Fixed and Variable Depth Disconnect Switches

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Fixed and Variable Depth Disconnect Switches > Bulletin 1494F Fixed-Depth Flange-Mounted Disconnect Switches

Bulletin 1494F Fixed-Depth Flange-Mounted Disconnect Switches

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Accessories

Click to enlarge - 1494-2_18-1 Description For Use With Cat. No.
Auxiliary Contacts
1 N.O. Contact
1494C, 1494F, 1494V, and 1494M (30…400 A), 1494G (30…400 A) Disconnect Switches

1494D, 1494V¬  (125…400 A Frame) Circuit Breakers

1495-N8
1 N.C. Contact 1495-N9
Click to enlarge - 1494-2_18-4 Click to enlarge - 1494-2_18-5 Auxiliary Contacts 1 N.O. Contact 1494C, 1494G, and 1494V Disconnect Switches
600 A
595-A
Cat. No. 595-A Cat. No. 595-B 1 N.C. Contact
595-B
Click to enlarge - 1494-2_18-6 Auxiliary Contact Adapter Kit For Disconnect Switches 600 A only T  595-N1
Cat. No. 595-N1
Click to enlarge - 1495_N24_GS Auxiliary Contact Adapter Kit For Disconnect Switches with Left-Hand Mechanism 30…100 A Disconnect Switch 1494V Disconnect Switch with Left-Hand Mechanism,
30…100 A
T  1495-N24
Cat. No. 1495-N24 Auxiliary Contact Adapter Kit For Disconnect Switches with Left-Hand Mechanism 200 A Disconnect Switch 1494V Disconnect Switch with Left-Hand Mechanism,
200…400 A
T  1495-N25
Click to enlarge - 1494-2_18-2 Click to enlarge - 1494-2_18-3 Auxiliary Contact Adapter Kit For Circuit Breakers 125 A and 150 A Frame Allen-Bradley, Cutler-Hammer 1494D, 1494V Circuit Breakers T  1495-N21
250 A, 400 A Frame Allen-Bradley, Cutler-Hammer 1494V Circuit Breaker T  1495-N23
250 A Frame Allen-Bradley, Cutler-Hammer 1494D Circuit Breaker T  1495-N22
400 A Frame Allen-Bradley, Cutler-Hammer 1494D Circuit Breaker T  1495-N16
Cat. No.
1495-N21
Cat. No.
1495-N23
600 A, 800 A, 1200 A Frame
Cutler-Hammer
1494D Circuit Breaker T  1495-N13
Click to enlarge - 1494-2_18-7 Click to enlarge - 1494-2_18-8 Auxiliary Contacts 1 N.O. Contact 1494R Disconnect Switch 30 A, 60 A 895-A1
1 N.C. Contact 895-B1
1 N.O. and 1 N.C. Contact 895-C1
Auxiliary Contact Adapter Kit for 1 contact 895-M11
Cat. No. 895-A1 Cat. No. 895-M11 Auxiliary Contact Adapter Kit for 2 contacts 895-M12
Click to enlarge - 1494-2_18-9 Click to enlarge - 1494-2_18-10 Auxiliary Contacts 1 N.O. Contact 1494R Disconnect Switch
100 A, 200 A
895-A2
1 N.C. Contact 895-B2
1 N.O. and 1 N.C. Contact 895-C2
Auxiliary Contact Adapter Kit for 1 contact 895-M21
Cat. No. 895-A2 Cat. No. 895-M21 Auxiliary Contact Adapter Kit for 2 contacts 895-M22
Click to enlarge - 1495-N34_GS Electrical Interlocks 1 N.O. and 1 N.C. — early break 1494C, 1494G & 1494V Disconnect Switches with Left-/Right-Hand Mechanism,
30…100 & 600 A
‡  1495-N34
2 N.O. and 2 N.C. — early break ‡  1495-N35
1 N.O. and 1 N.C. — early break 1494C, 1494G, & 1494V Disconnect Switch with Right-Hand Mechanism,
200 A, 400 A
1495-N43
2 N.O. and 2 N.C. — early break 1495-N44
1 N.O. and 1 N.C. — early break 1494C and 1494V Disconnect Switch with Left-Hand Mechanism, 30…100 A 1495-N37
Cat. No. 1495-N34 2 N.O. and 2 N.C. — early break 1495-N38
Click to enlarge - 1495-N35_GS 1 N.O. and 1 N.C. — early break 1494V Disconnect Switch with Left-Hand Mechanism, 200 A 1495-N39
2 N.O. and 2 N.C. — early break 1495-N40
1 N.O. and 1 N.C. — early break 1494V Disconnect Switch with Left-Hand Mechanism, 400 A 1495-N41
2 N.O. and 2 N.C. — early break 1495-N42
10 A DPDT – early break (for 30 A, Type 1 & 3R only) 1494H Safety Switch 1495-N77
15 A DPDT – early break (for 30 A, Type 12)
15 A DPDT – early break (for all 60 A, 100 A, & 200 A, Type 1, 3R, and 12)
1495-N78
Cat. No. 1495-N35 Electrical Interlock Adapter Kit 600 A Disconnect Switch 1494G Disconnect Switch 1495-N36
  
¬ Requires an adapter kit on new installations.
T One adapter kit enables up to two auxiliary contacts to be installed.
‡ Additional adapter kit (Cat. No. 1495-N36) required for installation on 600 A switch.

Click to enlarge - 1494-2_19-1 Description For Use With Cat. No.
Lug Connectors (3 per package) 1494C, 1494F, 1494G, and 1494V Disconnect Switches  
Disconnect Size [A] Wire Size
30 #14…8 AWG Wire ¬ 
60 #14…4 AWG Wire §  1494R-N1
100 #8…1/0 AWG Wire §  1494R-N2
200 #6…4/0 AWG Wire §  1494R-N3
#6…250 MCM Wire (oversized) §  199-LF1
400 (2) of #1/0…250 MCM Wire §  1494R-N14
#4 AWG…500 MCM Wire (oversized) §  1494R-N15
600 (2) of #1/0…350 MCM Wire §  1494R-N10
Cat. No. 1494R-N3 (2) of #1/0…350 MCM Wire 1491-N621 or 1491-R621 600 A fuse blocks §  1494R-N11
Click to enlarge - 1494-2_19-2 Ground Connectors 1494C, 1494F, 1494G, and 1494V Disconnect Switches
599-GR1
Ground Lug Kits 30…100 A
200…400 A 599-GR2
600 A 599-GR3
30, 60 A 1494H & 1494HL Safety Switches 599-GR4
Cat. No. 599-GR1 100, 200 A 599-GR5
  Neutral Kits
30 A @ 250/600V AC Fusible (Type 1 & 3R)
1494H Safety Switches
599-NK1
30 A @ 250/600V AC Non-Fusible (Type 1 & 3R) 599-NK2
30 A @ 250/600V AC Fusible & Non-Fusible (Type 12) 599-NK3
60 A @ 250/600V AC Fusible & Non-Fusible (Type 1 & 3R) 599-NK4
60 A @ 250/600V AC Fusible (Type 12) 599-NK5
60 A @ 250/600V AC Non-Fusible (Type 12) 599-NK6
100 A @ 250/600V AC Fusible (Type 1 & 3R) 599-NK7
100 A @ 250/600V AC Non-Fusible (Type 1, 3R, and 12) 599-NK8
100 A @ 250/600V AC Fusible (Type 12) 599-NK9
200 A @ 250/600V AC Fusible & Non-Fusible (Type 1 & 3R) 599-NK10
200 A @ 250/600V AC Fusible & Non-Fusible (Type 12) 599-NK11
Click to enlarge - 1494-2_19-3 Fuse Clips (6 per package) 1494C, 1494F, 1494G, and 1494V Disconnect Switches

1491 Fuse Blocks



1401-N41
Fuse Class Fuse Clip Rating [A]
250V 600V
H, J 30
60 30 1401-N42
60 1401-N43
100 100 1401-N44
200 200 1401-N45
400 400 1401-N46
J 600 600 T 
R 30 1401-N50
60 30 1401-N51
60 1401-N52
100 100 1401-N53
200 200 1401-N54
400 400 1401-N55
H, R 600 600 ‡ 
  Class R Fuse Clip Kits
30 A @ 250V AC (Type 1, 3R, 12)
1494H Safety Switches
1401-N70
30 A @ 600V AC (Type 1, 3R) 1401-N71
30 A @ 600V AC (Type 12) 1401-N72
60 A @ 250V AC (Type 1, 3R, 12) 1401-N73
60 A @ 600V AC (Type 1, 3R, and 12) 1401-N74
100 A @ 250/600V AC (Type 1 & 3R) 1401-N75
100 A @ 250/600V AC (Type 12) 1401-N76
200 A @ 250/600V AC (Type 1, 3R, and 12) 1401-N77
  
¬ All terminals of the 30 A switches are furnished with self-lifting pressure plate connectors as standard.
T Fuse clips not required; fuse bolts directly to terminal. ‡ Included with Bulletin 1491 separate mounted fuse blocks.
§ Each kit contains (3) lugs. § Each kits contains (2) lugs.

Click to enlarge - 1495_FuseCover_GS Protective Fuse Covers (for use with Bul. 1494C, 1494G, and 1494V disconnect switches)
Switch Rating [A] Fuse Class Fuse Clip Rating [A] Cat. No.
250V 600V
30
30
60
30
60
60
100
Nonfusible
H, R
H, R
J
J
Nonfusible
Nonfusible

30
60
30
60




30
60

1495-N64
30
60
100
H, R
H, R
J


100
30
60
100
1495-N65
100 H, R 100 100 1495-N66
200
200
Nonfusible
H, J, R

200

200
Ø  1495-N67
200
200
Nonfusible
H, J, R

200

200
z  1495-N62
400
400
Nonfusible
H, J, R

400

400
Ø  1495-N68
400
400
Nonfusible
H, J, R

400

400
z  1495-N63
600
600
Nonfusible
J

600

600
Ø  1495-N61
  Protective Line Covers (for use with Bul. 1494C, 1494G, and 1494V disconnect switches)
30…100 1495-N80
200 1495-N81
400 1495-N82
600 1495-N83
  
Ø Switch with right-hand mechanism.
z Switch with left-hand mechanism.

Description For Use With Cat. No.
Click to enlarge - 1494-2_21-1 Defeater Bracket Extension Kit
For use with operating handles that do not align properly with the door catch or door hardware on enclosures with a rolled lip flange construction.
All 1494F and 1494V Handles (except 1494V-R1 and 1494V-R2)
For 400…600 A switches, defeater bracket is included with connecting rod kits.
1494V-H12
Click to enlarge - 1494-2_21-2 Alternate Mounting Kits
For use where the flange material thickness is greater than 3/16 in. (4.8 mm).
Operating Handles 1494V-H1 or 1494V-H11 1494V-H3
Operating Handles 1494V-H2 1494V-H6
Click to enlarge - 1494-2_21-3 Channel Support Kits
For use to prevent flexing of the operating handle mounting surface. This is especially useful when the operating handle is mounted on a channel in a multi-door enclosure.
30…200 A Switches
Applies only to Operating Handle Cat. Nos. 1494F-P1, M1, and S1.
1494V-H15
  Conduit Hubs (for Type 3R enclosures)¬ 
19.05 mm (3/4 in.) hub
1494H Safety Switches
1495-N71
25.4 mm (1 in.) hub 1495-N72
31.75 mm (1-1/4 in.) hub 1495-N73
38.1 mm (1-1/2 in.) hub 1495-N74
50.8 mm (2 in.) hub 1495-N75
63.5 mm (2-1/2 in.) hub 1495-N76
Click to enlarge - 1494-2_21-4 Conduit Connectors

Metallic Conduit Connectors


1 in. (25.4 mm)
30 A 1494G Disconnect Switches 1232-N11
1-1/4 in. (31.75 mm) 60 A 1232-N12
1-1/2 in. (38.1 mm) 100 A 1232-N13
2-1/2 in. (63.5 mm) 200 A 1232-N14
3 in. (76.2 mm) 400…600 A 1232-N15
Click to enlarge - 1494-2_21-5 Non-Metallic Conduit Connectors

1/2 in. (12.7 mm)
30 A 1490-N1
3/4 in. (19 mm) 30 A 1490-N9
1 in. (25.4 mm) 30 A 1490-N10
1-1/4 in. (31.75 mm) 60 A 1490-N11
1-1/2 in. (38.1 mm) 100 A 1490-N5
2 in. (50.8 mm) 200 A 1490-N6
2-1/2 in. (63.5 mm) 200 A 1490-N7
3 in. (76.2 mm) 400…600 A 1490-N8
Click to enlarge - 1494-2_21-6 Grounding Adapters

#14…10 AWG, 1/2 in. (12.7 mm)
30 A 1490-N19
#14…8 AWG, 3/4 in. (19 mm) 30 A 1490-N20
#14…8 AWG, 1 in. (24.5 mm) 30 A 1490-N21
#14…4 AWG, 1-1/4 in. (31.8 mm) 60 A 1490-N22
#8…1/0 AWG, 1-1/2 in. (38.1 mm) 100 A 1490-N23
#8…1/0 AWG, 2 in. (50.8 mm) 200 A 1490-N24
#6…2/0 AWG, 2-1/2 in. (63.5 mm) 200 A 1490-N25
#6…4/0 AWG, 3 in. (76.2 mm) 400…600 A 1490-N26
  
¬ Packaged in quantities of 10.

Click to enlarge - 1494-2_20-1a Click to enlarge - 1494-2_20-2 Decription For Use With Cat. No.§ 
Type 12 Door Hardware Kit Includes:
handle, cam, defeater actuator lever, rollers, and shims

Enclosure Height less than 40 in. (1016 mm)

Top and Side (Right Hand)
1494C,
All 1494V
1494V-L1¬ 
Top and Side (Left Hand) 1494V-LL1¬ 
Enclosure Height 40…60 in. (1016…1524 mm)

Top and Side (Right Hand)
Bottom
1494V-L1¬ 
and 1494V-L2
Cat. No. 1494V-L1 Top and Side (Left Hand)
Bottom
1494V-LL1¬ 
and 1494V-L2
Click to enlarge - 1494-2_20-1b Enclosure Height greater than 60 in. (1524 mm)

Top, Side and Bottom (Right Hand)
1494V-L3¬ 
Cat. No. 1494V-L2 Cat. No. 1494V-L3 Top, Side and Bottom (Left Hand) 1494V-LL3¬ 
Click to enlarge - 1494-2_20-3 Type 12 Door Hardware Kit Includes:
Handle, cam, defeater actuator lever, rollers, and shims

Enclosure Height less than 30 in. (762 mm)

Top and Side (Right Hand)
1494F
1494M,
1494D
1494F-L1¬ 
Top and Side (Left Hand) 1494F-LL1¬ 
Top and Bottom (Right Hand) 1494F-L2¬ 
Top and Bottom (Left Hand) 1494F-LL2¬ 
Enclosure Height 30…48 in. (762…1219 mm)

Top and Bottom (Right Hand)
Side
1494F-L2¬ 
and 1494F-L3
Top and Bottom (Left Hand)
Side
1494F-LL2
and 1494F-L3¬ 
Enclosure Height greater than 48 in. (1219 mm)

Top, Side, and Bottom (Right Hand)
1494F-L4T 
Cat. No. 1494F-L2 and 1494F-L3 Top, Side, and Bottom (Left Hand) 1494F-LL4T 
Click to enlarge - 1494-2_20-4 Master Door Interlock Kits
Interlock kits are designed to provide interlocking between the master and auxiliary doors of the same enclosure and for use with Cat. Nos. 1494F-L4 and 1494F-LL4 hardware kits or Cat. Nos. 1494V-L3 and 1494V-LL3 hardware kits. Specify one master door kit and as many auxiliary door kits as necessary (9 maximum). Connecting bars must be supplied by user.
1494C,
1494F,
1494M,
1494D,
1494V
1494F-N20‡ 
Cat. No. 1494F-N20 Auxiliary Door Interlock Kit 1494F-N21
  
¬ Door hardware kit does not include rectangular connecting bars (1/4 x 1/2 in.). To be provided by customer.
T Door hardware kit does not include rectangular connecting bars (1/4 x 5/8 in.). To be provided by customer.
‡ Master door interlock kit does not include rectangular connecting bars (3/8 x 3/8 in.). To be provided by customer.
§ If the Rockwell Automation door hardware kits are to be installed in a commercially available enclosure, consult the enclosure manufacturer's application data for proper kit selection.