWG #2…250 MCM AWG |
||||
| Recommended Torque | 30 A 60 A 100 A 200 A |
Conductor into Lug 36…40 lbin 35…45 lbin 35…50 lbin 275 lbin |
||||
| Mechanisms | Zinc-plated steel, Bronze chromate finish | |||||
Bulletin 1494D, 1494V Circuit Breakers
| Electrical Ratings | ||||||||
| Frame Size | 125 A | 150 A | 250 A | 400 A | 600 A | 800 A | 1200 A | |
| Auxiliary Contacts | ||||||||
| 1494V, 1494D | ||||||||
| NEMA/EEMAC | B600, P300 | |||||||
| IEC Ratings | ACII Ux |
12…120V 220…240V 380…400V 500…600V |
Ie |
6 A 3 A 1.5 A 1.2 A |
||||
| Maximum Number of Auxiliary Contacts | 2 | |||||||
| Mechanical Data | ||||||||
| Mechanical Life (Typical) | 10 000 | |||||||
| Construction | ||||||||
| Mechanisms | Zinc-plated steel | |||||||
| Environmental Data | ||||||||
| Ambient Temperature¬ | Operating | 20…+40 °C (4…+104 °F) | ||||||
| Storage | 40…+65 °C (40…+149 °F) | |||||||
| Altitude (per IEC 947-5) | 2000 m per IEC 337-1 | |||||||
| Relative Humidity (per IEC 947-3) | 90% @ 20 °C (68 °F), 50% @ 40 °C (104 °F) | |||||||
| ¬ Refer to circuit breaker specifications for other limitations. | ||||||||
Bulletin 1491 Fuse Blocks
| Electrical | ||||||
| UL Fuse Type | Class H | Class J | Class R | Class C | Class CC | |
| CSA Fuse Type | HRCI-H | HRCI-J | HRCI-R | HRCI-C | HRCI-MISC | |
| Maximum Fuse Cartridge Size | 30…600 A | 30…600 A | 30…600 A | 30…600 A | 30 A | |
| Maximum Voltage | AC | 600V | 600V | 600V | 600V | 600V |
| DC | 250V | 250V | 250V | 250V | 250V | |
| Thermal Current Rating | 30…600 A | 30…600 A | 30…600 A | 30…600 A | 30 A | |
| Maximum Short Circuit Prospective Fault Current | 10 kA | 200 kA | 200 kA | 100 kA | 200 kA | |
| Construction | ||||||
| Fuse Clips | Tin-plated copper | |||||
| Terminals | Tin-plated copper | |||||
| Fuse Block Base | Phenolic or Porcelain | |||||
| Environmental | ||||||
| Ambient Temperature | Open | 20…+55 °C (4…+131 °F) | ||||
| Enclosed | 20…+40 °C (4…+104 °F) | |||||
| Storage | 40…+65 °C (40…+149 °F) | |||||
| Altitude (per IEC 947-5) | 2000 m | |||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F) | |||||
Approximate Dimensions
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494C, 1494V
|
|
|
Disconnect Switches¬
| NEMA Size [A] |
A | BT | C | D | E | F | |
| Max. | Min. | Max. | |||||
| 30 | 6-19/64 (160) |
7-31/32 (202) |
6-3/4 (171) |
21-5/8 (549) |
2-3/4 (69.9) |
7-9/16 (192) |
3-7/8 (98.5) |
| 60 | 6-19/64 (160) |
8-15/32 (215) |
6-3/4 (171) |
21-5/8 (549) |
2-9/16 (65.1) |
7-9/16 (192) |
3-7/8 (98.5) |
| 100 | 6-19/64 (160) |
9-1/8 (231.8) |
6-3/4 (171) |
21-5/8 (549) |
3-37/64 (90.9) |
7-9/16 (192) |
3-7/8 (98.5) |
| 200 | 8-5/64 (205.2) |
15-9/64 (384.5) |
7-3/4 (197) |
21-5/8 (549) |
6-35/64 (166.3) |
8-25/32 (223) |
4-21/32 (118) |
| 400 | 11 (279.4) |
11-5/8 (295.3) |
9 (229) |
21-5/8 (549) |
8 (203.2) |
10 (254) |
5-1/2 (139.7) |
| 600 | 15-23/32 (399.2) |
17-19/32 (446.8) |
9 (229) |
21-5/8 (549) |
12 (304.8) |
11-27/32 (300.8) |
8-51/64 (223.3) |
| ¬ Approximate dimensions are for reference only. | |||||||
| T This approximate dimension will vary by fuse class and size. | |||||||
| Approximate dimension with Class J fuses. | |||||||
Circuit Breakers§
| Frame | A | C | D | E | F | |
| Min. | Max. | |||||
| 125A 140U-H, 140M-H, EF, HMCPE 150A EHD, FD, FDB, FDC, HFD, HMCP |
6 (152.4) |
6-3/4 (171.5) |
23 (584.2) |
6 (152.4) |
5-7/16 (138.1) |
5 (127) |
| 250A 140U-J, 140M-J, EF 250A JD, JDB, JDC, HJD, HMCP |
11-1/4 (285.8) |
7-7/8 (200.0) |
22-9/16 (573.1) |
10 (254) |
5-23/32 (145.2) |
9-23/32 (246.8) |
| 400 A KD, KDB, KDC, HKD, HMCP |
11-3/8 (228.9) |
7-7/8 (200.0) |
22-9/16 (573.1) |
12 (304.8) |
7-1/8 (181.0) |
9-21/32 (245.3) |
| § Approximate dimensions are for reference only. | ||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494F, 1494M Disconnect Switches¬
|
|
| NEMA Size [A] | A | BT | C | D | E | F | G | H | J | K | L | P | S | |
| Min. | Max. | |||||||||||||
| Without Door Hardware | ||||||||||||||
| 30 | 5-15/16 (150.8) |
10-3/4 (273.1) |
6-3/8 (161.9) |
— | 2-3/16 (55.6) |
7-1/2 (190.5) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-1/8 (54) |
2-1/16 (52.4) |
| 60 | 5-15/16 (150.8) |
13-3/16 (335) |
6-3/8 (161.9) |
— | 2 (50.8) |
7-1/2 (190.5) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-1/8 (54) |
3-1/4 (82.6) |
| 100 | 7-15/16 (200.4) |
16-3/4 (425.5) |
8-1/2 (215.9) |
— | 5 (127) |
8-1/4 (209.6) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-1/8 (54) |
8-9/64 (206.8) |
| 200 | 10-1/2 (266.7) |
20-13/16 (528.6) |
9 (228.6) |
— | 7 (177.8) |
11-3/8 (289) |
5-9/16 (141.3) |
1-1/4 (31.8) |
11-1/8 (282.6) |
1-11/16 (42.9) |
13/16 (20.6) |
9-1/2 (241.3) |
2-9/32 (57.9) |
10-13/32 (264.3) |
| Small and Intermediate Enclosures with Door Hardware | ||||||||||||||
| 30 | 5-15/16 (150.8) |
10-3/4 (273.1) |
6-3/8 (161.9) |
— | 2-3/16 (55.6) |
7-1/2 (190.5) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-5/32 (54.8) |
2-1/4 (57.2) |
| 60 | 5-15/16 (150.8) |
13-3/16 (335) |
6-3/8 (161.9) |
— | 2 (50.8) |
7-1/2 (190.5) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-5/32 (54.8) |
3-1/4 (82.6) |
| 100 | 7-15/16 (200.4) |
16-3/4 (425.5) |
8-1/2 (215.9) |
— | 5 (127) |
8-1/4 (209.6) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-5/32 (54.8) |
8-9/64 (206.8) |
| 200 | 10-1/2 (266.7) |
20-13/16 (528.6) |
9 (228.6) |
— | 7 (177.8) |
11-3/8 (289) |
5-9/16 (141.3) |
1-1/4 (31.8) |
11-1/8 (282.6) |
1-11/16 (42.9) |
13/16 (20.6) |
9-1/2 (241.3) |
2-5/16 (58.7) |
10-13/32 (264.3) |
| Large Enclosures with Door Hardware | ||||||||||||||
| 30 | 5-15/16 (150.8) |
10-3/4 (273.1) |
6-3/8 (161.9) |
— | 2-3/16 (55.6) |
7-1/2 (190.5) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-1/4 (57.2) |
2-3/4 (69.9) |
| 60 | 5-15/16 (150.8) |
13-3/16 (335) |
6-3/8 (161.9) |
— | 2 (50.8) |
7-1/2 (190.5) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-1/4 (57.2) |
3-1/4 (82.6) |
| 100 | 7-15/16 (200.4) |
16-3/4 (425.5) |
8-1/2 (215.9) |
— | 5 (127) |
8-1/4 (209.6) |
3-3/4 (95.3) |
1-3/16 (30.2) |
8-1/2 (215.9) |
1-7/16 (36.5) |
15/32 (11.9) |
7-3/16 (182.6) |
2-1/4 (57.2) |
8-9/64 (206.8) |
| 200 | 10-1/2 (266.7) |
20-13/16 (528.6) |
9 (228.6) |
— | 7 (177.8) |
11-3/8 (289) |
5-9/16 (141.3) |
1-1/4 (31.8) |
11-1/8 (282.6) |
1-11/16 (42.9) |
13/16 (20.6) |
9-1/2 (241.3) |
2-11/32 (59.5) |
10-13/32 (264.3) |
| ¬ Approximate dimensions are for reference only. | ||||||||||||||
| T This approximate dimension will vary by fuse class and size. | ||||||||||||||
| Minimum wiring space for the maximum wire size. | ||||||||||||||
Bulletin 1494D Circuit Breakers§
| Cutler-Hammer Frame | A | C | D | E | F | |
| Min. | Max. | |||||
| 150 A — EHD, FD, FDB, FDC, HFD, HMCP | 7-13/16 (198.4) | 6-3/8 (161.9) | — | 6 (152.4) | 5-5/8 (142.9) | 6-7/16 (163.5) |
| 250 A — JD, JDB, JDC, HJD, HMCP | 11-1/2 (292.1) | 8-3/8 (212.7) | — | 8 (203.2) | 5-13/16 (147.6) | 9-7/16 (239.7) |
| 400 A — KD, KDB, KDC, HKD, HMCP | 11-1/2 (292.1) | 8-3/8 (212.7) | — | 12 (304.8) | 6-7/8 (174.6) | 9-7/16 (239.7) |
| 600 A — LD, HLD, LDC, LA, HLA, LC, HLC | 11-3/8 (288.9) | 9-1/2 (241.3) | — | 8 (203.2) | 12 (304.8) | 10-17/32 (267.5) |
| 800 A — MA, MDL, HMDL, HMA, MC, ND, HND, NDC | 16 (406.4) | 9-1/2 (241.3) | — | 10 (254) | 12-5/16 (312.7) | 15-3/32 (183.4) |
| 1200 A — NB TRI-PAK | 22 (558.8) | 9-1/2 (241.3) | — | 10 (254) | 12-5/16 (312.7) | 21-3/32 (535.8) |
| 1200 A — HNC, ND, HND, NDC, NB, HNB, NC, HNC | 16 (406.4) | 9-1/2 (241.3) | — | 12 (304.8) | 12-5/16 (312.7) | 25-3/32 (183.4) |
| § Approximate dimensions are for reference only. | ||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches
Type 3R/4/12 (Enclosure Code "F") Painted Metal Enclosures
|
| Size [A] | Fuse Style¬ |
Number of Poles |
Bulletin No. |
Approximate Dimensions in Inches (Millimeters) | Approx. Shipping Weight in lbs (kg) |
||||||||
| A Height |
B Width |
C Depth |
D Mounting |
E Mounting |
F Mounting |
G Handle Depth |
H | J | |||||
| 30 | A | 2 or 3 | 1494G | 13 5/16 (338) |
10 1/2 (267) |
8 1/4 (210) |
14 11/16 (373) |
T | 5 1/4 (133) |
5 9/16 (141) |
15 21/32 (398) |
11/32 (9) |
20 (9.07) |
| 60 | |||||||||||||
| 30 | B | 2 or 3 | 1494G | 20 (509) |
10 1/2 (267) |
10 3/16 (259) |
21 7/16 (545) |
T | 5 1/4 (133) |
5 9/16 (141) |
22 13/32 (569) |
11/32 (9) |
30 (13.6) |
| 60 | |||||||||||||
| 100 | A | ||||||||||||
| 30 | C | 6 | 1494G | 27 1/2 (698) |
10 1/2 (267) |
8 1/4 (210) |
28 7/8 (733) |
T | 5 1/4 (133) |
5 9/16 (141) |
29 7/8 (759) |
13/16 (21) |
60 (27.21) |
| D | |||||||||||||
| 60 | C | ||||||||||||
| D | |||||||||||||
| 30 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 30 | A | 2 or 3 | 1494GX | 30 (762) |
20 1/2 (521) |
10 3/16 (259) |
31 3/8 (797) |
15 1/4 (387) |
15 1/4 (387) |
5 9/16 (141) |
32 3/8 (822) |
13/16 (21) |
90 (40.82) |
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 100 | D | 6 | 1494G | ||||||||||
| 100 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 100 | B | 2 or 3 | 1494G | 31 1/2 (800) |
10 1/2 (267) |
10 3/32 (257) |
32 7/8 (835) |
T | 5 1/4 (133) |
5 9/16 (141) |
33 27/32 (860) |
11/32 (9) |
70 (31.73) |
| C | 6 | ||||||||||||
| 200 | A | 2 or 3 | |||||||||||
| B | |||||||||||||
| 100 | A | 2 or 3 | 1494GX | 50 (1270) |
22 (559) |
11 1/2 (292) |
51 3/8 (1305) |
15 1/4 (387) |
15 1/4 (387) |
5 9/16 (141) |
52 11/32 (1330) |
11/32 (9) |
200 (90.7) |
| B | |||||||||||||
| 200 | C | 6 | 1494G | ||||||||||
| D | |||||||||||||
| 200 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 400 | A | 2 or 3 | 1494G | 50 (1270) |
22 (559) |
11 1/2 (292) |
51 3/8 (1305) |
15 1/4 (387) |
15 1/4 (387) |
7 5/8 (194) |
52 11/32 (1330) |
11/32 (9) |
200 (90.7) |
| 600 | A | ||||||||||||
| 400 | B | 2 or 3 | 1494G | 56 (1422) |
30 1/2 (775) |
13 51/64 (350) |
57 5/8 (1464) |
20 (508) |
25 1/4 (641) |
7 5/8 (194) |
62 5/8 (1590) |
1 (25.4) |
300 (136.05) |
| 600 | B | ||||||||||||
| ¬ A = Non-Fusible, Fusible 250V - Class H/R, Fusible 600V - Class J B = Fusible 600V - Class H/R C = Non-fusible D = Fusible 250V - Class H/R, Fusible 600V - Class J |
|||||||||||||
| T These enclosures have one top mounting hole located on the center line. All other enclosures have two top mounting holes located as shown. | |||||||||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches
Type 4/4X (Enclosure Code "C") Stainless Steel Enclosure
|
| Size [A] | Fuse Style¬ |
Number of Poles |
Bulletin No. |
Approximate Dimensions in Inches (Millimeters) | Approx. Shipping Weight in lbs (kg) |
||||||||
| A Height |
B Width |
C Depth |
D Mounting |
E Mounting |
F Mounting |
G Handle Depth |
H | J | |||||
| 30 | A | 2 or 3 | 1494G | 13 5/16 (338) |
10 1/2 (267) |
8 9/16 (217) |
14 11/16 (373) |
T | 5 1/4 (133) |
5 9/16 (141) |
15 21/32 (398) |
13/16 (21) |
20 (9.07) |
| 60 | |||||||||||||
| 30 | B | 2 or 3 | 1494G | 27 1/2 (698) |
10 1/2 (267) |
8 1/4 (210) |
28 7/8 (733) |
T | 7 (178) |
5 9/16 (141) |
29 3/4 (756) |
13/16 (21) |
60 (27.21) |
| C | 6 | ||||||||||||
| D | |||||||||||||
| 60 | B | 2 or 3 | |||||||||||
| C | 6 | ||||||||||||
| D | |||||||||||||
| 30 | A | 2 or 3 | 1494GY | ||||||||||
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 30 | A | 2 or 3 | 1494GX | 30 (762) |
20 1/2 (521) |
9 7/8 (251) |
31 3/8 (797) |
17 (432) |
17 (432) |
5 9/16 (141) |
32 1/4 (819) |
13/16 (21) |
90 (40.82) |
| B | |||||||||||||
| 60 | A | ||||||||||||
| B | |||||||||||||
| 100 | A | 2 or 3 | 1494G | ||||||||||
| B | |||||||||||||
| C | 6 | ||||||||||||
| D | |||||||||||||
| 100 | A | 2 or 3 | 1494GX | 50 (1270) |
22 (559) |
11 3/16 (284) |
51 3/8 (1305) |
18 1/2 (470) |
18 1/2 (470) |
5 9/16 (141) |
52 1/4 (1327) |
13/16 (21) |
200 (90.7) |
| B | |||||||||||||
| 200 | A | 2 or 3 | 1494G | ||||||||||
| B | |||||||||||||
| C | 6 | ||||||||||||
| D | |||||||||||||
| 400 | A | 2 or 3 | 1494G | 56 (1422) |
30 1/2 (775) |
13 51/64 (350) |
57 5/8 (1464) |
20 (508) |
25 1/4 (641) |
7 5/8 (194) |
58 5/8 (1489) |
1 (25.4) |
300 (136.05) |
| B | |||||||||||||
| 600 | A | ||||||||||||
| B | |||||||||||||
| ¬ A = Non-Fusible, Fusible 250V - Class H/R, Fusible 600V - Class J B = Fusible 600V - Class H/R C = Non-fusible D = Fusible 250V - Class H/R, Fusible 600V - Class J |
|||||||||||||
| T These enclosures have one top mounting hole located on the center line. All other enclosures have two top mounting holes located as shown. | |||||||||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches
Type 4/4X (Enclosure Code "S") Non-metallic, Corrosion-resistant Enclosure
|
| Size [A] | Fuse Style¬ | Number of Poles |
Bulletin No. |
Approximate Dimensions in Inches (Millimeters) | Approx. Shipping Weight in lbs (kg) |
|||
| A Height |
B Width |
C Depth |
D Handle Depth |
|||||
| 30 | A | 2 or 3 | 1494G | 24 (610) |
10 (254) |
6 7/8 (175) |
4 7/8 (124) |
28 (12.7) |
| B | ||||||||
| 60 | A | |||||||
| B | ||||||||
| 30 | A | 2 or 3 | 1494GX | 24 (610) |
21 (533) |
9 1/4 (235) |
4 7/8 (124) |
60 (27.2) |
| B | ||||||||
| 60 | A | |||||||
| B | ||||||||
| 100 | A | 1494G | ||||||
| B | ||||||||
| ¬ A = Non-fusible, Fusible 250V - Class H/R, Fusible 600V - Class J/H/R B = Fusible 600V - Class H/R |
||||||||
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494H Safety Switches
Type 1 (Enclosure Code "A") Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
Knockout Fig. # |
| 30 | 240V | 10-3/8 (263.5) | 6-1/2 (165.1) | 3-3/8 (85.7) | 7-1/8 (181) | 1 |
| 600V | 12-5/8 (320.7) | 8-5/8 (219.1) | 4 (101.6) | 9-1/2 (241.3) | 2 | |
| Non-fusible | 10-9/16 (268.3) | 8-1/2 (215.9) | 4 (101.6) | 9-1/4 (235) | 2 | |
| 60 | 240V | 17-5/8 (447.7) | 9-1/2 (241.3) | 5 (127) | 10-1/8 (257.2) | 3 |
| 600V | 21-3/8 (542.9) | |||||
| Non-fusible | 17-5/8 (447.7) | |||||
| 100 | 240V | 21-3/8 (543) | 9-1/2 (241.3) | 5 (127) | 10-1/8 (257.2) | 3 |
| 600V | 22-3/4 (577.9) | 4 | ||||
| Non-fusible | 17-5/8 (447.7) | 3 | ||||
| 200 | 240V | 31-5/8 (803.3) | 13-5/8 (346.1) | 5-1/4 (133.4) | 14-1/2 (368.3) | 5 |
| 600V | ||||||
| Non-fusible | ||||||
Knockouts — Conduit Size
|
|
|
|
|
||||
| Fig. 1 | Fig. 2 | Fig. 3 | Fig. 4 | Fig. 5 |
| Switch Size [A] | Knockouts | ||||||||
| A | B | C | D | F | G | H | J | K | |
| 30 | 9/32 (7.1) | 1/4 (6.4) | 1/2 (12.7) | 1/2 (12.7) | — | — | 3/4 (19.1) | 1 (25.4) | 1 (25.4) |
| 60 | — | — | 3/4 (19.1) | 3/4 (19.1) | — | — | 1 (25.4) | 1-1/4 (31.8) | 1-1/2 (38.1) |
| 100 | — | — | — | — | — | — | 1-1/4 (31.8) | 1-1/2 (38.1) | 2 (50.8) |
| 200 | — | — | — | — | — | — | 1-1/2 (38.1) | 2 (50.8) | 2-1/2 (63.5) |
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494H Safety Switches
Type 3R (Enclosure Code "N") Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
Knockout Fig. # |
| 30 | 240V | 10-5/8 (269.9) | 6-7/8 (174.6) | 3-5/16 (84.1) | 7-1/8 (181) | 6 |
| 600V | 13-1/4 (336.6) | 8-7/8 (225.4) | 4 (101.6) | 9-1/2 (241.3) | 7 | |
| Non-fusible | 13-1/4 (336.6) | 8-7/8 (225.4) | 4 (101.6) | 9-1/2 (241.3) | 7 | |
| 60 | 240V | 17-1/2 (444.5) | 9-7/8 (250.8) | 5 (127) | 10-1/8 (257.2) | 8 |
| 600V | 22-1/4 (565.2) | 10-5/8 (269.9) | ||||
| Non-fusible | 17-1/2 (444.5) | 10-1/8 (257.2) | ||||
| 100 | 240V | 22-1/4 (565.2) | 9-7/8 (250.8) | 5 (127) | 10-5/8 (269.9) | 8 |
| 600V | 22-1/4 (565.2) | |||||
| Non-fusible | 17-1/2 (444.5) | 10-1/8 (257.2) | ||||
| 200 | 240V | 31-1/2 (800.1) | 14 (355.6) | 5-5/16 (134.9) | 14-1/8 (361.9) | 9 |
| 600V | ||||||
| Non-fusible | ||||||
Knockouts — Conduit Size
|
|
|
|
|||
| Fig. 6 | Fig. 7 | Fig. 8 | Fig. 9 |
| Switch Size [A] | Knockouts | ||||||||
| A | B | C | D | F | G | H | J | K | |
| 30 | 9/32 (7.1) | 1/4 (6.4) | 1/2 (12.7) | 1/2 (12.7) | — | — | 3/4 (19.1) | 1 (25.4) | 1 (25.4) |
| 60 | — | — | 3/4 (19.1) | 3/4 (19.1) | — | — | 1 (25.4) | 1-1/4 (31.8) | 1-1/2 (38.1) |
| 100 | — | — | — | — | — | — | 1-1/4 (31.8) | 1-1/2 (38.1) | 2 (50.8) |
| 200 | — | — | — | — | — | — | 1-1/2 (38.1) | 2 (50.8) | 2-1/2 (63.5) |
Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494H Safety Switches
Type 12 (Enclosure Code "F") Painted Metal Enclosures
|
| Switch Size [A] | Fuse Style | A Height |
B Width |
C Depth |
D Width (with handle) |
| 30 | 240V | 11-3/8 (288.9) | 7-3/8 (187.3) | 5-1/16 (128.6) | 8-1/8 (206.4) |
| 600V | 13-3/8 (339.7) | 9-3/8 (238.1) | 5-5/16 (134.9) | 10-1/4 (260.4) | |
| Non-fusible | 5-1/16 (128.6) | ||||
| 60 | 240V | 19-3/8 (492.1) | 9-3/8 (238.1) | 5-1/16 (128.6) | 10-1/4 (260.4) |
| 600V | 5-5/16 (134.9) | ||||
| Non-fusible | 5-1/16 (128.6) | ||||
| 100 | 240V | 25-3/8 (644.5) | 13-1/2 (342.9) | 5-5/16 (134.9) | 14-1/4 (362) |
| 600V | |||||
| Non-fusible | |||||
| 200 | 240V | 35-1/8 (892.2) | 13-1/2 (342.9) | 5-5/16 (134.9) | 15-1/4 (387.4) |
| 600V | 14-1/2 (368.3) | ||||
| Non-fusible | |||||