Fixed and Variable Depth Disconnect Switches

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Fixed and Variable Depth Disconnect Switches > Bulletin 1494R Variable-Depth Door-Mounted Rotary Disconnect Switches

Bulletin 1494R Variable-Depth Door-Mounted Rotary Disconnect Switches

Introduction Standards Compliance and Certifications Product Selection Accessories Approximate Dimensions
Product Selection

Build a Catalog Number


Non-Fusible Disconnect Switch Kits

Includes switch, operating handle, AND connecting rod (line and load lug connectors located in the Accessories section on Accessories.

Complete Non-Fused Disconnect Switch Kits for Type 1 and Type 12 Enclosures
Continuous
Current
Rating [A]
600V AC
125V DC
UL and CSA Applications
Maximum Hp
AC 1-Phase DC★  IEC Applications
Maximum kW (AC23)
Open Type
without
Enclosure
3-Phase, 60 Hz 3-Phase, 50 Hz
200…208V 230V 460V 575V 115V 230V 125V 220…240V 380…440V 500…600V Cat. No.‡ 
30 7.5 7.5 15 20 2 3 3 5.8 11 15 1494R-N30
60 15 15 30 40 3 10 5 11 22 37 1494R-N60
100 30 30 60 75 10 22 45 55 1494R-N100
200 60 60 125 150 45 90 110 1494R-N200
  

Longer Shafts

Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.


The standard lengths for shafts furnished with the disconnect switches are 9-1/2 (241.3) on the 30 and 60 A and 11 (279.4) on the 100 and 200 A. Longer shafts are available and must be ordered separately. Approximate dimensions are not intended for manufacturing purposes.

Shaft Kits
Disconnect Switch Size [A] Length Cat. No.
30
60
18 (457.2) 1494R-N4
100 24 (609.6) 1494R-N5
200 24 (609.6) 1494R-N6
  
★ Ratings based on utilizing 2 poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
‡ Can be converted to a fusible disconnect switch by adding separately mounted Bulletin 1491 fuse blocks located on Fuse Blocks.