Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Operating Mechanisms > Bulletin 1494M Fixed-Depth Remote Operated Flange-Mounted Disconnect Switches
Bulletin 1494M Fixed-Depth Remote Operated Flange-Mounted Disconnect Switches
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
|
|
| Right-hand flange-mounted, remote operated, non-fusible disconnect switch, and operating mechanism |
|
Bulletin 1494M — Fixed-Depth Flange-Mounted Operating Mechanisms
Operating mechanism for remote operation of a disconnect switch:
- Remote: 30…200 A disconnect switch
- Fusible or non-fusible
- Can be used with enclosure Type 1 and 12
- Available in left-hand or right-hand flange operation
- Lockable handle
Description
Operation — The remote mechanism consists of (2) components a disconnect switch and the operating mechanism. To obtain a functional device, these components must be properly combined with a connecting link (supplied by the customer). This method allows the user to determine specific distances required between the disconnect switch and the operating mechanism.
Note:The operating mechanism can only be mounted below the switch.