Bulletin 1494R Variable-Depth Door-Mounted Rotary Disconnect Switches
|
Bulletin 1494R — Variable-Depth Door-Mounted Rotary
Disconnect Switches
Industrial rated disconnect switch for use in non-flanged constructed enclosures with depths up to 23 inches.
- 3-pole, 600V AC rating
- 30, 60, 100, and 200 A ratings
- Available in a non-fusible version
- Can accommodate Class H, J, K, and R fuses
- Fuse blocks are separately mounted
- Can be used with enclosure Types 1 and 12
- Lockable handle
Standards Compliance and Certifications
- UR recognized (File No. E47418) per UL 98
- CSA Certified (File No. LR1324) per
CSA C22.2 No. 4)
Product Selection
Non-Fusible Disconnect Switch Kits
Includes switch, operating handle, AND connecting rod (line and load lug connectors located in the Accessories section on Accessories.
| Complete Non-Fused Disconnect Switch Kits for Type 1 and Type 12 Enclosures | |||||||||||
| Continuous Current Rating [A] 600V AC 125V DC |
UL and CSA Applications Maximum Hp |
AC 1-Phase | DC¬ | IEC Applications Maximum kW (AC23) |
Open Type without Enclosure |
||||||
| 3-Phase, 60 Hz | 3-Phase, 50 Hz | ||||||||||
| 200…208V | 230V | 460V | 575V | 115V | 230V | 125V | 220…240V | 380…440V | 500…600V | Cat. No.T | |
| 30 | 7.5 | 7.5 | 15 | 20 | 2 | 3 | 3 | 5.8 | 11 | 15 | 1494R-N30 |
| 60 | 15 | 15 | 30 | 40 | 3 | 10 | 5 | 11 | 22 | 37 | 1494R-N60 |
| 100 | 30 | 30 | 60 | 75 | — | — | 10 | 22 | 45 | 55 | 1494R-N100 |
| 200 | 60 | 60 | 125 | 150 | — | — | — | 45 | 90 | 110 | 1494R-N200 |
Longer Shafts
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
The standard lengths for shafts furnished with the disconnect switches are 9-1/2 (241.3) on the 30 and 60 A and 11 (279.4) on the 100 and 200 A. Longer shafts are available and must be ordered separately. Approximate dimensions are not intended for manufacturing purposes.
| Shaft Kits | ||
| Disconnect Switch Size [A] | Length | Cat. No. |
| 30 60 |
18 (457.2) | 1494R-N4 |
| 100 | 24 (609.6) | 1494R-N5 |
| 200 | 24 (609.6) | 1494R-N6 |
| ¬ Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line. | ||
| T Can be converted to a fusible disconnect switch by adding separately mounted Bulletin 1491 fuse blocks located on Fuse Blocks. | ||
Approximate Dimensions
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1494R Disconnect Switches
|
|
| NEMA Size [A] |
A | B | C | D | E | F | G | H | J | K | L | M | N | P | Q | R | |||
| Standard Shaft | Long Shaft | ||||||||||||||||||
| Min. | Max. | Min. | Max. | ||||||||||||||||
| 30 | 3-31/32 (100.8) |
4-13/16 (122.2) |
3-9/16 (90.5) |
1-1/8 (28.6) |
3-1/8 (79.4) |
3-1/8 (79.4) |
27/64 (10.7) |
1 (25.4) |
4-3/8 (111.1) |
10-7/8 (276.2) |
4-3/8 (111.1) |
19-3/8 (492.1) |
¬ | T | 1 (25.4) |
3/16 (4.8) |
5 (127.0) |
2-13/16 (71.4) |
2-13/16 (71.4) |
| 60 | 4-21/32 (118.3) |
5-1/4 (133.4) |
3-9/16 (90.5) |
1-1/16 (27.0) |
3-13/16 (96.8) |
3-1/8 (79.4) |
27/64 (10.7) |
1 (25.4) |
4-1/2 (114.3) |
10-7/8 (276.2) |
4-1/2 (114.3) |
19-3/8 (492.1) |
¬ | T | 1 (25.4) |
3/16 (4.8) |
5 (127.0) |
2-13/16 (71.4) |
2-13/16 (71.4) |
| 100 | 6-7/16 (163.5) |
7-3/16 (187.3) |
5-7/16 (138.1) |
15/16 (23.8) |
5 (127.0) |
5 (127.0) |
23/32 (18.3) |
1-1/2 (38.1) |
6-1/4 (158.8) |
12-7/8 (327.0) |
6-1/4 (158.8) |
25-7/8 (657.2) |
| § | 1-3/8 (34.9) |
1/4 (6.4) |
7-11/16 (195.3) |
4-3/16 (106.4) |
3 (76.2) |
| 200 | 7-1/4 (184.2) |
9-1/2 (241.3) |
6-1/2 (165.1) |
1-7/16 (36.5) |
5-3/4 (146.1) |
5-3/4 (146.1) |
3/4 (19.1) |
1-23/32 (43.7) |
7-7/16 (188.9) |
12-7/8 (327.0) |
7-7/16 (188.9) |
25-7/8 (657.2) |
| § | 1-3/8 (34.9) |
1/4 (6.4) |
7-11/16 (195.3) |
4-3/16 (106.4) |
3 (76.2) |
| ¬ The adjusted coupling position is determined by measuring the cabinet depth and subtracting 9/16 in. | |||||||||||||||||||
| T The shaft length is determined by measuring the cabinet depth (dimension J) and subtracting 1-3/8 in. | |||||||||||||||||||
| The adjusted coupling position is determined by measuring the cabinet depth and subtracting 15/16 in. | |||||||||||||||||||
| § The shaft length is determined by measuring the cabinet depth (dimension J) and subtracting 1-7/8 in. | |||||||||||||||||||