Bulletin 100S-C/104S-C Safety Contactors

Click to enlarge - 100S-C_104S-C-77-1 Click to enlarge - 100S-C_104S-C-77-2

Bulletin 100S/104S Safety Contactors


Bulletin 100S-C/104S-C safety contactors provide mechanically linked positively guided contacts, required in feedback circuits of modern safety applications. The mechanically linked N.C. auxiliary contacts will not change state when a power pole welds. In addition, the gold-plated bifurcated auxiliary contacts are ideally suited for low-energy applications or feedback control circuits with multiple series-connected N.C. auxiliary contacts.

Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories and/or replacement coils.

Standards Compliance and Certifications

Standards Compliance

EN50205
CSA C22.2 No. 14
UL 508
EN/IEC 60947-4
IEC 60947-4-1 Annex H — Mirror Contacts
IEC 60947-5-1 Annex L — Mechanically Linked Contacts


Certifications

SUVA Third-Party Certified
CE Marked
cULus Listed (File No. E3125;
Guide NLDX, NLDX7)


Product Selection

3-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Aux. Contacts Cat. No.¬ T 
3Æ kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66a-3 Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ   Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 0 5 100S-C09Ä05BC
1 4 100S-C09Ä14BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 0 5 100S-C12Ä05BC
1 4 100S-C12Ä14BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 0 5 100S-C16Ä05BC
1 4 100S-C16Ä14BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 0 5 100S-C23Ä05BC
1 4 100S-C23Ä14BC
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 4 100S-C30Ä04BC
1 4 100S-C30Ä14BC
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 4 100S-C37Ä04BC
1 4 100S-C37Ä14BC
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 4 100S-C43Ä04BC
1 4 100S-C43Ä14BC
60 100 18.5 32 37 32 5 10 15 20 40 50 0 4 ‡  100S-C60Ä04BC
1 4 ‡  100S-C60Ä14BC
72 100 22 40 45 40 5 15 20 25 50 60 0 4 ‡  100S-C72Ä04BC
1 4 ‡  100S-C72Ä14BC
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 4 ‡  100S-C85Ä04BC
1 4 ‡  100S-C85Ä14BC
  
¬ For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä05BC becomes Cat. No. 100S-C09Ä05C.
‡ Bifurcated front-mount auxiliary contacts on Cat. Nos. 100S-C60…C85 conform to mirror contact performance only.

ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Click to enlarge - 100C_104C-68-1
Cat. No.
100S-C09Ä05C
Line Side


Click to enlarge - 100C_104C-68-2
Cat. No.
100S-C09UÄ05C
Load Side


4-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors Contact Configuration Cat. No.¬ ‡ 
AC-2, AC-3, AC-4 Hp (60 Hz)
3Æ kW (50 Hz)T  Main Pole Auxillary Contacts
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ T  Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
      Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C. N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 4 0 0 4 100S-C09Ä404BC
3 1 0 4 100S-C09Ä304BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 4 0 0 4 100S-C12Ä404BC
3 1 0 4 100S-C12Ä304BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 4 0 0 4 100S-C16Ä404BC
3 1 0 4 100S-C16Ä304BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 4 0 0 4 100S-C23Ä404BC
3 1 0 4 100S-C23Ä304BC
  
¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T Three-phase ratings only apply to contactors with at least three N.O. power poles.
‡ If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä404BC becomes Cat. No. 100S-C09Ä404C.

ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Reversing AC- and DC-Operated Contactors


Click to enlarge - 100S-C_104S-C-77-2


Ie [A] Ratings for Switching AC Motors Aux. Contacts
Installed per Contactor
Cat. No.¬ T 
AC-2, AC-3, AC-4 Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
3Æ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ   Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C. ‡ 
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 0 6 104S-C09Ä012BC
1 5 104S-C09Ä210BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 0 6 104S-C12Ä012BC
1 5 104S-C12Ä210BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 0 6 104S-C16Ä012BC
1 5 104S-C16Ä210BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 0 6 104S-C23Ä012BC
1 5 104S-C23Ä210BC
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 5 104S-C30Ä010BC
1 5 104S-C30Ä210BC
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 5 104S-C37Ä010BC
1 5 104S-C37Ä210BC
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 5 104S-C43Ä010BC
1 5 104S-C43Ä210BC
60 100 18.5 32 37 32 5 10 15 20 40 50 0 5 §  104S-C60Ä010BC
1 5 §  104S-C60Ä210BC
72 100 22 40 45 40 5 15 20 25 50 60 0 5 §  104S-C72Ä010BC
1 5 §  104S-C72Ä210BC
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 5 §  104S-C85Ä010BC
1 5 §  104S-C85Ä210BC
  
¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C09Ä05BC becomes Cat. No. 104S-C09Ä05C.
‡ One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock.
§ Bifurcated front-mount auxiliary contacts on Cat. Nos. 104S-C60…C85 conform to mirror contact performance only.

Ä Coil Voltage Code and Terminal Position

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09Ä05BC becomes Cat. No.100S-C09D05BC.

[V] 12 24 32 36 42 48 100 100-110 110 120 127 200 200-220 208 208-240 220-230
AC, 50 Hz R K V W X Y KP D P S KG L F
AC, 60 Hz Q J V X KP D KG H L
AC, 50/60 Hz KJ KY KP KD KG KL KL
  
[V] 230 230-240 240 277 347 380 380-400 400 400-415 440 480 500 550 600  
AC, 50 Hz VA T N G B M C
AC, 60 Hz A T I E N B C
AC, 50/60 Hz KF KA KN KB
  

[V] 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100S-C09…C43 Standard DC ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode DJ
Electronic with Integrated Diode EJ
100S-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
  

Coil Terminal Position


Terminal Markings

Terminal Markings

3-Pole Safety Contactors

Click to enlarge - 100S_c09-25_05C term Click to enlarge - 100S_c09-23_14C term Click to enlarge - 100S_c30-85_04C term
Cat. Nos. 100S-C09Ä05C…C23Ä05C Cat. Nos. 100S-C09Ä14C…C23Ä14C Cat. Nos. 100S-C30Ä04C…C85Ä04C

4-Pole Safety Contactors

Click to enlarge - 100S_c09-23_404C term Click to enlarge - 100S-C09_C23_304C term
Cat. Nos. 100S-C09Ä404C…C23Ä404C Cat. Nos. 100S-C09Ä304C…C23Ä304C

Reversing Safety Contactors

Click to enlarge - 104S_c09-23_210C term Click to enlarge - 104S_c30-85_010C term
Cat. Nos. 104S-C09Ä210C…C23Ä210C Cat. Nos. 104S-C30Ä010C…C85Ä010C

Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X
  Electronic — EI
AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
    Ie £ 500V [A] 20 20 20 32 32 32 32 (40)¬  65 65 75 75 85 100
690V [A] 20 20 20 32 32 32 32 (40)¬  65 65 75 75 85 100
1000V [A]
230V [kW] 8 8 8 13 13 13 13 26 26 30 30 34 40
240V [kW] 8.3 8.3 8.3 13 13 13 13 27 27 31 31 35 42
400V [kW] 14 14 14 22 22 22 22 45 45 52 52 59 69
415V [kW] 14 14 14 23 23 23 23 47 47 54 54 61 72
500V [kW] 17 17 17 28 28 28 28 56 56 65 65 74 87
690V [kW] 24 24 24 38 38 38 38 78 78 90 90 102 120
1000V [kW]
Ambient temperature 60 °C
    Ie £ 500V [A] 16 16 16 32 32 32 32 65 65 60 60 80 100
690V [A] 16 16 16 32 32 32 32 65 65 60 60 80 100
1000V [A]
230V [kW] 6.4 6.4 6.4 13 13 13 13 26 26 24 24 25 40
240V [kW] 6.7 6.7 6.7 13 13 13 13 27 27 25 25 26 42
400V [kW] 11 11 11 22 22 22 22 45 45 42 42 44 69
415V [kW] 12 12 12 23 23 23 23 47 47 43 43 45 72
500V [kW] 14 14 14 28 28 28 28 56 56 52 52 55 87
690V [kW] 19 19 19 38 38 38 38 78 78 72 72 75 120
1000V [kW]
Switching of 3-phase Motors; (50 Hz)
Ambient temperature 60 °C, AC-2, AC-3
  230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 29 30 38 55
690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 9 21 25 34
1000V [A]
230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 18.5 18.5 22 32
415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 20 20 22 32
500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 18.5 20 25 37
690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 7.5 18.5 22 32
1000V [kW]
Load Carrying Capacity per UL/CSA
General Purpose Current (enclosed)
  [A] 12 15 18 25 25 30 30 55 60 60 60 75 90
Rated power (enclosed)
    1-phase 115V [A] 9.8 9.8 13.8 9.8 9.8 16 24 24 34 34 34 34 56
230V [A] 8 10 12 10 12 17 17 28 28 28 28 40 50
115V [Hp] 0.5 0.5 0.75 0.5 0.5 1 2 2 3 3 3 3 5
230V [Hp] 1 1.5 2 1.5 2 3 3 5 5 5 5 7.5 10
    3-phase 200V [A] 6.9 7.8 11 7.8 11 17.5 17.5 25.3 32.2 32.2 32.2 32.2 48.3
230V [A] 6 6.8 9.6 6.8 9.6 15.2 22 28 28 28 28 42 54
460V [A] 4.8 7.6 11 7.6 11 14 21 27 34 34 34 40 52
575V [A] 3.9 6.1 9 9 11 17 17 27 32 17 32 32 52
200V [Hp] 1.5 2 3 2 3 5 5 7.5 10 10 10 10 15
230V [Hp] 1.5 2 3 2 3 5 7.5 10 10 10 10 15 20
460V [Hp] 3 5 7.5 5 7.5 10 15 20 25 25 25 30 40
575V [Hp] 3 5 7.5 7.5 10 15 15 25 30 15 30 30 50
  
¬ Values in ( ) with increased cross-section and cable lug

  100/104-C, 100S/104S-C 100/104-D, 100S-D
  72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X X
AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
Electronic — EI AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
    Ie £ 500V [A] 100 100 130 130 160 160 250 250 250 250 350 350 450 540 800 1000
690V [A] 100 100 130 130 160 160 250 250 250 250 350 350 450 540 800 1000
1000V [A] 160 160 250 250 250 250 350 350 450 540
230V [kW] 40 40 52 52 64 64 100 100 100 100 139 139 179 199 319 398
240V [kW] 42 42 54 54 67 67 104 104 104 104 145 145 187 208 333 416
400V [kW] 69 69 90 90 111 111 173 173 173 173 242 242 312 346 554 693
415V [kW] 72 72 93 93 115 115 180 180 180 180 252 252 323 359 575 719
500V [kW] 87 87 113 113 139 139 217 217 217 217 303 303 390 433 693 866
690V [kW] 120 120 155 155 191 191 299 299 299 299 418 418 538 598 956 1195
1000V [kW] 277 277 433 433 433 433 606