Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Fixed and Variable Depth Disconnect Switches > Bulletin 1494V Variable Depth Flange-Mounted Disconnect Switches
Bulletin 1494V Variable Depth Flange-Mounted Disconnect Switches
| Introduction | Standards Compliance and Certifications | Catalog Number Explanation | Product Selection | Accessories | Specifications | Approximate Dimensions |
Fusible and Non-Fusible Disconnect Switch Kits
- Non-fusible disconnect switch kit includes: switch, connecting rod, and metal handle.
- Fusible disconnect switch kit includes: switch, connecting rod, metal handle, trailer fuse block, and fuse clips.
- Optional kit accessories listed on the following pages can be added to the disconnect switch kits to create (1) cat. no.
Example: Cat. No. 1494V-DR233-A-B-F.
| Complete Disconnect Switch Kits for Type 1, 3R, 4, and 12 Metal Enclosures | ||||||||||||||||||||||
| Cont. Current Rating [A] 600V AC 250V DC |
UL and CSA Applications Maximum HP |
AC 1-Phase | DC¬ | IEC Applications Maximum kW (AC23) |
Fuse Clip Rating [A] |
Fuse Class | Switch with Right-Hand Mechanismā¹ |
Switch with Left-Hand Mechanism |
||||||||||||||
| 3-Phase, 60 Hz | 3-Phase, 50 Hz | Fusible Disconnect Switch Kit |
Non-Fusible Disconnect Switch Kit |
Fusible Disconnect Switch Kit |
Non-Fusible Disconnect Switch Kit |
|||||||||||||||||
| 115V | 200… 208V |
230V | 460V | 575V | 115V | 230V | 125V | 250V | 220… 240V |
380… 440V |
500… 600V |
250V | 600V | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |||||
| 30 | 3 | 7.5 | 7.5 | 15 | 20 | 2 | 3 | 3 | 5 | 5.5 | 11 | 15 | 30 | — | H | 1494V-DH233 | 1494V-DN30 | 1494V-DHX233 | 1494V-DNX30 | |||
| 30 | — | R | 1494V-DR233 | 1494V-DRX233 | ||||||||||||||||||
| 30 | — | J | 1494V-DJ233 | 1494V-DJX233 | ||||||||||||||||||
| — | 30 | H | 1494V-DH633 | 1494V-DHX633 | ||||||||||||||||||
| — | 30 | R | 1494V-DR633 | 1494V-DRX633 | ||||||||||||||||||
| — | 30 | J | 1494V-DJ633 | 1494V-DJX633 | ||||||||||||||||||
| 60 | — | H | 1494V-DH236 | 1494V-DHX236 | ||||||||||||||||||
| 60 | — | R | 1494V-DR236 | 1494V-DRX236 | ||||||||||||||||||
| 60 | — | J | 1494V-DJ236 | 1494V-DJX236 | ||||||||||||||||||
| — | 60 | H | 1494V-DH636 | 1494V-DHX636 | ||||||||||||||||||
| — | 60 | R | 1494V-DR636 | 1494V-DRX636 | ||||||||||||||||||
| — | 60 | J | 1494V-DJ636 | 1494V-DJX636 | ||||||||||||||||||
| 60 | 7.5 | 15 | 15 | 30 | 50 | 3 | 10 | 5 | 10 | 11 | 22 | 37 | 30 | — | H | 1494V-DH263 | 1494V-DN60 | 1494V-DHX263 | 1494V-DNX60 | |||
| 30 | — | R | 1494V-DR263 | 1494V-DRX263 | ||||||||||||||||||
| 30 | — | J | 1494V-DJ263 | 1494V-DJX263 | ||||||||||||||||||
| — | 30 | H | 1494V-DH663 | 1494V-DHX663 | ||||||||||||||||||
| — | 30 | R | 1494V-DR663 | 1494V-DRX663 | ||||||||||||||||||
| — | 30 | J | 1494V-DJ663 | 1494V-DJX663 | ||||||||||||||||||
| 60 | — | H | 1494V-DH266 | 1494V-DHX266 | ||||||||||||||||||
| 60 | — | R | 1494V-DR266 | 1494V-DRX266 | ||||||||||||||||||
| 60 | — | J | 1494V-DJ266 | 1494V-DJX266 | ||||||||||||||||||
| — | 60 | H | 1494V-DH666 | 1494V-DHX666 | ||||||||||||||||||
| — | 60 | R | 1494V-DR666 | 1494V-DRX666 | ||||||||||||||||||
| — | 60 | J | 1494V-DJ666 | 1494V-DJX666 | ||||||||||||||||||
| 100 | 100 | H | 1494V-DH661 | 1494V-DHX661 | ||||||||||||||||||
| 100 | 100 | R | 1494V-DR661 | 1494V-DRX661 | ||||||||||||||||||
| 100 | 100 | J | 1494V-DJ661 | 1494V-DJX661 | ||||||||||||||||||
| 100 | — | 25 | 30 | 60 | 75 | — | — | — | 20 | 22 | 45 | 55 | 60 | — | H | 1494V-DH216 | 1494V-DN100 | 1494V-DHX216 | 1494V-DNX100 | |||
| 60 | — | R | 1494V-DR216 | 1494V-DRX216 | ||||||||||||||||||
| 60 | — | J | 1494V-DJ216 | 1494V-DJX216 | ||||||||||||||||||
| — | 60 | H | 1494V-DH616 | 1494V-DHX616 | ||||||||||||||||||
| — | 60 | R | 1494V-DR616 | 1494V-DRX616 | ||||||||||||||||||
| — | 60 | J | 1494V-DJ616 | 1494V-DJX616 | ||||||||||||||||||
| 100 | — | H | 1494V-DH211 | 1494V-DHX211 | ||||||||||||||||||
| 100 | — | R | 1494V-DR211 | 1494V-DRX211 | ||||||||||||||||||
| 100 | — | J | 1494V-DJ211 | 1494V-DJX211 | ||||||||||||||||||
| — | 100 | H | 1494V-DH611 | 1494V-DHX611 | ||||||||||||||||||
| — | 100 | R | 1494V-DR611 | 1494V-DRX611 | ||||||||||||||||||
| — | 100 | J | 1494V-DJ611 | 1494V-DJX611 | ||||||||||||||||||
| — | 200 | J | 1494V-DJ612 | 1494V-DJX612 | ||||||||||||||||||
| 200 | — | 50…60 | 60 | 125 | 150 | — | — | — | 40 | 48 | 90 | 110 | 100 | — | H | 1494V-DH221 | 1494V-DN200 | 1494V-DHX221 | 1494V-DNX200 | |||
| 100 | — | R | 1494V-DR221 | 1494V-DRX221 | ||||||||||||||||||
| 100 | — | J | 1494V-DJ221 | 1494V-DJX221 | ||||||||||||||||||
| — | 100 | H | 1494V-DH621 | 1494V-DHX621 | ||||||||||||||||||
| — | 100 | R | 1494V-DR621 | 1494V-DRX621 | ||||||||||||||||||
| — | 100 | J | 1494V-DJ621 | 1494V-DJX621 | ||||||||||||||||||
| 200 | — | H | 1494V-DH222 | 1494V-DHX222 | ||||||||||||||||||
| 200 | — | R | 1494V-DR222 | 1494V-DRX222 | ||||||||||||||||||
| 200 | — | J | 1494V-DJ222 | 1494V-DJX222 | ||||||||||||||||||
| — | 200 | H | 1494V-DH622 | 1494V-DHX622 | ||||||||||||||||||
| — | 200 | R | 1494V-DR622 | 1494V-DRX622 | ||||||||||||||||||
| — | 200 | J | 1494V-DJ622 | 1494V-DJX622 | ||||||||||||||||||
| — | 400 | J | 1494V-DJ624 | 1494V-DJX624 | ||||||||||||||||||
| 400 | — | 75 | 125 | 250 | 350 | — | — | — | 50 | 90 | 185 | 257 | 200 | — | H | 1494V-DH242 | 1494V-DN400 | 1494V-DHX242 | 1494V-DNX400 | |||
| 200 | — | R | 1494V-DR242 | 1494V-DRX242 | ||||||||||||||||||
| 200 | — | J | 1494V-DJ242 | 1494V-DJX242 | ||||||||||||||||||
| — | 200 | H | 1494V-DH642 | 1494V-DHX642 | ||||||||||||||||||
| — | 200 | R | 1494V-DR642 | 1494V-DRX642 | ||||||||||||||||||
| — | 200 | J | 1494V-DJ642 | 1494V-DJX642 | ||||||||||||||||||
| 400 | — | H | 1494V-DH244 | 1494V-DHX244 | ||||||||||||||||||
| 400 | — | R | 1494V-DR244 | 1494V-DRX244 | ||||||||||||||||||
| 400 | — | J | 1494V-DJ244 | 1494V-DJX244 | ||||||||||||||||||
| — | 400 | H | 1494V-DH644 | 1494V-DHX644 | ||||||||||||||||||
| — | 400 | R | 1494V-DR644 | 1494V-DRX644 | ||||||||||||||||||
| — | 400 | J | 1494V-DJ644 | 1494V-DJX644 | ||||||||||||||||||
| 600 | — | 150 | 200 | 400 | 500 | — | — | — | 50 | 150 | 295 | 375 | 400 | — | H | 1494V-DH204 | 1494V-DN600 | § | 1494V-DH204 | § | 1494V-DN600 | |
| 400 | — | R | 1494V-DR204 | 1494V-DR204 | ||||||||||||||||||
| 400 | — | J | 1494V-DJ204 | 1494V-DJ204 | ||||||||||||||||||
| — | 400 | H | 1494V-DH604 | 1494V-DH604 | ||||||||||||||||||
| — | 400 | R | 1494V-DR604 | 1494V-DR604 | ||||||||||||||||||
| — | 400 | J | 1494V-DJ604 | 1494V-DJ604 | ||||||||||||||||||
| 600 | — | H | 1494V-DH206 | 1494V-DH206 | ||||||||||||||||||
| 600 | — | R | 1494V-DR206 | 1494V-DR206 | ||||||||||||||||||
| 600 | — | J | 1494V-DJ206 | 1494V-DJ206 | ||||||||||||||||||
| — | 600 | H | 1494V-DH606 | 1494V-DH606 | ||||||||||||||||||
| — | 600 | R | 1494V-DR606 | § | 1494V-DR606 | |||||||||||||||||
| — | 600 | J | T | 1494V-DJ606 | T | 1494V-DJ606 | ||||||||||||||||
| ¬ Ratings based on utilizing two poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line. | ||||||||||||||||||||||
| T Class J fuses bolt directly to the switch and trailer fuse block. | ||||||||||||||||||||||
| Class J fuses can be installed on Class H fuse clips. However, when selecting a fuse cover (option code E), select the proper clip (Class H, J, or R) in order to receive the correct size fuse cover. Example: Cat. No. 1494V-DH233-E becomes Cat. No. 1494V-DJ233-E or Cat. No. 1494V-DR233-E. | ||||||||||||||||||||||
| § Switch can be converted in the field for left-hand operation. | ||||||||||||||||||||||
Kit Accessories
| Bulletin 1494V Kit Accessories — Field Installed | |||||||||
| Description | Suffix Code | Switch Size | |||||||
| 30 A | 60 A | 100 A | 200 A | 400 A | 600 A | ||||
| Longer connecting rod (9-1/2…23 in.) | A | A | A | A | A | A | A | ||
| Disconnect handle — Stainless steel | Ø | B | A | A | A | A | A | A | |
| Disconnect handle — Non-metallic | Ø | C | A | A | A | A | — | — | |
| Standard size wire connecting lugs — Line and load side | D | Included | A | A | A | A | A | ||
| Oversize wire connecting lugs — Line and load side | D1 | — | — | — | A | A | — | ||
| Protective fuse cover with door | § | E | A | A | A | A | A | A | |
| Auxiliary contact | 1 N.O. | F | A | A | A | A | A | A | |
| 2 N.O. | FF | A | A | A | A | A | A | ||
| 1 N.C. | G | A | A | A | A | A | A | ||
| 2 N.C. | GG | A | A | A | A | A | A | ||
| Electrical interlock (Early break) |
1 N.O. & 1 N.C. | H | A | A | A | A | A | A | |
| 2 N.O. & 2 N.C. | HH | A | A | A | A | A | A | ||
| Ø Metal disconnect handle provided as standard. For stainless steel handle, select suffix code B. For non-metallic handle, select suffix code C. | |||||||||
| § Select the proper fuse clip (Class J, H, or R) in order to receive the correct size fuse cover. Example: Cat. Nos. 1494V-DH233-E, 1494V-DJ233-E, or 1494V-DR233-E. |
|||||||||
Disconnect Switches
| Continuous Current Rating [A] 600V AC 250V DC |
NEMA, UL, CSA Maximum Rating Hp |
AC 1-Phase | DCT | IEC Utilization Category AC-23 Maximum Rating kW |
Switch with Right-Hand Mechanism |
Switch with Left-Hand Mechanism |
|||||||
| 3-Phase, 60 Hz | 3-Phase, 50 Hz | ||||||||||||
| 200…208V | 230V | 460V | 575V | 115 | 230 | 250 | 220…240V | 380…440V | 500…600V | Cat. No. Switch Only |
Cat. No. Switch Only |
||
| 30 | 7.5 | 7.5 | 15 | 20 | 2 | 3 | 5 | 5.5 | 11 | 15 | 1494V-DS30 | 1494V-DSX30 | |
| 60 | 15 | 15 | 30 | 50 | 3 | 10 | 10 | 11 | 22 | 37 | 1494V-DS60 | 1494V-DSX60 | |
| 100 | 25 | 30 | 60 | 75 | — | — | 20 | 22 | 45 | 55 | 1494V-DS100 | 1494V-DSX100 | |
| 200 | 50…60 | 60 | 125 | 150 | — | — | 40 | 48 | 90 | 110 | 1494V-DS200 | 1494V-DSX200 | |
| 400 | 75 | 125 | 250 | 350 | — | — | 50 | 90 | 185 | 257 | 1494V-DS400 | 1494V-DSX400 | |
| 600 | 150 | 200 | 400 | 500 | — | — | 50 | 150 | 295 | 375 | 1494V-DS600 | § | 1494V-DS600 |
| T Ratings based on utilizing two poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line. | |||||||||||||
| § Switch can be converted in the field for left-hand operation. | |||||||||||||
Connecting Rods
Dimensions are in inches (millimeters). Approximate dimensions are not intended for manufacturing purposes.
| Disconnect Switch Size [A] |
Enclosure Depth§ | Cat. No. | ||
| Minimum | Maximum | |||
| 30, 60, 100, 200 | 6-3/4 (172) | 9-1/8 (232) | 1494V-RA3 | |
| 6-3/4 (172) | 21-5/8 (549) | 1494V-RA4 | ||
| 400, 600 | 9-1/2 (241) | 10 (254) | Ø | 1494V-RB3 |
| 9-1/2 (241) | 23 (584) | Ø | 1494V-RB4 | |
| § Enclosure depth is measured from the top of the flange to the disconnect switch mounting surface (mm). | ||||
| Ø Kit includes two connecting rods. | ||||
Operating Handles
| Handle Type |
Description | Mounting | Disconnect Switch Size [A] |
Cat. No. |
| Type 1, 3R, 4, 4X, 12 | Nonmetallic | Right or Left Flange | 30, 60, 100, 200 | 1494F-P1 |
| Type 1, 3R, 4, 12 | Painted Metal | Right or Left Flange | 30, 60, 100, 200 | 1494F-M1 |
| 400, 600 | 1494F-M2 | |||
| Type 4, 4X | Stainless Steel | Right or Left Flange | 30, 60, 100, 200 | 1494F-S1 |
| 400, 600 | 1494F-S2 | |||
Trailer Fuse Block Kits
For Class H, J, or R fuses, select the proper fuse clip kit from the table below.
| Disconnect Switch Size [A] | Cat. No. | |
| 30 | 1494V-FS30 | |
| 60 | 1494V-FS60 | |
| 100 | 1494V-FS100 | |
| 200 | v | 1494V-FS200 |
| 400 | 1494V-FS400 | |
| 600 — 600 A Class J fuse | 1494-FS600 | |
| 600 — 400 A Class H, J, and R fuse | 1494V-FSV400 | |
| 600 — 600 A Class H fuse | ª | 1491-N621 |
| 600 — 600 A Class R fuse | ª | 1491-R621 |
| v When installing 400 A Class J fuses, use adapter kit (Cat. No. 1401-N171). | ||
| ª Separately mounted fuse blocks (3 required). | ||
Fuse Clip Kits
- Includes six clips and mounting hardware
| Fuse Class | Fuse Clip Rating [A] | For Use With | Cat. No. | |
| 250V | 600V | |||
| H, J | 30 | — | 1494C, 1494F, 1494G, 1494M, 1494V Disconnect Switches |
1401-N41 |
| 60 | 30 | 1401-N42 | ||
| — | 60 | 1401-N43 | ||
| 100 | 100 | 1401-N44 | ||
| 200 | 200 | 1401-N45 | ||
| 400 | 400 | 1401-N46 | ||
| 600 | 600 | 11 | ||
| J | 30 | 30 | 1401-N42 | |
| 60 | 60 | 1401-N43 | ||
| 100 | 100 | 1401-N44 | ||
| 200 | 200 | 1401-N45 | ||
| 400 | 400 | 1401-N46 | ||
| 600 | 600 | ª | ||
| R | 30 | — | 1401-N50 | |
| 60 | 30 | 1401-N51 | ||
| — | 60 | 1401-N52 | ||
| 100 | 100 | 1401-N53 | ||
| 200 | 200 | 1401-N54 | ||
| 400 | 400 | 1401-N55 | ||
| 600 | 600 | 11 | ||
| ª Fuse clips not required: fuse bolts directly to terminal. | ||||