Safety Switches

Catalogs > Industrial Controls Catalog > Motor Control, NEMA > Disconnect Switches > Safety Switches > Bulletin 1494H Safety Switches — Industrial

Bulletin 1494H Safety Switches — Industrial

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Product Selection

Build a Catalog Number


Non-Fusible Disconnect Switch (600V AC)

Continuous
Current
Rating [A]
UL & CSA Application Horsepower (Maximum) Type 1 Type 3R Type 12
1-Phase (60 Hz) 3-Phase (60 Hz) 1-Phase (60 Hz) 3-Phase (60 Hz)
240V AC 240V AC 480V AC 600V AC 125V DC 250V DC Cat. No. Cat. No. Cat. No.
30 3 10 20 30 3 5 1494H-BA3N 1494H-BN3N 1494H-BF3N
60 10 20 50 60 5 10 1494H-CA3N 1494H-CN3N 1494H-CF3N
100 20 40 75 100 20 1494H-DA3N 1494H-DN3N 1494H-DF3N
200 30 60 125 150 40 1494H-EA3N 1494H-EN3N 1494H-EF3N
  

Fusible Disconnect Switch (240V AC)★ 

Continuous
Current
Rating [A]
UL & CSA Application Horsepower Type 1 Type 3R Type 12
1-Phase (60 Hz) 3-Phase (60 Hz) 1-Phase (60 Hz)
240V AC 240V AC 480V AC 600V AC 125V DC 250V DC Cat. No. Cat. No. Cat. No.
Std. Max. Std. Max. Std. Max. Std. Max.
30 1.5 3 3 7.5 2 3 5 1494H-BA3H2 1494H-BN3H2 1494H-BF3H2
60 3 10 7.5 15 5 10 1494H-CA3H2 1494H-CN3H2 1494H-CF3H2
100 7.5 15 15 30 20 1494H-DA3H2 1494H-DN3H2 1494H-DF3H2
200 15 25 60 40 1494H-EA3H2 1494H-EN3H2 1494H-EF3H2
  
★ Includes a neutral lug for four wire applications.

Fusible Disconnect Switch (600V AC)

Continuous
Current
Rating [A]
UL & CSA Application Horsepower Type 1 Type 3R Type 12
1-Phase (60 Hz) 3-Phase (60 Hz) 1-Phase (60 Hz) 250V DC
240V AC 240V AC 480V AC 600V AC 125V DC 250V DC Cat. No. Cat. No. Cat. No.
Std. Max. Std. Max. Std. Max. Std. Max. Std. Max. Std. Max.
30 1.5 3 3 7.5 5 15 7.5 20 2 3 5 1494H-BA3H6 1494H-BN3H6 1494H-BF3H6
60 3 10 7.5 15 15 30 15 50 5 10 1494H-CA3H6 1494H-CN3H6 1494H-CF3H6
100 7.5 15 15 30 25 60 30 75 20 1494H-DA3H6 1494H-DN3H6 1494H-DF3H6
200 15 25 60 50 125 60 150 40 1494H-EA3H6 1494H-EN3H6 1494H-EF3H6
  

Ground Lugs

Description Cat. No.
Ground lug (for 30, 60 A switch) 599-GR4
Ground lug (for 100, 200 A switch) 599-GR5
  

Conduit Hubs (Type 3R)

Description Cat. No.
19.05 mm (3/4 in.) hub 1495-N71
25.4 mm (1 in.) hub 1495-N72
31.75 mm (1-1/4 in.) hub 1495-N73
38.1 mm (1-1/2 in.) hub 1495-N74
50.8 mm (2 in.) hub 1495-N75
63.5 mm (2-1/2 in.) hub 1495-N76
  

Electrical Interlock

Description Cat. No.
10 A DPDT – early break (for 30 A, Type 1 & 3R only) 1495-N77
15 A DPDT – early break (for 30 A, Type 12)
15 A DPDT – early break (for all 60 A, 100 A, & 200 A, Type 1, 3R, and 12)
1495-N78
  

Heavy Duty Class R Fuse Clip Kits

Description Cat. No.
30 A @ 250V AC (Type 1, 3R, and 12) 1401-N70
30 A @ 600V AC (Type 1 & 3R) 1401-N71
30 A @ 600V AC (Type 12) 1401-N72
60 A @ 250V AC (Type 1, 3R, and 12) 1401-N73
60 A @ 600V AC (Type 1, 3R, and 12) 1401-N74
100 A @ 250/600V AC (Type 12) 1401-N76
100 A @ 250/600V AC (Type 1 & 3R)
100 A @ 250/600V AC (Type 1 & 3R)
200 A @ 250/600V AC (Type 1, 3R, and 12)
1401-N77
  

Neutral Kits

Description Cat. No.
30 A @ 250/600V AC Fusible (Type 1 & 3R) 599-NK1
30 A @ 250/600V AC Non-Fusible (Type 1 & 3R) 599-NK2
30 A @ 250/600V AC Fusible & Non-Fusible (Type 12) 599-NK3
60 A @ 250/600V AC Fusible & Non-Fusible (Type 1 & 3R) 599-NK4
60 A @ 250/600V AC Fusible (Type 12) 599-NK5
60 A @ 250/600V AC Non-Fusible (Type 12) 599-NK6
100 A @ 250/600V AC Fusible (Type 1 & 3R) 599-NK7
100 A @ 250/600V AC Non-Fusible (Type 1, 3R, and 12) 599-NK8
100 A @ 250/600V AC Fusible (Type 12) 599-NK9
200 A @ 250/600V AC Fusible & Non-Fusible (Type 1 & 3R) 599-NK10
200 A @ 250/600V AC Fusible & Non-Fusible (Type 12) 599-NK11