Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Fixed and Variable Depth Disconnect Switches > Bulletin 1494F Fixed-Depth Flange-Mounted Disconnect Switches
Bulletin 1494F Fixed-Depth Flange-Mounted Disconnect Switches
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
Bulletin 1494C, 1494F, 1494G, 1494M, 1494R, 1494V Disconnect Switches
| Disconnect Switch Electrical Ratings | ||||||||
| Switch Size | 30 A | 60 A | 100 A | 200 A | 400 A | 600 A | ||
| Rated insulation voltage Ui (UL) IEC | (600) 660V | |||||||
| Ratings UL/CSA/NEMA |
HP | 230V/60 Hz 460V/60 Hz 575V/60 Hz |
7.5 15 20 |
15 30 50 |
30 60 75 |
60 125 150 |
125 250 350 |
200 400 500 |
| 250V DC | 5 | 10 | 20 | 40 | 50 | 50 | ||
| Continuous Current |
600V AC 250V DC |
30 | 60 | 100 | 200 | 400 | 600 | |
| Auxiliary Contact Electical Ratings | ||||||||
| NEMA/EEMAC | B600, P300 | |||||||
| IEC Ratings | Ui 660V | Ith 10 A | ||||||
ACII Ux |
12…120V 220…240V 380…400V 500…600V |
Ie |
6 A 3 A 1.5 A 1.2 A |
|||||
| Mechanical | ||||||||
| Degree of protection | Operating handles | Molded Type 1, 3R, 4, 4X, 12, Painted Type 1, 3R, 4, 12 Stainless Steel Type 4, 4X |
||||||
| Mechanical life (Typical) | 20 000 operations (30…200 A) 10 000 operations (400…600 A) | |||||||
| Switching frequency (operations/hr) | 30, 60, 100, and 200 A sizes — 300 maximum400 and 600 A size — 240 Maximum | |||||||
| Environmental | ||||||||
| Temperature | Operating | -35…+40 °C (-31…+104 °F) | ||||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||||
| Altitude (per IEC 947-5) | 2000m per IEC 337-1 | |||||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C and 50% at 40 °C | |||||||
| Design Specification/Test Requirements | ||||||||
| Dielectric strength | 2200V for 1 minute | |||||||
| Electrical life | 6000 operations at rated current | |||||||
| Short Circuit Withstand Capability | 10 000 A: unfused 10 000 A: with Class H fuses 200 000 A: with Class J or Class R fuses | |||||||
| Construction | ||||||||
| Switch body material | Phenolic | |||||||
| Contact material | Copper, tin-plated | |||||||
| Terminals | 30 A 60 A 100 A 200 A 400 A 600 A |
#10 - 32 screw and self-lifting pressure plate 1/4 in. - 28 screw-lug, copper 5/16 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper 1/2 in. - 13 screw-lug, copper |
||||||
| All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire. | ||||||||
| Conductor Size (mm2) | 30 A 60 A 100 A 200 A 400 A 600 A |
#14…8 AWG (1.5…10 mm2) #14…4 AWG (2.5…16 mm2) #8…1/0 AWG (10…50 mm2) #6…4/0 AWG (16…95 mm2) 2 of #1/0 AWG…250 MCM (2 per lug) 2 of 185 mm2…250 MCM 2 of #1/0 AWG…350 MCM (2 per lug) 2 of 185 mm2…350 MCM |
||||||
| Recommended Torque | 30 A 60 A 100 A 200 A 400 A 600 A |
Conductor into Lug 20 lbin 45 lbin 150 lbin 275 lbin 325 lbin 325 lbin |
Lug to Terminal 20 lbin 50 lbin 90 lbin 175 lbin 275 lbin 275 lbin |
|||||
| Mechanisms | Zinc-plated steel, RoHS Compliant finish | |||||||
Bulletin 1494H Disconnect Switches
| Disconnect Switch Electrical Ratings | ||||||
| Switch Size | 30 A | 60 A | 100 A | 200 A | ||
| Rated insulation voltage Ui (UL) IEC | (600) 660V | |||||
| Ratings UL/CSA/NEMA |
Hp | 230V/60 Hz 460V/60 Hz 575V/60 Hz |
10 20 30 |
20 50 60 |
40 75 100 |
60 125 150 |
| 250V DC | 5 | 10 | 20 | 40 | ||
| Continuous Current |
600V AC 250V DC |
30 | 60 | 100 | 200 | |
| Auxiliary Contact Electical Ratings | ||||||
| Continuous Current | 10 A | 15 A | ||||
| Pole Configuration | DPDT | DPDT | ||||
| Mechanical | ||||||
| Degree of protection | Operating handles | Painted Type 1, 3R, 12 | ||||
| Mechanical life (Typical) | 10 000 operations | |||||
| Switching frequency (operations/hr) | 300 maximum | |||||
| Environmental | ||||||
| Temperature | Operating | -35…+40 °C (-31…+104 °F) | ||||
| Storage | -40…+65 °C (-40…+149 °F) | |||||
| Altitude (per IEC 947-5) | 2000m per IEC 337-1 | |||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C and 50% at 40 °C | |||||
| Design Specification/Test Requirements | ||||||
| Dielectric strength | 2200V for 1 minute | |||||
| Electrical life | 6000 operations at rated current | |||||
| Short Circuit Withstand Capability | 10 000 A: unfused 10 000 A: with Class H fuses 200 000 A: with Class J or Class R fuses (30…100 A) 100 000 A: with Class J or Class R fuses (200 A) |
|||||
| Construction | ||||||
| Switch body material | Phenolic | |||||
| Contact material | Copper, tin-plated | |||||
| Terminals | 30 A 60 A 100 A 200 A |
#10 - 32 screw and self-lifting pressure plate 1/4 in. - 28 screw-lug, copper 5/16 in. - 24 screw-lug, copper 3/8 in. - 24 screw-lug, copper |
||||
| All wire rated 75 °C (167 °F) or higher must be sized per the local Electric Code for 75 °C (167 °F) wire. | ||||||
| Conductor Size (mm2) | 30 A 60 A 100 A 200 A |
#14…8 AWG #12…2 AWG #10…1/0 AWG #2…250 MCM AWG |
||||
| Recommended Torque | 30 A 60 A 100 A 200 A |
Conductor into Lug 36…40 lbin 35…45 lbin 35…50 lbin 275 lbin |
||||
| Mechanisms | Zinc-plated steel, Bronze chromate finish | |||||
Bulletin 1494D, 1494V Circuit Breakers
| Electrical Ratings | ||||||||
| Frame Size | 125 A | 150 A | 250 A | 400 A | 600 A | 800 A | 1200 A | |
| Auxiliary Contacts | ||||||||
| 1494V, 1494D | ||||||||
| NEMA/EEMAC | B600, P300 | |||||||
| IEC Ratings | ACII Ux |
12…120V 220…240V 380…400V 500…600V |
Ie |
6 A 3 A 1.5 A 1.2 A |
||||
| Maximum Number of Auxiliary Contacts | 2 | |||||||
| Mechanical Data | ||||||||
| Mechanical Life (Typical) | 10 000 | |||||||
| Construction | ||||||||
| Mechanisms | Zinc-plated steel | |||||||
| Environmental Data | ||||||||
| Ambient Temperature¬ | Operating | 20…+40 °C (4…+104 °F) | ||||||
| Storage | 40…+65 °C (40…+149 °F) | |||||||
| Altitude (per IEC 947-5) | 2000 m per IEC 337-1 | |||||||
| Relative Humidity (per IEC 947-3) | 90% @ 20 °C (68 °F), 50% @ 40 °C (104 °F) | |||||||
| ¬ Refer to circuit breaker specifications for other limitations. | ||||||||
Bulletin 1491 Fuse Blocks
| Electrical | ||||||
| UL Fuse Type | Class H | Class J | Class R | Class C | Class CC | |
| CSA Fuse Type | HRCI-H | HRCI-J | HRCI-R | HRCI-C | HRCI-MISC | |
| Maximum Fuse Cartridge Size | 30…600 A | 30…600 A | 30…600 A | 30…600 A | 30 A | |
| Maximum Voltage | AC | 600V | 600V | 600V | 600V | 600V |
| DC | 250V | 250V | 250V | 250V | 250V | |
| Thermal Current Rating | 30…600 A | 30…600 A | 30…600 A | 30…600 A | 30 A | |
| Maximum Short Circuit Prospective Fault Current | 10 kA | 200 kA | 200 kA | 100 kA | 200 kA | |
| Construction | ||||||
| Fuse Clips | Tin-plated copper | |||||
| Terminals | Tin-plated copper | |||||
| Fuse Block Base | Phenolic or Porcelain | |||||
| Environmental | ||||||
| Ambient Temperature | Open | 20…+55 °C (4…+131 °F) | ||||
| Enclosed | 20…+40 °C (4…+104 °F) | |||||
| Storage | 40…+65 °C (40…+149 °F) | |||||
| Altitude (per IEC 947-5) | 2000 m | |||||
| Relative Humidity (per IEC 947-3) | 90% at 20 °C (68 °F) and 50% at 40 °C (104 °F) | |||||