Disconnect Switches

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Cable-Operated Disconnect Switches

Cable-Operated Disconnect Switches

Introduction Standards Compliance and Certifications Catalog Number Explanation Product Selection Accessories Specifications Approximate Dimensions
Product Selection

Fusible and Non-Fusible Disconnect Switch Kits


Complete Disconnect Switch Kits for Type 1, 3R, 4, and 12 Metal Enclosures
Cont.
Current
Rating
[A]
600V AC
250V DC
UL and CSA
Applications
Maximum HP
AC 1-Phase DCT  IEC Applications
Maximum kW
(AC23)
Fuse Clip Rating
[A]
Fuse Class Switch with
Right-Hand Mechanism
Switch with
Left-Hand Mechanism
3-Phase, 60 Hz 3-Phase, 50 Hz Fusible
Disconnect
Switch Kit
Non-Fusible
Disconnect
Switch Kit
Fusible
Disconnect
Switch Kit
Non-Fusible
Disconnect
Switch Kit
115V 200…
208V
230V 460V 575V 115V 230V 125V 250V 220…
240V
380…
440V
500…
600V
250V 600V Cat. No.¬  Cat. No.¬  Cat. No.¬  Cat. No.¬ 
30 3 7.5 7.5 15 20 2 3 3 5 5.5 11 15 30 H ‡  1494C-DH233 1494C-DN30 ‡  1494C-DHX233 1494C-DNX30
30 R 1494C-DR233 1494C-DRX233
30 J 1494C-DJ233 1494C-DJX233
30 H ‡  1494C-DH633 ‡  1494C-DHX633
30 R 1494C-DR633 1494C-DRX633
30 J 1494C-DJ633 1494C-DJX633
60 H ‡  1494C-DH236 ‡  1494C-DHX236
60 R 1494C-DR236 1494C-DRX236
60 J 1494C-DJ236 1494C-DJX236
60 H ‡  1494C-DH636 ‡  1494C-DHX636
60 R 1494C-DR636 1494C-DRX636
60 J 1494C-DJ636 1494C-DJX636
60 7.5 15 15 30 50 3 10 5 10 11 22 37 30 H ‡  1494C-DH263 1494C-DN60 ‡  1494C-DHX263 1494C-DNX60
30 R 1494C-DR263 1494C-DRX263
30 J 1494C-DJ263 1494C-DJX263
30 H ‡  1494C-DH663 ‡  1494C-DHX663
30 R 1494C-DR663 1494C-DRX663
30 J 1494C-DJ663 1494C-DJX663
60 H ‡  1494C-DH266 ‡  1494C-DHX266
60 R 1494C-DR266 1494C-DRX266
60 J 1494C-DJ266 1494C-DJX266
60 H ‡  1494C-DH666 ‡  1494C-DHX666
60 R 1494C-DR666 1494C-DRX666
60 J 1494C-DJ666 1494C-DJX666
100 100 H ‡  1494C-DH661 ‡  1494C-DHX661
100 100 R 1494C-DR661 1494C-DRX661
100 100 J 1494C-DJ661 1494C-DJX661
100 25 30 60 75 20 22 45 55 60 H ‡  1494C-DH216 1494C-DN100 ‡  1494C-DHX216 1494C-DNX100
60 R 1494C-DR216 1494C-DRX216
60 J 1494C-DJ216 1494C-DJX216
60 H ‡  1494C-DH616 ‡  1494C-DHX616
60 R 1494C-DR616 1494C-DRX616
60 J 1494C-DJ616 1494C-DJX616
100 H ‡  1494C-DH211 ‡  1494C-DHX211
100 R 1494C-DR211 1494C-DRX211
100 J 1494C-DJ211 1494C-DJX211
100 H ‡  1494C-DH611 ‡  1494C-DHX611
100 R 1494C-DR611 1494C-DRX611
100 J 1494C-DJ611 1494C-DJX611
200 J 1494C-DJ612 1494C-DJX612
200 50…60 60 125 150 40 48 90 110 100 H ‡  1494C-DH221 1494C-DN200 ‡  1494C-DHX221 1494C-DNX200
100 R 1494C-DR221 1494C-DRX221
100 J 1494C-DJ221 1494C-DJX221
100 H ‡  1494C-DH621 ‡  1494C-DHX621
100 R 1494C-DR621 1494C-DRX621
100 J 1494C-DJ621 1494C-DJX621
200 H ‡  1494C-DH222 ‡  1494C-DHX222
200 R 1494C-DR222 1494C-DRX222
200 J 1494C-DJ222 1494C-DJX222
200 H ‡  1494C-DH622 ‡  1494C-DHX622
200 R 1494C-DR622 1494C-DRX622
200 J 1494C-DJ622 1494C-DJX622
400 J 1494C-DJ624 1494C-DJX624
400 75 125 250 300 50 90 185 259 200 H ‡  1494C-DH242 1494C-DN400 ‡  1494C-DHX242 1494C-DNX400
200 R 1494C-DR242 1494C-DRX242
200 J 1494C-DJ242 1494C-DJX242
200 H ‡  1494C-DH642 ‡  1494C-DHX642
200 R 1494C-DR642 1494C-DRX642
200 J 1494C-DJ642 1494C-DJX642
400 H ‡  1494C-DH244 ‡  1494C-DHX244
400 R 1494C-DR244 1494C-DRX244
400 J 1494C-DJ244 1494C-DJX244
400 H ‡  1494C-DH644 ‡  1494C-DHX644
400 R 1494C-DR644 1494C-DRX644
400 J 1494C-DJ644 1494C-DJX644
600 150 200 400 500 50 150 295 375 400 H ‡  1494C-DH204 1494C-DN600 ‡  1494C-DHX204 1494C-DNX600
400 R 1494C-DR204 1494C-DRX204
400 J 1494C-DJ204 1494C-DJX204
400 H ‡  1494C-DH604 ‡  1494C-DHX604
400 R 1494C-DR604 1494C-DRX604
400 J 1494C-DJ604 1494C-DJX604
600 H ‡  1494C-DH206 ‡  1494C-DHX206
600 R 1494C-DR206 1494C-DRX206
600 J 1494C-DJ206 1494C-DJX206
600 H ‡  1494C-DH606 ‡  1494C-DHX606
600 R 1494C-DR606 1494C-DRX606
600 J 1494C-DJ606 1494C-DJX606
  
¬ The catalog number is incomplete until you select the cable mechanism code from the table below.
T Ratings based on utilizing two poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC line.
‡ Class J fuses can be installed on Class H fuse clips. However, when selecting a fuse cover (option code E), select the proper clip (Class H, J, or R) in order to receive the correct size fuse cover. Example: Cat. No. 1494C-DH233-E becomes Cat. No. 1494C-DJ233-E or Cat. No. 1494C-DR233-E.

Cable Mechanism Code

Select the desired cable length to complete the catalog number. Example: 1494C-DH633 with a 4 foot cable = 1494C-DH633-A4

Bulletin 1494C Cable Mechanism Code
Description Suffix Code
3 ft cable §  A3
4 ft cable A4
5 ft cable A5
6 ft cable §  A6
10 ft cable A10
  
§ Only available with 30…100 A switches.
§ Only available with 200…600 A switches.

Kit Accessories

Example: 1494C-DH233-A4-D-E Basic 30A fusible disconnect switch with 4 foot cable, non-metallic handle, line and load lugs, fuse cover

Bulletin 1494V Kit Accessories — Field Installed
Description Suffix Code Switch Size
30 A 60 A 100 A 200 A 400 A 600 A
Longer connecting rod (9-1/2…23 in.) A A A A A A A
Disconnect handle — Stainless steel Ø  B A A A A A A
Disconnect handle — Metal Ø  B1 A A A A
Standard size wire connecting lugs — Line and load side D Included A A A A A
Oversize wire connecting lugs — Line and load side D1 A A
Protective fuse cover with door z  E A A A A A A
Auxiliary contact 1 N.O. F A A A A A A
2 N.O. FF A A A A A A
1 N.C. G A A A A A A
2 N.C. GG A A A A A A
Electrical interlock
(Early break)
1 N.O. & 1 N.C. H A A A A A A
2 N.O. & 2 N.C. HH A A A A A A
  
Ø Non-metallic handle provided as standard on the 30…200 A switches (non-metallic handles are not available for the 400…600 A switches). The painted metal handle is provided as standard on the 400…600 A switches. For stainless steel handle, select suffix code B. For metal handle, select suffix code B1.
z Select the proper fuse clip (Class J, H, or R) in order to receive the correct size fuse cover.
Example: Cat. Nos. 1494V-DH233-E, 1494V-DJ233-E, or 1494V-DR233-E.

Disconnect Switches

Cont.
Current
Rating¬ 
[A]
600V AC
250V DC
NEMA, UL, CSA
Maximum Rating Hp
AC 1-Phase DCT  IEC Utilization
Category AC-23
Maximum Rating kW
Switch for
Right-Hand Mechanism
Switch for
Left-Hand Mechanism
3-Phase, 60 Hz 3-Phase, 50 Hz
200…208V 230V 460V 575V 115 230 250 220…240V 380…440V 500…600V Cat. No.
Switch Only
Cat. No.
Switch Only
30 7.5 7.5 15 20 2 3 5 5.5 11 15 1494F-D30 1494F-DX30
60 15 15 30 50 3 10 10 11 22 37 1494F-D60 1494F-DX60
100 25 30 60 75 20 22 45 55 1494F-D100 1494F-DX100
200 50…60 60 125 150 40 48 90 110 1494F-D200 1494F-DX200
400 75 125 250 350 50 90 185 257 1494F-D400 1494F-DX400
600 150 200 400 500 50 150 295 375 1494V-DS600 ‡  1494V-DS600
  
¬ Also rated operational current for utilization categories AC-20 and AC-21 (IEC 408).
T Ratings based on utilizing two poles in series to break one line of the DC supply voltage and the remaining pole breaking the second DC supply line.
‡ Switch can be converted in the field for left-hand operation.

Cable Mechanisms

Disconnect Switch Size [A] Cable Length [ft] Right-Hand Cable Mechanisms Left-Hand Cable Mechanisms
Cat. No. Cat. No.
30, 60, 100 3 1494C-CM1 1494C-CMX1
4 1494C-CM2 1494C-CMX2
5 1494C-CM3 1494C-CMX3
10 1494C-CM4 1494C-CMX4
200 4 1494C-CM5 1494C-CMX5
5 1494C-CM6 1494C-CMX6
6 1494C-CM7 1494C-CMX7
10 1494C-CM8 1494C-CMX8
400 4 1494C-CM9 1494C-CMX9
5 1494C-CM10 1494C-CMX10
6 1494C-CM11 1494C-CMX11
10 1494C-CM12 1494C-CMX12
600 4 1494C-CM13 1494C-CMX13
5 1494C-CM14 1494C-CMX14
6 1494C-CM15 1494C-CMX15
10 1494C-CM16 1494C-CMX16
  

Operating Handles

Handle
Type
Description Mounting Disconnect
Switch Size [A]
Cat. No.
Type 1, 3R, 4, 4X, 12 Nonmetallic Right or Left Flange 30, 60, 100, 200 1494F-P1
Type 1, 3R, 4, 12 Painted Metal Right or Left Flange 30, 60, 100, 200 1494F-M1
400, 600 1494F-M2
Type 4, 4X Stainless Steel Right or Left Flange 30, 60, 100, 200 1494F-S1
400, 600 1494F-S2
  

Trailer Fuse Block Kits

For Class H, J, or R fuses, select the proper fuse clip kit from the table below.

Disconnect Switch Size [A] Cat. No.
30 1494V-FS30
60 1494V-FS60
100 1494V-FS100
200 v  1494V-FS200
400 1494V-FS400
600 — 600 A Class J fuse 1494-FS600
600 — 400 A Class H, J, and R fuse 1494V-FSV400
600 — 600 A Class H fuse ª  1491-N621
600 — 600 A Class R fuse ª  1491-R621
  
v When installing 400 A Class J fuses, use adapter kit (Cat. No. 1401-N171). Fuse clips not required.
ª Separately mounted fuse blocks (3 required).

Fuse Clip Kits


Fuse Class Fuse Clip Rating [A] For Use With Cat. No.
250V 600V
H, J 30 1494C, 1494F,
1494G, 1494M,
1494V Disconnect
Switches
1401-N41
60 30 1401-N42
60 1401-N43
100 100 1401-N44
200 200 1401-N45
400 400 1401-N46
600 600 Ø 
J 30 30 1401-N42
60 60 1401-N43
100 100 1401-N44
200 200 1401-N45
400 400 1401-N46
600 600 ª 
R 30 1401-N50
60 30 1401-N51
60 1401-N52
100 100 1401-N53
200 200 1401-N54
400 400 1401-N55
600 600 Ø 
  
ª Fuse clips not required: fuse bolts directly to terminal.
Ø Included with Bulletin 1491 separately mounted fuse blocks.