Bulletin 1494M Fixed-Depth Remote Operated Flange-Mounted Disconnect Switches

Click to enlarge - 1494-2_2-5 Click to enlarge - 1494-2_2-6
Right-hand flange-mounted, remote operated, non-fusible disconnect switch,
and operating mechanism

Bulletin 1494M — Fixed-Depth Flange-Mounted Operating Mechanisms

Operating mechanism for remote operation of a disconnect switch:


Description

Operation — The remote mechanism consists of (2) components – a disconnect switch and the operating mechanism. To obtain a functional device, these components must be properly combined with a connecting link (supplied by the customer). This method allows the user to determine specific distances required between the disconnect switch and the operating mechanism.
Note:The operating mechanism can only be mounted below the switch.


Standards Compliance and Certifications

Standards Compliance

UL 508
CSA C22.2, No. 14


Certifications

UL Recognized (File No. E3125, Guide No. NLDX2)
CSA Certified (File No. LR1234)


Product Selection

Fusible and Non-Fusible Disconnect Kits


Complete Disconnect Switch Kit for Type 1 and Type 12¬ 
Continuous
Current
Rating [A]
600V AC
250V DC
UL and CSA Applications
Maximum Hp
AC 1-Phase DCT  IEC Applications
Maximum kW (AC23)
Open Type without Enclosure Flange Construction
Fusible Non-Fusible
3-Phase, 60 Hz 3-Phase, 50 Hz Right Hand Left Hand Right Hand Left Hand
200…208V 230V 460V 575V 115V 230V 125V 250V 220…240V 380…440V 500…600V Cat. No. Cat. No. Cat. No. Cat. No.
30 7.5 7.5 15 20 2 3 3 5 5.5 11 15 1494M-NF30 1494M-NFL30 1494M-N30 1494M-NL30
60 15 15 30 40 3 10 5 10 11 22 30 1494M-NF60 1494M-NFL60 1494M-N60 1494M-NL60
100 30 30 60 75 10 20 22 45 55 1494M-NF100 1494M-NFL100 1494M-N100 1494M-NL100
200 60 60 100 100 20 40 45 75 75 1494M-NF200 1494M-NFL200 1494M-N200 1494M-NL200
  
¬ Does not include rectangular bar stock 1/4 x 5/8 in. (6.35 x 15.8 mm) connecting bar between switch and remote operating mechanism and handle to be provided by user.
T Ratings based on utilizing two poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.

Fuse Block Adapter Plate Kits with Fuse Clips

Disconnect
Size [A]
Fuse Clip
Rating [A]
Class R Class J Class H
250V 600V 600V 250V 600V
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
30 30 1494F-R233 1494F-R633 1494F-J633 1494F-C233 1494F-C633
60 1494F-R263 1494F-R663 1494F-J663 1494F-C263 1494F-C663
60 1494F-R636 1494F-C636
60 1494F-R266 1494F-R666 1494F-J666 1494F-C266 1494F-C666
100 1494F-R216 1494F-R616 1494F-J616 1494F-C216 1494F-C616
100 100 1494F-R211 1494F-R611 1494F-J611 1494F-C211 1494F-C611
200 1494F-R221 1494F-R621 1494F-J621 1494F-C221 1494F-C621
200 200 1494F-R222 1494F-R622 1494F-J622 1494F-C222 1494F-C622
  

Accessories

Click to enlarge - 1494-2_18-1 Description For Use With Cat. No.
Auxiliary Contacts
1 N.O. Contact
1494C, 1494F, 1494V, and 1494M (30…400 A), 1494G (30…400 A) Disconnect Switches

1494D, 1494V¬  (125…400 A Frame) Circuit Breakers

1495-N8
1 N.C. Contact 1495-N9
Click to enlarge - 1494-2_18-4 Click to enlarge - 1494-2_18-5 Auxiliary Contacts 1 N.O. Contact 1494C, 1494G, and 1494V Disconnect Switches
600 A
595-A
Cat. No. 595-A Cat. No. 595-B 1 N.C. Contact
595-B
Click to enlarge - 1494-2_18-6 Auxiliary Contact Adapter Kit For Disconnect Switches 600 A only T  595-N1
Cat. No. 595-N1
Click to enlarge - 1495_N24_GS Auxiliary Contact Adapter Kit For Disconnect Switches with Left-Hand Mechanism 30…100 A Disconnect Switch 1494V Disconnect Switch with Left-Hand Mechanism,
30…100 A
T  1495-N24
Cat. No. 1495-N24 Auxiliary Contact Adapter Kit For Disconnect Switches with Left-Hand Mechanism 200 A Disconnect Switch 1494V Disconnect Switch with Left-Hand Mechanism,
200…400 A
T  1495-N25
Click to enlarge - 1494-2_18-2 Click to enlarge - 1494-2_18-3 Auxiliary Contact Adapter Kit For Circuit Breakers 125 A and 150 A Frame Allen-Bradley, Cutler-Hammer 1494D, 1494V Circuit Breakers T  1495-N21
250 A, 400 A Frame Allen-Bradley, Cutler-Hammer 1494V Circuit Breaker T  1495-N23
250 A Frame Allen-Bradley, Cutler-Hammer 1494D Circuit Breaker T  1495-N22
400 A Frame Allen-Bradley, Cutler-Hammer 1494D Circuit Breaker T  1495-N16
Cat. No.
1495-N21
Cat. No.
1495-N23
600 A, 800 A, 1200 A Frame
Cutler-Hammer
1494D Circuit Breaker T  1495-N13
Click to enlarge - 1494-2_18-7 Click to enlarge - 1494-2_18-8 Auxiliary Contacts 1 N.O. Contact 1494R Disconnect Switch 30 A, 60 A 895-A1
1 N.C. Contact 895-B1
1 N.O. and 1 N.C. Contact 895-C1
Auxiliary Contact Adapter Kit for 1 contact 895-M11
Cat. No. 895-A1 Cat. No. 895-M11 Auxiliary Contact Adapter Kit for 2 contacts 895-M12
Click to enlarge - 1494-2_18-9 Click to enlarge - 1494-2_18-10 Auxiliary Contacts 1 N.O. Contact 1494R Disconnect Switch
100 A, 200 A
895-A2
1 N.C. Contact 895-B2
1 N.O. and 1 N.C. Contact 895-C2
Auxiliary Contact Adapter Kit for 1 contact 895-M21
Cat. No. 895-A2 Cat. No. 895-M21 Auxiliary Contact Adapter Kit for 2 contacts 895-M22
Click to enlarge - 1495-N34_GS Electrical Interlocks 1 N.O. and 1 N.C. — early break 1494C, 1494G & 1494V Disconnect Switches with Left-/Right-Hand Mechanism,
30…100 & 600 A
‡  1495-N34
2 N.O. and 2 N.C. — early break ‡  1495-N35
1 N.O. and 1 N.C. — early break 1494C, 1494G, & 1494V Disconnect Switch with Right-Hand Mechanism,
200 A, 400 A
1495-N43
2 N.O. and 2 N.C. — early break 1495-N44
1 N.O. and 1 N.C. — early break 1494C and 1494V Disconnect Switch with Left-Hand Mechanism, 30…100 A 1495-N37
Cat. No. 1495-N34 2 N.O. and 2 N.C. — early break 1495-N38
Click to enlarge - 1495-N35_GS 1 N.O. and 1 N.C. — early break 1494V Disconnect Switch with Left-Hand Mechanism, 200 A 1495-N39
2 N.O. and 2 N.C. — early break 1495-N40
1 N.O. and 1 N.C. — early break 1494V Disconnect Switch with Left-Hand Mechanism, 400 A 1495-N41
2 N.O. and 2 N.C. — early break 1495-N42
10 A DPDT – early break (for 30 A, Type 1 & 3R only) 1494H Safety Switch 1495-N77
15 A DPDT – early break (for 30 A, Type 12)
15 A DPDT – early break (for all 60 A, 100 A, & 200 A, Type 1, 3R, and 12)
1495-N78
Cat. No. 1495-N35 Electrical Interlock Adapter Kit 600 A Disconnect Switch 1494G Disconnect Switch 1495-N36
  
¬ Requires an adapter kit on new installations.
T One adapter kit enables up to two auxiliary contacts to be installed.
‡ Additional adapter kit (Cat. No. 1495-N36) required for installation on 600 A switch.

Click to enlarge - 1494-2_19-1 Description For Use With Cat. No.
Lug Connectors (3 per package) 1494C, 1494F, 1494G, and 1494V Disconnect Switches  
Disconnect Size [A] Wire Size
30 #14…8 AWG Wire ¬ 
60 #14…4 AWG Wire §  1494R-N1
100 #8…1/0 AWG Wire §  1494R-N2
200 #6…4/0 AWG Wire §  1494R-N3
#6…250 MCM Wire (oversized) §  199-LF1
400 (2) of #1/0…250 MCM Wire §  1494R-N14
#4 AWG…500 MCM Wire (oversized) §  1494R-N15
600 (2) of #1/0…350 MCM Wire §  1494R-N10
Cat. No. 1494R-N3 (2) of #1/0…350 MCM Wire 1491-N621 or 1491-R621 600 A fuse blocks §  1494R-N11
Click to enlarge - 1494-2_19-2 Ground Connectors 1494C, 1494F, 1494G, and 1494V Disconnect Switches
599-GR1
Ground Lug Kits 30…100 A
200…400 A 599-GR2
600 A 599-GR3
30, 60 A 1494H & 1494HL Safety Switches 599-GR4
Cat. No. 599-GR1 100, 200 A 599-GR5
  Neutral Kits
30 A @ 250/600V AC Fusible (Type 1 & 3R)
1494H Safety Switches
599-NK1
30 A @ 250/600V AC Non-Fusible (Type 1 & 3R) 599-NK2
30 A @ 250/600V AC Fusible & Non-Fusible (Type 12) 599-NK3
60 A @ 250/600V AC Fusible & Non-Fusible (Type 1 & 3R) 599-NK4
60 A @ 250/600V AC Fusible (Type 12) 599-NK5
60 A @ 250/600V AC Non-Fusible (Type 12) 599-NK6
100 A @ 250/600V AC Fusible (Type 1 & 3R) 599-NK7
100 A @ 250/600V AC Non-Fusible (Type 1, 3R, and 12) 599-NK8
100 A @ 250/600V AC Fusible (Type 12) 599-NK9
200 A @ 250/600V AC Fusible & Non-Fusible (Type 1 & 3R) 599-NK10
200 A @ 250/600V AC Fusible & Non-Fusible (Type 12) 599-NK11
Click to enlarge - 1494-2_19-3 Fuse Clips (6 per package) 1494C, 1494F, 1494G, and 1494V Disconnect Switches

1491 Fuse Blocks



1401-N41
Fuse Class Fuse Clip Rating [A]
250V 600V
H, J 30
60 30 1401-N42
60 1401-N43
100 100 1401-N44
200 200 1401-N45
400 400 1401-N46
J 600 600 T 
R 30 1401-N50
60 30 1401-N51
60 1401-N52
100 100 1401-N53
200 200 1401-N54
400 400 1401-N55
H, R 600 600 ‡ 
  Class R Fuse Clip Kits
30 A @ 250V AC (Type 1, 3R, 12)
1494H Safety Switches
1401-N70
30 A @ 600V AC (Type 1, 3R) 1401-N71
30 A @ 600V AC (Type 12) 1401-N72
60 A @ 250V AC (Type 1, 3R, 12) 1401-N73
60 A @ 600V AC (Type 1, 3R, and 12) 1401-N74
100 A @ 250/600V AC (Type 1 & 3R) 1401-N75
100 A @ 250/600V AC (Type 12) 1401-N76
200 A @ 250/600V AC (Type 1, 3R, and 12) 1401-N77
  
¬ All terminals of the 30 A switches are furnished with self-lifting pressure plate connectors as standard.
T Fuse clips not required; fuse bolts directly to terminal. ‡ Included with Bulletin 1491 separate mounted fuse blocks.
§ Each kit contains (3) lugs. § Each kits contains (2) lugs.

Click to enlarge - 1495_FuseCover_GS Protective Fuse Covers (for use with Bul. 1494C, 1494G, and 1494V disconnect switches)
Switch Rating [A] Fuse Class Fuse Clip Rating [A] Cat. No.
250V 600V
30
30
60
30
60
60
100
Nonfusible
H, R
H, R
J
J
Nonfusible
Nonfusible

30
60
30
60




30
60

1495-N64
30
60
100
H, R
H, R
J


100
30
60
100
1495-N65
100 H, R 100 100 1495-N66
200
200
Nonfusible
H, J, R

200

200
Ø  1495-N67
200
200
Nonfusible
H, J, R

200

200
z  1495-N62
400
400
Nonfusible
H, J, R

400

400
Ø  1495-N68
400
400
Nonfusible
H, J, R

400

400
z  1495-N63
600
600
Nonfusible
J

600

600
Ø  1495-N61
  Protective Line Covers (for use with Bul. 1494C, 1494G, and 1494V disconnect switches)
30…100 1495-N80
200 1495-N81
400 1495-N82
600 1495-N83
  
Ø Switch with right-hand mechanism.
z Switch with left-hand mechanism.

Description For Use With Cat. No.
Click to enlarge - 1494-2_21-1 Defeater Bracket Extension Kit
For use with operating handles that do not align properly with the door catch or door hardware on enclosures with a rolled lip flange construction.
All 1494F and 1494V Handles (except 1494V-R1 and 1494V-R2)
For 400…600 A switches, defeater bracket is included with connecting rod kits.
1494V-H12
Click to enlarge - 1494-2_21-2 Alternate Mounting Kits
For use where the flange material thickness is greater than 3/16 in. (4.8 mm).
Operating Handles 1494V-H1 or 1494V-H11 1494V-H3
Operating Handles 1494V-H2 1494V-H6
Click to enlarge - 1494-2_21-3 Channel Support Kits
For use to prevent flexing of the operating handle mounting surface. This is especially useful when the operating handle is mounted on a channel in a multi-door enclosure.
30…200 A Switches
Applies only to Operating Handle Cat. Nos. 1494F-P1, M1, and S1.
1494V-H15
  Conduit Hubs (for Type 3R enclosures)¬ 
19.05 mm (3/4 in.) hub
1494H Safety Switches
1495-N71
25.4 mm (1 in.) hub 1495-N72
31.75 mm (1-1/4 in.) hub 1495-N73
38.1 mm (1-1/2 in.) hub 1495-N74
50.8 mm (2 in.) hub 1495-N75
63.5 mm (2-1/2 in.) hub 1495-N76
Click to enlarge - 1494-2_21-4 Conduit Connectors

Metallic Conduit Connectors


1 in. (25.4 mm)
30 A 1494G Disconnect Switches 1232-N11
1-1/4 in. (31.75 mm) 60 A 1232-N12
1-1/2 in. (38.1 mm) 100 A 1232-N13
2-1/2 in. (63.5 mm) 200 A 1232-N14
3 in. (76.2 mm) 400…600 A 1232-N15
Click to enlarge - 1494-2_21-5 Non-Metallic Conduit Connectors

1/2 in. (12.7 mm)
30 A 1490-N1
3/4 in. (19 mm) 30 A 1490-N9
1 in. (25.4 mm) 30 A 1490-N10
1-1/4 in. (31.75 mm) 60 A 1490-N11
1-1/2 in. (38.1 mm) 100 A 1490-N5
2 in. (50.8 mm) 200 A 1490-N6
2-1/2 in. (63.5 mm) 200 A 1490-N7
3 in. (76.2 mm) 400…600 A 1490-N8
Click to enlarge - 1494-2_21-6 Grounding Adapters

#14…10 AWG, 1/2 in. (12.7 mm)
30 A 1490-N19
#14…8 AWG, 3/4 in. (19 mm) 30 A 1490-N20
#14…8 AWG, 1 in. (24.5 mm) 30 A 1490-N21
#14…4 AWG, 1-1/4 in. (31.8 mm) 60 A 1490-N22
#8…1/0 AWG, 1-1/2 in. (38.1 mm) 100 A 1490-N23
#8…1/0 AWG, 2 in. (50.8 mm) 200 A 1490-N24
#6…2/0 AWG, 2-1/2 in. (63.5 mm) 200 A 1490-N25
#6…4/0 AWG, 3 in. (76.2 mm) 400…600 A 1490-N26
  
¬ Packaged in quantities of 10.

Click to enlarge - 1494-2_20-1a Click to enlarge - 1494-2_20-2 Decription For Use With Cat. No.§ 
Type 12 Door Hardware Kit Includes:
handle, cam, defeater actuator lever, rollers, and shims

Enclosure Height less than 40 in. (1016 mm)

Top and Side (Right Hand)
1494C,
All 1494V
1494V-L1¬ 
Top and Side (Left Hand) 1494V-LL1¬ 
Enclosure Height 40…60 in. (1016…1524 mm)

Top and Side (Right Hand)
Bottom
1494V-L1¬ 
and 1494V-L2
Cat. No. 1494V-L1 Top and Side (Left Hand)
Bottom
1494V-LL1¬ 
and 1494V-L2
Click to enlarge - 1494-2_20-1b Enclosure Height greater than 60 in. (1524 mm)

Top, Side and Bottom (Right Hand)
1494V-L3¬ 
Cat. No. 1494V-L2 Cat. No. 1494V-L3 Top, Side and Bottom (Left Hand) 1494V-LL3¬ 
Click to enlarge - 1494-2_20-3 Type 12 Door Hardware Kit Includes:
Handle, cam, defeater actuator lever, rollers, and shims

Enclosure Height less than 30 in. (762 mm)

Top and Side (Right Hand)
1494F
1494M,
1494D
1494F-L1¬ 
Top and Side (Left Hand) 1494F-LL1¬ 
Top and Bottom (Right Hand) 1494F-L2¬ 
Top and Bottom (Left Hand) 1494F-LL2¬ 
Enclosure Height 30…48 in. (762…1219 mm)

Top and Bottom (Right Hand)
Side
1494F-L2¬ 
and 1494F-L3
Top and Bottom (Left Hand)
Side
1494F-LL2
and 1494F-L3¬ 
Enclosure Height greater than 48 in. (1219 mm)

Top, Side, and Bottom (Right Hand)
1494F-L4T 
Cat. No. 1494F-L2 and 1494F-L3 Top, Side, and Bottom (Left Hand) 1494F-LL4T 
Click to enlarge - 1494-2_20-4 Master Door Interlock Kits
Interlock kits are designed to provide interlocking between the master and auxiliary doors of the same enclosure and for use with Cat. Nos. 1494F-L4 and 1494F-LL4 hardware kits or Cat. Nos. 1494V-L3 and 1494V-LL3 hardware kits. Specify one master door kit and as many auxiliary door kits as necessary (9 maximum). Connecting bars must be supplied by user.
1494C,
1494F,
1494M,
1494D,
1494V
1494F-N20‡ 
Cat. No. 1494F-N20 Auxiliary Door Interlock Kit 1494F-N21
  
¬ Door hardware kit does not include rectangular connecting bars (1/4 x 1/2 in.). To be provided by customer.
T Door hardware kit does not include rectangular connecting bars (1/4 x 5/8 in.). To be provided by customer.
‡ Master door interlock kit does not include rectangular connecting bars (3/8 x 3/8 in.). To be provided by customer.
§ If the Rockwell Automation door hardware kits are to be installed in a commercially available enclosure, consult the enclosure manufacturer's application data for proper kit selection.

Specifications

Bulletin 1494C, 1494F, 1494G, 1494M, 1494R, 1494V Disconnect Switches

Disconnect Switch Electrical Ratings
Switch Size 30 A 60 A 100 A 200 A 400 A 600 A
Rated insulation voltage Ui (UL) IEC (600) 660V
Ratings
UL/CSA/NEMA
HP 230V/60 Hz
460V/60 Hz
575V/60 Hz
7.5
15
20
15
30
50
30
60
75
60
125
150
125
250
350
200
400
500
250V DC 5 10 20 40 50 50
Continuous
Current
600V AC
250V DC
30 60 100 200 400 600
Auxiliary Contact Electical Ratings
NEMA/EEMAC B600, P300
IEC Ratings Ui    660V Ith    10 A  


ACII    Ux
12…120V
220…240V
380…400V
500…600V


Ie
6 A
3 A
1.5 A
1.2 A
Mechanical
Degree of protection Operating handles Molded Type 1, 3R, 4, 4X, 12,
Painted Type 1, 3R, 4, 12
Stainless Steel Type 4, 4X
Mechanical life (Typical) 20 000 operations (30…200 A) 10 000 operations (400…600 A)
Switching frequency (operations/hr) 30, 60, 100, and 200 A sizes — 300 maximum400 and 600 A size — 240 Maximum
Environmental
Temperature Operating -35…+40 °C (-31…+104 °F)
Storage -40…+65 °C (-40…+149 °F)
Altitude (per IEC 947-5) 2000m per IEC 337-1
Relative Humidity (per IEC 947-3) 90% at 20 °C and 50% at 40 °C
Design Specification/Test Requirements
Dielectric strength 2200V for 1 minute
Electrical life 6000 operations at rated current
Short Circuit Withstand Capability 10 000 A: unfused        10 000 A: with Class H fuses        200 000 A: with Class J or Class R fuses
Construction
Switch body material Phenolic
Contact material Copper, tin-plated
Terminals 30 A
60 A
100 A
200 A
400 A
600 A
#10 - 32 screw and self-lifting pressure plate
1/4 in. - 28 screw-lug, copper
5/16 in. - 24 screw-lug, copper
3/8 in. - 24 screw-lug, copper
3/8 in. - 24 screw-lug, copper
1/2 in. - 13 screw-lug, copper
All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire.
Conductor Size (mm2) 30 A
60 A
100 A
200 A
400 A
600 A
#14…8 AWG (1.5…10 mm2)
#14…4 AWG (2.5…16 mm2)
#8…1/0 AWG (10…50 mm2)
#6…4/0 AWG (16…95 mm2)
2 of #1/0 AWG…250 MCM (2 per lug) 2 of 185 mm2…250 MCM
2 of #1/0 AWG…350 MCM (2 per lug) 2 of 185 mm2…350 MCM
Recommended Torque
30 A
60 A
100 A
200 A
400 A
600 A
Conductor into Lug
20 lbin
45 lbin
150 lbin
275 lbin
325 lbin
325 lbin
Lug to Terminal
20 lbin
50 lbin
90 lbin
175 lbin
275 lbin
275 lbin
Mechanisms Zinc-plated steel, RoHS Compliant finish
  

Bulletin 1494H Disconnect Switches

Disconnect Switch Electrical Ratings
Switch Size 30 A 60 A 100 A 200 A
Rated insulation voltage Ui (UL) IEC (600) 660V
Ratings
UL/CSA/NEMA
Hp 230V/60 Hz
460V/60 Hz
575V/60 Hz
10
20
30
20
50
60
40
75
100
60
125
150
250V DC 5 10 20 40
Continuous
Current
600V AC
250V DC
30 60 100 200
Auxiliary Contact Electical Ratings
Continuous Current 10 A 15 A
Pole Configuration DPDT DPDT
Mechanical
Degree of protection Operating handles Painted Type 1, 3R, 12
Mechanical life (Typical) 10 000 operations
Switching frequency (operations/hr) 300 maximum
Environmental
Temperature Operating -35…+40 °C (-31…+104 °F)
Storage -40…+65 °C (-40…+149 °F)
Altitude (per IEC 947-5) 2000m per IEC 337-1
Relative Humidity (per IEC 947-3) 90% at 20 °C and 50% at 40 °C
Design Specification/Test Requirements
Dielectric strength 2200V for 1 minute
Electrical life 6000 operations at rated current
Short Circuit Withstand Capability 10 000 A: unfused    10 000 A: with Class H fuses    200 000 A: with Class J or Class R fuses (30…100 A)
100 000 A: with Class J or Class R fuses (200 A)
Construction
Switch body material Phenolic
Contact material Copper, tin-plated
Terminals 30 A
60 A
100 A
200 A
#10 - 32 screw and self-lifting pressure plate
1/4 in. - 28 screw-lug, copper
5/16 in. - 24 screw-lug, copper
3/8 in. - 24 screw-lug, copper
All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire.
Conductor Size (mm2) 30 A
60 A
100 A
200 A
#14…8 AWG
#12…2 AWG
#10…1/0 AWG
#2…250 MCM AWG
Recommended Torque
30 A
60 A
100 A
200 A
Conductor into Lug
36…40 lbin
35…45 lbin
35…50 lbin
275 lbin
Mechanisms Zinc-plated steel, Bronze chromate finish
  

Bulletin 1494D, 1494V Circuit Breakers

Electrical Ratings
Frame Size 125 A 150 A 250 A 400 A 600 A 800 A 1200 A
Auxiliary Contacts
1494V, 1494D
NEMA/EEMAC B600, P300
IEC Ratings

ACII    Ux
12…120V
220…240V
380…400V
500…600V


Ie
6 A
3 A
1.5 A
1.2 A
Maximum Number of Auxiliary Contacts 2
Mechanical Data
Mechanical Life (Typical) 10 000
Construction
Mechanisms Zinc-plated steel
Environmental Data
Ambient Temperature¬  Operating –20…+40 °C (–4…+104 °F)
Storage –40…+65 °C (–40…+149 °F)
Altitude (per IEC 947-5) 2000 m per IEC 337-1
Relative Humidity (per IEC 947-3) 90% @ 20 °C (68 °F), 50% @ 40 °C (104 °F)
  
¬ Refer to circuit breaker specifications for other limitations.

Bulletin 1491 Fuse Blocks

Electrical
UL Fuse Type Class H Class J Class R Class C Class CC
CSA Fuse Type HRCI-H HRCI-J HRCI-R HRCI-C HRCI-MISC
Maximum Fuse Cartridge Size 30…600 A 30…600 A 30…600 A 30…600 A 30 A
Maximum Voltage AC 600V 600V 600V 600V 600V
DC 250V 250V 250V 250V 250V
Thermal Current Rating 30…600 A 30…600 A 30…600 A 30…600 A 30 A
Maximum Short Circuit Prospective Fault Current 10 kA 200 kA 200 kA 100 kA 200 kA
Construction
Fuse Clips Tin-plated copper
Terminals Tin-plated copper
Fuse Block Base Phenolic or Porcelain
Environmental
Ambient Temperature Open –20…+55 °C (–4…+131 °F)
Enclosed –20…+40 °C (–4…+104 °F)
Storage –40…+65 °C (–40…+149 °F)
Altitude (per IEC 947-5) 2000 m
Relative Humidity (per IEC 947-3) 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F)
  

Approximate Dimensions

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494C, 1494V

Click to enlarge - 1494-2_24-1


Click to enlarge - 1494-2_24-2
Bulletin 1494V — 30…200 A


Click to enlarge - 1494-2_24-3
Bulletin 1494V — 400…600 A


Disconnect Switches¬ 

NEMA Size
[A]
A BT  C D E F
Max. Min. Max.
30 6-19/64
(160)
7-31/32
(202)
6-3/4
(171)
21-5/8
(549)
2-3/4
(69.9)
7-9/16
(192)
3-7/8
(98.5)
60 6-19/64
(160)
8-15/32
(215)
6-3/4
(171)
21-5/8
(549)
2-9/16
(65.1)
7-9/16
(192)
3-7/8
(98.5)
100 6-19/64
(160)
9-1/8
(231.8)
6-3/4
(171)
21-5/8
(549)
3-37/64
(90.9)
7-9/16
(192)
3-7/8
(98.5)
200 8-5/64
(205.2)
15-9/64
(384.5)
7-3/4
(197)
21-5/8
(549)
6-35/64
(166.3)
8-25/32
(223)
4-21/32
(118)
400 11
(279.4)
11-5/8
(295.3)
9
(229)
21-5/8
(549)
8
(203.2)
10
(254)
5-1/2
(139.7)
600 15-23/32
(399.2)
17-19/32
(446.8)‡ 
9
(229)
21-5/8
(549)
12
(304.8)
11-27/32
(300.8)
8-51/64
(223.3)
  
¬ Approximate dimensions are for reference only.
T This approximate dimension will vary by fuse class and size.
‡ Approximate dimension with Class J fuses.

Circuit Breakers§ 

Frame A C D E F
Min. Max.
125A
140U-H, 140M-H, EF, HMCPE
150A
EHD, FD, FDB, FDC, HFD, HMCP
6
(152.4)
6-3/4
(171.5)
23
(584.2)
6
(152.4)
5-7/16
(138.1)
5
(127)
250A
140U-J, 140M-J, EF
250A
JD, JDB, JDC, HJD, HMCP
11-1/4
(285.8)
7-7/8
(200.0)
22-9/16
(573.1)
10
(254)
5-23/32
(145.2)
9-23/32
(246.8)
400 A
KD, KDB, KDC, HKD, HMCP
11-3/8
(228.9)
7-7/8
(200.0)
22-9/16
(573.1)
12
(304.8)
7-1/8
(181.0)
9-21/32
(245.3)
  
§ Approximate dimensions are for reference only.

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494F, 1494M Disconnect Switches¬ 

Click to enlarge - 1494-2_25-1


Click to enlarge - 1494-2_25-2


NEMA Size [A] A BT  C D E F G H J K L P S‡ 
Min. Max.
Without Door Hardware
30 5-15/16
(150.8)
10-3/4
(273.1)
6-3/8
(161.9)
2-3/16
(55.6)
7-1/2
(190.5)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-1/8
(54)
2-1/16
(52.4)
60 5-15/16
(150.8)
13-3/16
(335)
6-3/8
(161.9)
2
(50.8)
7-1/2
(190.5)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-1/8
(54)
3-1/4
(82.6)
100 7-15/16
(200.4)
16-3/4
(425.5)
8-1/2
(215.9)
5
(127)
8-1/4
(209.6)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-1/8
(54)
8-9/64
(206.8)
200 10-1/2
(266.7)
20-13/16
(528.6)
9
(228.6)
7
(177.8)
11-3/8
(289)
5-9/16
(141.3)
1-1/4
(31.8)
11-1/8
(282.6)
1-11/16
(42.9)
13/16
(20.6)
9-1/2
(241.3)
2-9/32
(57.9)
10-13/32
(264.3)
Small and Intermediate Enclosures with Door Hardware
30 5-15/16
(150.8)
10-3/4
(273.1)
6-3/8
(161.9)
2-3/16
(55.6)
7-1/2
(190.5)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-5/32
(54.8)
2-1/4
(57.2)
60 5-15/16
(150.8)
13-3/16
(335)
6-3/8
(161.9)
2
(50.8)
7-1/2
(190.5)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-5/32
(54.8)
3-1/4
(82.6)
100 7-15/16
(200.4)
16-3/4
(425.5)
8-1/2
(215.9)
5
(127)
8-1/4
(209.6)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-5/32
(54.8)
8-9/64
(206.8)
200 10-1/2
(266.7)
20-13/16
(528.6)
9
(228.6)
7
(177.8)
11-3/8
(289)
5-9/16
(141.3)
1-1/4
(31.8)
11-1/8
(282.6)
1-11/16
(42.9)
13/16
(20.6)
9-1/2
(241.3)
2-5/16
(58.7)
10-13/32
(264.3)
Large Enclosures with Door Hardware
30 5-15/16
(150.8)
10-3/4
(273.1)
6-3/8
(161.9)
2-3/16
(55.6)
7-1/2
(190.5)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-1/4
(57.2)
2-3/4
(69.9)
60 5-15/16
(150.8)
13-3/16
(335)
6-3/8
(161.9)
2
(50.8)
7-1/2
(190.5)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-1/4
(57.2)
3-1/4
(82.6)
100 7-15/16
(200.4)
16-3/4
(425.5)
8-1/2
(215.9)
5
(127)
8-1/4
(209.6)
3-3/4
(95.3)
1-3/16
(30.2)
8-1/2
(215.9)
1-7/16
(36.5)
15/32
(11.9)
7-3/16
(182.6)
2-1/4
(57.2)
8-9/64
(206.8)
200 10-1/2
(266.7)
20-13/16
(528.6)
9
(228.6)
7
(177.8)
11-3/8
(289)
5-9/16
(141.3)
1-1/4
(31.8)
11-1/8
(282.6)
1-11/16
(42.9)
13/16
(20.6)
9-1/2
(241.3)
2-11/32
(59.5)
10-13/32
(264.3)
  
¬ Approximate dimensions are for reference only.
T This approximate dimension will vary by fuse class and size.
‡ Minimum wiring space for the maximum wire size.

Bulletin 1494D Circuit Breakers§ 

Cutler-Hammer Frame A C D E F
Min. Max.
150 A — EHD, FD, FDB, FDC, HFD, HMCP 7-13/16 (198.4) 6-3/8 (161.9) 6 (152.4) 5-5/8 (142.9) 6-7/16 (163.5)
250 A — JD, JDB, JDC, HJD, HMCP 11-1/2 (292.1) 8-3/8 (212.7) 8 (203.2) 5-13/16 (147.6) 9-7/16 (239.7)
400 A — KD, KDB, KDC, HKD, HMCP 11-1/2 (292.1) 8-3/8 (212.7) 12 (304.8) 6-7/8 (174.6) 9-7/16 (239.7)
600 A — LD, HLD, LDC, LA, HLA, LC, HLC 11-3/8 (288.9) 9-1/2 (241.3) 8 (203.2) 12 (304.8) 10-17/32 (267.5)
800 A — MA, MDL, HMDL, HMA, MC, ND, HND, NDC 16 (406.4) 9-1/2 (241.3) 10 (254) 12-5/16 (312.7) 15-3/32 (183.4)
1200 A — NB TRI-PAK 22 (558.8) 9-1/2 (241.3) 10 (254) 12-5/16 (312.7) 21-3/32 (535.8)
1200 A — HNC, ND, HND, NDC, NB, HNB, NC, HNC 16 (406.4) 9-1/2 (241.3) 12 (304.8) 12-5/16 (312.7) 25-3/32 (183.4)
  
§ Approximate dimensions are for reference only.

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches

Type 3R/4/12 (Enclosure Code "F") Painted Metal Enclosures

Click to enlarge - 1494-2_26-1


Size [A] Fuse
Style¬ 
Number
of Poles
Bulletin
No.
Approximate Dimensions in Inches (Millimeters) Approx.
Shipping
Weight in
lbs (kg)
A
Height
B
Width
C
Depth
D
Mounting
E
Mounting
F
Mounting
G
Handle
Depth
H J
30 A 2 or 3 1494G 13 5/16
(338)
10 1/2
(267)
8 1/4
(210)
14 11/16
(373)
T  5 1/4
(133)
5 9/16
(141)
15 21/32
(398)
11/32
(9)
20
(9.07)
60
30 B 2 or 3 1494G 20
(509)
10 1/2
(267)
10 3/16
(259)
21 7/16
(545)
T  5 1/4
(133)
5 9/16
(141)
22 13/32
(569)
11/32
(9)
30
(13.6)
60
100 A
30 C 6 1494G 27 1/2
(698)
10 1/2
(267)
8 1/4
(210)
28 7/8
(733)
T  5 1/4
(133)
5 9/16
(141)
29 7/8
(759)
13/16
(21)
60
(27.21)
D
60 C
D
30 A 2 or 3 1494GY
B
60 A
B
30 A 2 or 3 1494GX 30
(762)
20 1/2
(521)
10 3/16
(259)
31 3/8
(797)
15 1/4
(387)
15 1/4
(387)
5 9/16
(141)
32 3/8
(822)
13/16
(21)
90
(40.82)
B
60 A
B
100 D 6 1494G
100 A 2 or 3 1494GY
B
100 B 2 or 3 1494G 31 1/2
(800)
10 1/2
(267)
10 3/32
(257)
32 7/8
(835)
T  5 1/4
(133)
5 9/16
(141)
33 27/32
(860)
11/32
(9)
70
(31.73)
C 6
200 A 2 or 3
B
100 A 2 or 3 1494GX 50
(1270)
22
(559)
11 1/2
(292)
51 3/8
(1305)
15 1/4
(387)
15 1/4
(387)
5 9/16
(141)
52 11/32
(1330)
11/32
(9)
200
(90.7)
B
200 C 6 1494G
D
200 A 2 or 3 1494GY
B
400 A 2 or 3 1494G 50
(1270)
22
(559)
11 1/2
(292)
51 3/8
(1305)
15 1/4
(387)
15 1/4
(387)
7 5/8
(194)
52 11/32
(1330)
11/32
(9)
200
(90.7)
600 A
400 B 2 or 3 1494G 56
(1422)
30 1/2
(775)
13 51/64
(350)
57 5/8
(1464)
20
(508)
25 1/4
(641)
7 5/8
(194)
62 5/8
(1590)
1
(25.4)
300
(136.05)
600 B
  
¬ A = Non-Fusible, Fusible 250V - Class H/R, Fusible 600V - Class J
B = Fusible 600V - Class H/R
C = Non-fusible
D = Fusible 250V - Class H/R, Fusible 600V - Class J
T These enclosures have one top mounting hole located on the center line. All other enclosures have two top mounting holes located as shown.

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches

Type 4/4X (Enclosure Code "C") Stainless Steel Enclosure

Click to enlarge - 1494-2_27-1


Size [A] Fuse
Style¬ 
Number
of Poles
Bulletin
No.
Approximate Dimensions in Inches (Millimeters) Approx.
Shipping
Weight in
lbs (kg)
A
Height
B
Width
C
Depth
D
Mounting
E
Mounting
F
Mounting
G
Handle
Depth
H J
30 A 2 or 3 1494G 13 5/16
(338)
10 1/2
(267)
8 9/16
(217)
14 11/16
(373)
T  5 1/4
(133)
5 9/16
(141)
15 21/32
(398)
13/16
(21)
20
(9.07)
60
30 B 2 or 3 1494G 27 1/2
(698)
10 1/2
(267)
8 1/4
(210)
28 7/8
(733)
T  7
(178)
5 9/16
(141)
29 3/4
(756)
13/16
(21)
60
(27.21)
C 6
D
60 B 2 or 3
C 6
D
30 A 2 or 3 1494GY
B
60 A
B
30 A 2 or 3 1494GX 30
(762)
20 1/2
(521)
9 7/8
(251)
31 3/8
(797)
17
(432)
17
(432)
5 9/16
(141)
32 1/4
(819)
13/16
(21)
90
(40.82)
B
60 A
B
100 A 2 or 3 1494G
B
C 6
D
100 A 2 or 3 1494GX 50
(1270)
22
(559)
11 3/16
(284)
51 3/8
(1305)
18 1/2
(470)
18 1/2
(470)
5 9/16
(141)
52 1/4
(1327)
13/16
(21)
200
(90.7)
B
200 A 2 or 3 1494G
B
C 6
D
400 A 2 or 3 1494G 56
(1422)
30 1/2
(775)
13 51/64
(350)
57 5/8
(1464)
20
(508)
25 1/4
(641)
7 5/8
(194)
58 5/8
(1489)
1
(25.4)
300
(136.05)
B
600 A
B
  
¬ A = Non-Fusible, Fusible 250V - Class H/R, Fusible 600V - Class J
B = Fusible 600V - Class H/R
C = Non-fusible
D = Fusible 250V - Class H/R, Fusible 600V - Class J
T These enclosures have one top mounting hole located on the center line. All other enclosures have two top mounting holes located as shown.

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494G, 1494GX, 1494GY Enclosed Disconnect Safety Switches

Type 4/4X (Enclosure Code "S") Non-metallic, Corrosion-resistant Enclosure

Click to enlarge - 1_129


Size [A] Fuse Style¬  Number of
Poles
Bulletin
No.
Approximate Dimensions in Inches (Millimeters) Approx.
Shipping
Weight in
lbs (kg)
A
Height
B
Width
C
Depth
D
Handle
Depth
30 A 2 or 3 1494G 24
(610)
10
(254)
6 7/8
(175)
4 7/8
(124)
28
(12.7)
B
60 A
B
30 A 2 or 3 1494GX 24
(610)
21
(533)
9 1/4
(235)
4 7/8
(124)
60
(27.2)
B
60 A
B
100 A 1494G
B
  
¬ A = Non-fusible, Fusible 250V - Class H/R, Fusible 600V - Class J/H/R
B = Fusible 600V - Class H/R

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494H Safety Switches

Type 1 (Enclosure Code "A") Painted Metal Enclosures

Click to enlarge - 1494H_Type 1_Dims


Switch Size [A] Fuse Style A
Height
B
Width
C
Depth
D
Width (with handle)
Knockout Fig. #
30 240V 10-3/8 (263.5) 6-1/2 (165.1) 3-3/8 (85.7) 7-1/8 (181) 1
600V 12-5/8 (320.7) 8-5/8 (219.1) 4 (101.6) 9-1/2 (241.3) 2
Non-fusible 10-9/16 (268.3) 8-1/2 (215.9) 4 (101.6) 9-1/4 (235) 2
60 240V 17-5/8 (447.7) 9-1/2 (241.3) 5 (127) 10-1/8 (257.2) 3
600V 21-3/8 (542.9)
Non-fusible 17-5/8 (447.7)
100 240V 21-3/8 (543) 9-1/2 (241.3) 5 (127) 10-1/8 (257.2) 3
600V 22-3/4 (577.9) 4
Non-fusible 17-5/8 (447.7) 3
200 240V 31-5/8 (803.3) 13-5/8 (346.1) 5-1/4 (133.4) 14-1/2 (368.3) 5
600V
Non-fusible
  

Knockouts — Conduit Size

Click to enlarge - 1494H_Fig 1   Click to enlarge - 1494H_Fig 2   Click to enlarge - 1494H_Fig 3   Click to enlarge - 1494H_Fig 4   Click to enlarge - 1494H_Fig 5
Fig. 1 Fig. 2 Fig. 3 Fig. 4 Fig. 5

Switch Size [A] Knockouts
A B C D F G H J K
30 9/32 (7.1) 1/4 (6.4) 1/2 (12.7) 1/2 (12.7) 3/4 (19.1) 1 (25.4) 1 (25.4)
60 3/4 (19.1) 3/4 (19.1) 1 (25.4) 1-1/4 (31.8) 1-1/2 (38.1)
100 1-1/4 (31.8) 1-1/2 (38.1) 2 (50.8)
200 1-1/2 (38.1) 2 (50.8) 2-1/2 (63.5)
  

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494H Safety Switches

Type 3R (Enclosure Code "N") Painted Metal Enclosures

Click to enlarge - 1494H_Type 3R_Dims


Switch Size [A] Fuse Style A
Height
B
Width
C
Depth
D
Width (with handle)
Knockout Fig. #
30 240V 10-5/8 (269.9) 6-7/8 (174.6) 3-5/16 (84.1) 7-1/8 (181) 6
600V 13-1/4 (336.6) 8-7/8 (225.4) 4 (101.6) 9-1/2 (241.3) 7
Non-fusible 13-1/4 (336.6) 8-7/8 (225.4) 4 (101.6) 9-1/2 (241.3) 7
60 240V 17-1/2 (444.5) 9-7/8 (250.8) 5 (127) 10-1/8 (257.2) 8
600V 22-1/4 (565.2) 10-5/8 (269.9)
Non-fusible 17-1/2 (444.5) 10-1/8 (257.2)
100 240V 22-1/4 (565.2) 9-7/8 (250.8) 5 (127) 10-5/8 (269.9) 8
600V 22-1/4 (565.2)
Non-fusible 17-1/2 (444.5) 10-1/8 (257.2)
200 240V 31-1/2 (800.1) 14 (355.6) 5-5/16 (134.9) 14-1/8 (361.9) 9
600V
Non-fusible
  

Knockouts — Conduit Size

Click to enlarge - 1494H_Fig 6   Click to enlarge - 1494H_Fig 7   Click to enlarge - 1494H_Fig 8   Click to enlarge - 1494H_Fig 9
Fig. 6 Fig. 7 Fig. 8 Fig. 9

Switch Size [A] Knockouts
A B C D F G H J K
30 9/32 (7.1) 1/4 (6.4) 1/2 (12.7) 1/2 (12.7) 3/4 (19.1) 1 (25.4) 1 (25.4)
60 3/4 (19.1) 3/4 (19.1) 1 (25.4) 1-1/4 (31.8) 1-1/2 (38.1)
100 1-1/4 (31.8) 1-1/2 (38.1) 2 (50.8)
200 1-1/2 (38.1) 2 (50.8) 2-1/2 (63.5)
  

Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 1494H Safety Switches

Type 12 (Enclosure Code "F") Painted Metal Enclosures

Click to enlarge - 1494H_Type 12_Dims


Switch Size [A] Fuse Style A
Height
B
Width
C
Depth
D
Width (with handle)
30 240V 11-3/8 (288.9) 7-3/8 (187.3) 5-1/16 (128.6) 8-1/8 (206.4)
600V 13-3/8 (339.7) 9-3/8 (238.1) 5-5/16 (134.9) 10-1/4 (260.4)
Non-fusible 5-1/16 (128.6)
60 240V 19-3/8 (492.1) 9-3/8 (238.1) 5-1/16 (128.6) 10-1/4 (260.4)
600V 5-5/16 (134.9)
Non-fusible 5-1/16 (128.6)
100 240V 25-3/8 (644.5) 13-1/2 (342.9) 5-5/16 (134.9) 14-1/4 (362)
600V
Non-fusible
200 240V 35-1/8 (892.2) 13-1/2 (342.9) 5-5/16 (134.9) 15-1/4 (387.4)
600V 14-1/2 (368.3)
Non-fusible