Bulletin 100S-C/104S-C Safety Contactors

Click to enlarge - 100S-C_104S-C-77-1 Click to enlarge - 100S-C_104S-C-77-2

Bulletin 100S/104S Safety Contactors


Bulletin 100S-C/104S-C safety contactors provide mechanically linked positively guided contacts, required in feedback circuits of modern safety applications. The mechanically linked N.C. auxiliary contacts will not change state when a power pole welds. In addition, the gold-plated bifurcated auxiliary contacts are ideally suited for low-energy applications or feedback control circuits with multiple series-connected N.C. auxiliary contacts.

Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories and/or replacement coils.

Standards Compliance and Certifications

Standards Compliance

EN50205
CSA C22.2 No. 14
UL 508
EN/IEC 60947-4
IEC 60947-4-1 Annex H — Mirror Contacts
IEC 60947-5-1 Annex L — Mechanically Linked Contacts


Certifications

SUVA Third-Party Certified
CE Marked
cULus Listed (File No. E3125;
Guide NLDX, NLDX7)


Product Selection

3-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Aux. Contacts Cat. No.¬ T 
3Æ kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66a-3 Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ   Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 0 5 100S-C09Ä05BC
1 4 100S-C09Ä14BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 0 5 100S-C12Ä05BC
1 4 100S-C12Ä14BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 0 5 100S-C16Ä05BC
1 4 100S-C16Ä14BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 0 5 100S-C23Ä05BC
1 4 100S-C23Ä14BC
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 4 100S-C30Ä04BC
1 4 100S-C30Ä14BC
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 4 100S-C37Ä04BC
1 4 100S-C37Ä14BC
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 4 100S-C43Ä04BC
1 4 100S-C43Ä14BC
60 100 18.5 32 37 32 5 10 15 20 40 50 0 4 ‡  100S-C60Ä04BC
1 4 ‡  100S-C60Ä14BC
72 100 22 40 45 40 5 15 20 25 50 60 0 4 ‡  100S-C72Ä04BC
1 4 ‡  100S-C72Ä14BC
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 4 ‡  100S-C85Ä04BC
1 4 ‡  100S-C85Ä14BC
  
¬ For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä05BC becomes Cat. No. 100S-C09Ä05C.
‡ Bifurcated front-mount auxiliary contacts on Cat. Nos. 100S-C60…C85 conform to mirror contact performance only.

ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Click to enlarge - 100C_104C-68-1
Cat. No.
100S-C09Ä05C
Line Side


Click to enlarge - 100C_104C-68-2
Cat. No.
100S-C09UÄ05C
Load Side


4-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors Contact Configuration Cat. No.¬ ‡ 
AC-2, AC-3, AC-4 Hp (60 Hz)
3Æ kW (50 Hz)T  Main Pole Auxillary Contacts
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ T  Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
      Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C. N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 4 0 0 4 100S-C09Ä404BC
3 1 0 4 100S-C09Ä304BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 4 0 0 4 100S-C12Ä404BC
3 1 0 4 100S-C12Ä304BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 4 0 0 4 100S-C16Ä404BC
3 1 0 4 100S-C16Ä304BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 4 0 0 4 100S-C23Ä404BC
3 1 0 4 100S-C23Ä304BC
  
¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T Three-phase ratings only apply to contactors with at least three N.O. power poles.
‡ If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä404BC becomes Cat. No. 100S-C09Ä404C.

ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Reversing AC- and DC-Operated Contactors


Click to enlarge - 100S-C_104S-C-77-2


Ie [A] Ratings for Switching AC Motors Aux. Contacts
Installed per Contactor
Cat. No.¬ T 
AC-2, AC-3, AC-4 Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
3Æ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ   Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C. ‡ 
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 0 6 104S-C09Ä012BC
1 5 104S-C09Ä210BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 0 6 104S-C12Ä012BC
1 5 104S-C12Ä210BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 0 6 104S-C16Ä012BC
1 5 104S-C16Ä210BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 0 6 104S-C23Ä012BC
1 5 104S-C23Ä210BC
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 5 104S-C30Ä010BC
1 5 104S-C30Ä210BC
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 5 104S-C37Ä010BC
1 5 104S-C37Ä210BC
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 5 104S-C43Ä010BC
1 5 104S-C43Ä210BC
60 100 18.5 32 37 32 5 10 15 20 40 50 0 5 §  104S-C60Ä010BC
1 5 §  104S-C60Ä210BC
72 100 22 40 45 40 5 15 20 25 50 60 0 5 §  104S-C72Ä010BC
1 5 §  104S-C72Ä210BC
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 5 §  104S-C85Ä010BC
1 5 §  104S-C85Ä210BC
  
¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C09Ä05BC becomes Cat. No. 104S-C09Ä05C.
‡ One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock.
§ Bifurcated front-mount auxiliary contacts on Cat. Nos. 104S-C60…C85 conform to mirror contact performance only.

Ä Coil Voltage Code and Terminal Position

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09Ä05BC becomes Cat. No.100S-C09D05BC.

[V] 12 24 32 36 42 48 100 100-110 110 120 127 200 200-220 208 208-240 220-230
AC, 50 Hz R K V W X Y KP D P S KG L F
AC, 60 Hz Q J V X KP D KG H L
AC, 50/60 Hz KJ KY KP KD KG KL KL
  
[V] 230 230-240 240 277 347 380 380-400 400 400-415 440 480 500 550 600  
AC, 50 Hz VA T N G B M C
AC, 60 Hz A T I E N B C
AC, 50/60 Hz KF KA KN KB
  

[V] 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100S-C09…C43 Standard DC ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode DJ
Electronic with Integrated Diode EJ
100S-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
  

Coil Terminal Position


Terminal Markings

Assignment of Contacts

Safety Contactors with 3 Main Contacts and Standard Front-mount Auxiliary Contacts

Click to enlarge - 100S-C_3 Maincont_Std-aux


Safety Contactors with 4 Main Contacts and Standard Front-mount Auxiliary Contacts

Click to enlarge - 100S-C_4 Maincont_Std-aux


Safety Reversing Contactors with 3 Main Contacts and Standard Front-mount Auxiliary Contacts

Click to enlarge - 104S-C_3 Maincont_Std-aux


Safety Contactors with 3 Main Contacts and Bifurcated Front-mount Auxiliary Contacts

Click to enlarge - 100S-C_3 Maincont_Bif-aux


Safety Contactors with 4 Main Contacts and Bifurcated Front-mount Auxiliary Contacts

Click to enlarge - 100S-C_4 Maincont_Bif-aux


Safety Reversing Contactors with 3 Main Contacts and Bifurcated Front-mount Auxiliary Contacts

Click to enlarge - 104S-C_3Maincont_Bif-aux

Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X
  Electronic — EI
AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
    Ie £ 500V [A] 20 20 20 32 32 32 32 (40)¬  65 65 75 75 85 100
690V [A] 20 20 20 32 32 32 32 (40)¬  65 65 75 75 85 100
1000V [A]
230V [kW] 8 8 8 13 13 13 13 26 26 30 30 34 40
240V [kW] 8.3 8.3 8.3 13 13 13 13 27 27 31 31 35 42
400V [kW] 14 14 14 22 22 22 22 45 45 52 52 59 69
415V [kW] 14 14 14 23 23 23 23 47 47 54 54 61 72
500V [kW] 17 17 17 28 28 28 28 56 56 65 65 74 87
690V [kW] 24 24 24 38 38 38 38 78 78 90 90 102 120
1000V [kW]
Ambient temperature 60 °C
    Ie £ 500V [A] 16 16 16 32 32 32 32 65 65 60 60 80 100
690V [A] 16 16 16 32 32 32 32 65 65 60 60 80 100
1000V [A]
230V [kW] 6.4 6.4 6.4 13 13 13 13 26 26 24 24 25 40
240V [kW] 6.7 6.7 6.7 13 13 13 13 27 27 25 25 26 42
400V [kW] 11 11 11 22 22 22 22 45 45 42 42 44 69
415V [kW] 12 12 12 23 23 23 23 47 47 43 43 45 72
500V [kW] 14 14 14 28 28 28 28 56 56 52 52 55 87
690V [kW] 19 19 19 38 38 38 38 78 78 72 72 75 120
1000V [kW]
Switching of 3-phase Motors; (50 Hz)
Ambient temperature 60 °C, AC-2, AC-3
  230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 29 30 38 55
690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 9 21 25 34
1000V [A]
230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 18.5 18.5 22 32
415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 20 20 22 32
500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 18.5 20 25 37
690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 7.5 18.5 22 32
1000V [kW]
Load Carrying Capacity per UL/CSA
General Purpose Current (enclosed)
  [A] 12 15 18 25 25 30 30 55 60 60 60 75 90
Rated power (enclosed)
    1-phase 115V [A] 9.8 9.8 13.8 9.8 9.8 16 24 24 34 34 34 34 56
230V [A] 8 10 12 10 12 17 17 28 28 28 28 40 50
115V [Hp] 0.5 0.5 0.75 0.5 0.5 1 2 2 3 3 3 3 5
230V [Hp] 1 1.5 2 1.5 2 3 3 5 5 5 5 7.5 10
    3-phase 200V [A] 6.9 7.8 11 7.8 11 17.5 17.5 25.3 32.2 32.2 32.2 32.2 48.3
230V [A] 6 6.8 9.6 6.8 9.6 15.2 22 28 28 28 28 42 54
460V [A] 4.8 7.6 11 7.6 11 14 21 27 34 34 34 40 52
575V [A] 3.9 6.1 9 9 11 17 17 27 32 17 32 32 52
200V [Hp] 1.5 2 3 2 3 5 5 7.5 10 10 10 10 15
230V [Hp] 1.5 2 3 2 3 5 7.5 10 10 10 10 15 20
460V [Hp] 3 5 7.5 5 7.5 10 15 20 25 25 25 30 40
575V [Hp] 3 5 7.5 7.5 10 15 15 25 30 15 30 30 50
  
¬ Values in ( ) with increased cross-section and cable lug

  100/104-C, 100S/104S-C 100/104-D, 100S-D
  72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X X
AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
    Ie £ 500V [A] 100 100 130 130 160 160 250 250 250 250 350 350 450 540 800 1000
690V [A] 100 100 130 130 160 160 250 250 250 250 350 350 450 540 800 1000
1000V [A] 160 160 250 250 250 250 350 350 450 540
230V [kW] 40 40 52 52 64 64 100 100 100 100 139 139 179 199 319 398
240V [kW] 42 42 54 54 67 67 104 104 104 104 145 145 187 208 333 416
400V [kW] 69 69 90 90 111 111 173 173 173 173 242 242 312 346 554 693
415V [kW] 72 72 93 93 115 115 180 180 180 180 252 252 323 359 575 719
500V [kW] 87 87 113 113 139 139 217 217 217 217 303 303 390 433 693 866
690V [kW] 120 120 155 155 191 191 299 299 299 299 418 418 538 598 956 1195
1000V [kW] 277 277 433 433 433 433 606 606 779 866
Ambient temperature 60 °C
    Ie £ 500V [A] 100 100 110 110 135 135 210 210 210 210 300 300 380 425
690V [A] 100 100 110 110 135 135 210 210 210 210 300 300 380 425
1000V [A] 135 135 210 210 210 210 300 300 380 425
230V [kW] 40 40 44 44 54 54 84 84 84 84 120 120 151 169
240V [kW] 42 42 46 46 56 56 87 87 87 87 125 125 158 177
400V [kW] 69 69 76 76 94 94 145 145 145 145 208 208 263 294
415V [kW] 72 72 79 79 97 97 151 151 151 151 216 216 273 305
500V [kW] 87 87 95 95 117 117 182 182 182 182 260 260 329 368
690V [kW] 120 120 131 131 161 161 251 251 251 251 359 359 454 508
1000V [kW] 234 234 364 364 364 364 520 520 658 736
Switching of 3-phase Motors; (50 Hz)
Ambient temperature 60 °C, AC-2, AC-3
  230V [A] 72 85 85 85 95 110 140 140 180 180 210 250 300 420 630 860
240V [A] 72 85 85 85 95 110 140 140 180 180 210 250 300 420 630 860
400V [A] 72 85 85 85 95 110 140 140 180 180 210 250 300 420 630 860
415V [A] 72 85 85 85 95 110 (130)‡  140 (155)‡  140 (155)‡  180 (189)‡  180 (189)‡  210 (227)‡  250 (258)‡  300 (315)‡  420 630 860
500V [A] 67 80 80 80 95 110 115 140 140 180 210 250 300 420 630 753
690V [A] 42 49 22 49 95 110 115 140 140 180 210 250 300 420 492
1000V [A] 33 40 55 55 65 65 80 95 115 160
230V [kW] 22 25 25 25 30 34 45 45 57 57 67 80 97 135 200 250
240V [kW] 22 25 25 25 31 36 47 47 60 60 70 83 101 141 200 250
400V [kW] 40 45 45 45 53 61 78 78 101 101 118 140 170 238 355 500
415V [kW] 40 45 45 45 55 63 (75)‡  82 (90)‡  82 (90)‡  105 (110)‡  105 (110)‡  122 (132)‡  145 (150)‡  176 (185)‡  250 355 500
500V [kW] 45 55 55 55 66 76 80 98 98 126 147 177 213 298 450 560
690V [kW] 40 45 18.5 45 92 106 111 135 135 176 205 250 293 424 500
1000V [kW] 45 55 75 75 90 90 110 132 160 225
Load Carrying Capacity per UL/CSA
General Purpose Current (enclosed)
    [A] 90 100 125 130 160 160 220 220 220 220 300 300 340 420 630 860
Rated power (enclosed)
    1-phase 115V [A] 56 80 80 80 80 100 135 135
230V [A] 68 68 68 68 68 110 136 136 176 176 216
115V [Hp] 5 7.5 7.5 7.5 7.5 10 15 15
230V [Hp] 15 15 15 15 15 25 30 30 40 40 50
    3-phase 200V [A] 62.1 78.2 78.2 78.2 78.2 120 120 120 150 150 177 221 285 414 552 692
230V [A] 68 80 80 80 80 104 130 130 154 154 192 248 312 420 602 720
460V [A] 65 77 65 77 77 96 124 124 180 180 180 240 302 414 590 702
575V [A] 62 62 22 52 77 99 125 125 144 144 192 242 289 382 562 651
200V [Hp] 20 25 25 25 25 40 40 40 50 50 60 75 100 150 200 250
230V [Hp] 25 30 30 30 30 40 50 50 60 60 75 100 125 175 250 300
460V [Hp] 50 60 50 60 60 75 100 100 150 150 150 200 250 350 500 600
575V [Hp] 60 60 20 50 75 100 125 125 150 150 200 250 300 400 600 700
  
¬ Values in ( ) with increased cross-section and cable lug

 
100/104-K

100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X X
Electronic — EI
Switching of 3-phase Motors, (50Hz); Ambient temperature 60 °C, AC-4
  230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 38 55
690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 25 34
1000V [A]
230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 22 32
415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 22 32
500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 25 37
690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 22 32
1000V [kW]
Electronic — EI
AC-4 at approximately 200,000 operations 230V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
240V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
400/415V [A] 2 3.6 3.6 4.3 6.6 9 9 12 14 16.5 25.5
500V [A] 1.9 3.2 3.2 4.3 6.6 9 9 12 14 16.5 25.5
690V [A] 4.3 6.6 9 9 12 14 16.5 25.5
1000V [A]
230V¬  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 3.7 4 6.3
240V¬  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 4 4 7.5
400V¬  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
415V¬  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
500V¬  [kW] 0.75 1.5 1.5 2.2 3.7 5.5 5.5 7.5 7.5 10 15
690V¬  [kW] 3 5.5 7.5 7.5 10 11 15 22
1000V¬  [kW]
Max. switching frequency Ops/h 250 250 250 250 250 220 200 200 200 200 120
Wye-Delta (60 Hz)
  200V [Hp] 2.2 3 5 5 5 7½ 7½ 10 15 20 30
230V [Hp] 2.2 3 5 5 7½ 10 10 15 20 25 40
460V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
575V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
UL/CSA Elevator DutyT 
  200V [A] 7.8 11.0 11.0 17.5 25.3 25.3 32.2 32.2
230V [A] 6.8 9.6 15.2 15.2 22.0 28.0 28.0 42.0
460V [A] 7.6 11.0 14.0 21.0 27.0 27.0 34.0 40.0
575V [A] 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0
200V [Hp] 2 3 3 5 7½ 7½ 10 10
230V [Hp] 2 3 5 5 7½ 10 10 15
460V [Hp] 5 7½ 10 15 20 20 25 30
575V [Hp] 5 7½ 10 15 20 25 30 40
Star-Delta Starting (50 Hz)
  £ 230V [A] 11.3 20 20 21 26 35 46 61 66 76 107
£ 240V [A] 11.3 20 20 21 26 35 46 61 66 76 107
400V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
415V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
500V [A] 6.8 12.4 12.4 12 17 24 35 43 52 66 95
690V [A] 4.9 8.9 8.9 8.6 12 16 21 31 36 43 59
1000V [A]
230V¬  [kW] 3 5.5 5.5 5.5 7.5 10 13 17 20 22 32
240V¬  [kW] 3 5.5 5.5 5.5 7.5 10 13 18.5 20 22 32
400V¬  [kW] 4 7.5 10 7.5 10 13 20 25 32 40 55
415V¬  [kW] 4 7.5 11 7.5 11 15 22 25 37 40 55
500V¬  [kW] 4 7.5 7.5 7.5 11 15 22 25 32 45 63
690V¬  [kW] 4 7.5 7.5 7.5 10 13 18.5 25 32 40 55
1000V¬  [kW]
  
¬ Power ratings at 50 Hz: Preferred values according to IEC 60072-1 T Approval pending on Cat. No. 100-D210…D860.

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 95 110 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X
Electronic — EI X X X X X X X X X X
Switching of 3-phase Motors, (50Hz)
Ambient temperature 60°C, AC-4
  230V [A] 72 85 95 110 140 140 180 180 210 250 300 420
240V [A] 72 85 95 110 140 140 180 180 210 250 300 420
400V [A] 72 85 95 110 140 140 180 180 210 250 300 420
415V [A] 72 85 95 110 (130)T  140 (155)T  140 (155)T  180 (189)‡  180 (189)‡  210 (227)T  250 (258)T  300 (315)T  420
500V [A] 67 80 85 105 115 140 140 170 210 250 300 360
690V [A] 42 49 85 105 115 140 140 170 210 250 300 360
1000V [A] 33 40 55 55 65 65 80 95 115 160
230V [kW] 22 25 30 34 45 45 57 57 67 80 97 135
240V [kW] 22 25 31 36 47 47 60 60 70 83 101 141
400V [kW] 40 45 53 61 78 78 100 100 118 140 170 238
415V [kW] 40 45 55 63 (75)T  82 (90)T  82 (90)T  105 (110)T  105 (110)T  125 (132)T  145 (150)T  176 (185)T  250
500V [kW] 45 55 59 73 80 98 98 119 147 177 213 255
690V [kW] 40 45 81 102 110 135 135 167 205 250 293 356
1000V [kW] 45 55 75 75 90 90 110 132 160 225
AC-4 at approximately 200,000 operations
  230V [A] 31 38 43 50 60 60 67 67 85 105 140 170
240V [A] 31 38 43 50 60 60 67 67 85 105 140 170
400/415V [A] 31 38 43 50 60 60 67 67 85 105 140 170
500V [A] 31 38 43 50 60 60 67 67 85 105 140 170
690V [A] 31 38 43 50 60 60 67 67 85 105 140 170
1000V [A] 19 23 37 37 43 43 60 72 85 105
230V¬  [kW] 7.5 11 13 15 17 17 20 20 25 32 45 55
240V¬  [kW] 7.5 11 13 15 18.5 18.5 22 22 25 32 45 55
400V¬  [kW] 15 20 22 25 32 32 37 37 45 55 75 90
415V¬  [kW] 17 20 22 25 32 32 37 37 50 55 80 100
500V¬  [kW] 20 25 25 32 40 40 45 45 55 75 100 110
690V¬  [kW] 25 32 40 45 55 55 63 63 80 100 132 160
1000V¬  [kW] 22 30 50 50 55 55 80 100 110 150
Max. switching frequency Ops/h 120 120 120 120 120 120 100 100 120 100 70 70
Wye-Delta (60 Hz)
  200V [Hp] 40 50 40 60 60 60 75 75 100 125 175 250
230V [Hp] 50 60 50 60 75 75 100 100 125 175 200 250
460V [Hp] 100 125 100 125 175 175 200 200 250 350 450 600
575V [Hp] 100 125 125 150 200 200 250 250 300 450 500 650
UL/CSA Elevator DutyT 
  200V [A] 48.3 62.1 62.1 78 92 92 120 120 150 150 177 221
230V [A] 54.0 68.0 68.0 80 104 104 130 130 130 154 192 248
460V [A] 52.0 65.0 65.0 77 96 96 124 124 156 180 180 240
575V [A] 52.0 62.0 62.0 77 77 77 99 99 125 144 192 242
200V [Hp] 15 20 20 25 30 30 40 40 50 50 60 75
230V [Hp] 20 25 25 30 40 40 50 50 50 60 75 100
460V [Hp] 40 50 50 60 75 75 100 100 125 150 150 200
575V [Hp] 50 60 60 75 75 75 100 100 125 150 200 250
Star-Delta Starting (50 Hz)
  £ 230V [A] 125 147 165 191 242 242 312 312 364 433 520 727
£ 240V [A] 125 147 165 191 242 242 312 312 364 433 520 727
400V [A] 125 147 165 191 242 242 312 312 364 433 520 727
415V [A] 125 147 165 191 (225)T  242 (268)T  242 (268)T  312 (332)‡  312 (332)‡  364 (393)T  433 (447)T  520 (546)T  727
500V [A] 116 139 165 191 199 242 312 312 364 433 520 727
690V [A] 73 85 165 191 199 242 312 312 364 433 520 727
1000V [A] 57 69 95 95 113 113 139 165 200 277
230V¬  [kW] 37 45 45 55 75 75 90 90 110 132 160 220
240V¬  [kW] 40 50 50 63 80 80 100 100 125 150 160 250
400V¬  [kW] 63 80 80 100 132 132 160 160 200 250 300 425
415V¬  [kW] 63 80 80 (90)T  100 (132)T  132 (160)T  132 (160)T  160 160 220 250 315 (335)T  425
500V¬  [kW] 80 90 100 132 132 160 200 200 250 315 375 530
690V¬  [kW] 63 80 132 160 200 220 300 300 355 425 530 750
1000V¬  [kW] 75 90 132 132 160 160 200 220 280 400
  
T 415V: Values in ( ) AC-3 and AC-4 lifespan -25%

 
100/104-K

100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X X
Electronic — EI
Switching of Power Transformers,
AC-6a (50 Hz)
Inrush Current = n  
Rated transformer current  
    n = 30 £ 230V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 240V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 400V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 415V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 500V [A] 1.8 3.2 3.2 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 690V [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 1000V [A]
230V [kVA] 1.2 2 2 4.3 4.3 4.3 4.3 8 8 9.2 16
240V [kVA] 1.2 2 2 4.5 4.5 4.5 4.5 8.3 8.3 10 17
400V [kVA] 1.7 2.8 3.4 7.5 7.5 7.5 7.5 14 14 16 28
415V [kVA] 1.7 2.8 3.4 7.8 7.8 7.8 7.8 14 14 17 29
500V [kVA] 1.7 2.8 3.4 9.4 9.4 9.4 9.4 17 17 20 35
690V [kVA] 2 4 5 13 13 13 13 24 24 27 49
1000V [kVA]
    n = 20 £ 690V [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
    n = 15 £ 690V [A] 22 22 22 22 40 40 46 82
60 Hz Peak Inrush/peak rated transformer current
  n = 30 [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
200V [kVA] 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.1
208V [kVA] 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.7
240V [kVA] 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17.0
480V [kVA] 9.1 9.1 9.1 9.1 16.6 16.6 19.1 33.9
600V [kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.4
660V [kVA] 12.5 12.5 12.5 12.5 22.9 22.9 26.3 46.6
60 Hz Peak Inrush/peak rated transformer current
  n = 20 [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
200V [kVA] 5.6 5.6 5.6 5.6 10.4 10.4 12.0 21.2
208V [kVA] 5.9 5.9 5.9 5.9 10.8 10.8 12.4 22.1
240V [kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5
480V [kVA] 13.6 13.6 13.6 13.6 24.9 24.9 28.7 51.0
600V [kVA] 16.9 16.9 16.9 16.9 31.2 31.2 35.9 63.7
660V [kVA] 18.6 18.6 18.6 18.6 34.3 34.3 39.4 70.1
60 Hz Peak Inrush/peak rated transformer current
  n=15 [A] 22 22 22 22 40 40 46 82
200V [kVA] 7.5 7.5 7.5 7.5 13.9 13.9 15.9 28.4
208V [kVA] 7.8 7.8 7.8 7.8 14.4 14.4 16.6 29.5
240V [kVA] 9.0 9.0 9.0 9.0 16.6 16.6 19.1 34.1
480V [kVA] 18.1 18.1 18.1 18.1 33.3 33.3 38.2 68.2
600V [kVA] 22.6 22.6 22.6 22.6 41.6 41.6 47.8 85.2
660V [kVA] 24.9 24.9 24.9 24.9 45.7 45.7 52.6 93.7
  

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 95 110 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X
Electronic — EI X X X X X X X X X X
Switching of Power Transformers,
AC-6a (50 Hz)
Inrush Current
Rated transformer current
    n = 30 £ 230V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
£ 240V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
£ 400V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
£ 415V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
£ 500V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
£ 690V [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
£ 1000V [A] 53 60 70 70 85 85 105 125 150 210
230V [kVA] 16 16 21 24 28 28 34 34 42 50 60 84
240V [kVA] 17 17 22 25 29 29 35 35 44 52 62 87
400V [kVA] 28 28 37 42 48 48 59 59 73 87 104 145
415V [kVA] 29 29 38 43 50 50 61 61 75 90 108 151
500V [kVA] 35 35 46 52 61 61 74 74 91 108 130 182
690V [kVA] 49 49 64 72 84 84 102 102 125 149 179 251
1000V [kVA] 92 104 121 121 147 147 182 217 260 364
    n = 20 £ 690V [A] 61.3 61.3 80 90 105 105 128 128 158 188 225 315
    n = 15 £ 690V [A] 82 82 107 120 140 140 170 170 210 250 300 420
60 Hz Peak Inrush/peak rated transformer current
  n = 30 [A] 40.8 40.8 53 60 70 70 85 85 105 125 150 210
200V [kVA] 14.4 14.4 18.4 20.8 24.2 24.2 29.4 29.4 36.4 43.3 52.0 72.7
208V [kVA] 14.7 14.7 19.1 21.6 25.2 25.2 30.6 30.6 37.8 45.0 54.0 75.7
240V [kVA] 17.0 17.0 22.0 24.9 29.1 29.1 35.3 35.3 43.6 52.0 62.4 87.3
480V [kVA] 33.9 33.9 44.1 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
600V [kVA] 42.4 42.4 55.1 62.4 72.7 72.7 88.3 88.3 109 130 156 218
660V [kVA] 46.6 46.6 60.6 68.6 80.0 80.0 97.2 97.2 120 143 171 240
60 Hz Peak Inrush/peak rated transformer current
  n = 20 [A] 61.3 61.3 80 90 105 105 128 128 158 188 225 315
200V [kVA] 21.2 21.2 27.7 31.2 36.4 36.4 44.3 44.3 54.7 65.1 77.9 109
208V [kVA] 22.1 22.1 28.8 32.4 37.8 37.8 46.1 46.1 56.9 67.7 81.1 113
240V [kVA] 25.5 25.5 33.3 37.4 43.6 43.6 53.2 53.2 65.7 78.2 93.5 131
480V [kVA] 51.0 51.0 66.5 74.8 87.3 87.3 106 106 131 156 187 262
600V [kVA] 63.7 63.7 83.1 93.5 109 109 133 133 164 195 234 327
660V [kVA] 70.1 70.1 91.5 103 120 120 146 146 131 215 257 360
60 Hz Peak Inrush/peak rated transformer current
  n=15 [A] 82 82 107 120 140 140 170 170 210 250 300 420
200V [kVA] 28.4 28.4 37.1 41.6 48.5 48.5 58.9 58.9 72.7 86.6 104 145
208V [kVA] 29.5 29.5 38.5 43.2 50.4 50.4 61.2 61.2 75.7 90.1 108 151
240V [kVA] 34.1 34.1 44.5 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
480V [kVA] 68.2 68.2 89.0 99.8 116 116 141 141 175 208 249 349
600V [kVA] 85.2 85.2 111 125 145 145 177 177 218 260 312 436
660V [kVA] 93.7 93.7 122 137 160 160 194 194 240 286 343 480
  

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X
Electronic — EI
Switching of 3-phase Capacitors, AC-6b (50 Hz)¬ 
Single capacitor 40 °C 230V [kVar] 8 8 8.5 9 14 14 24 28
240V [kVar] 8 8 8.5 9 14 14 25 29
400V [kVar] 8 8 10 12.5 20 24 35 48
415V [kVar] 8 8 10 12.5 20 25 35 50
500V [kVar] 8 8 10 12.5 20 25 35 50
690V [kVar] 8 8 10 12.5 20 25 35 50
1000V [kVar]
    60 °C 230V [kVar] 8 8 8.5 9 12.5 12.5 18 28
240V [kVar] 8 8 8.5 9 12.5 12.5 18 29
400V [kVar] 8 8 10 12.5 20 21.5 30 42
415V [kVar] 8 8 10 12.5 20 22 30 42
500V [kVar] 8 8 10 12.5 20 25 30 42
690V [kVar] 8 8 10 12.5 20 25 30 42
1000V [kVar]
Group capacitors 40 °C 230V [kVar] 5 5 8 9 12.5 14 20 28
240V [kVar] 5 5 8 9 12.5 14 20 29
400V [kVar] 5 5 8 10 15 20 25 40
415V [kVar] 5 5 8 10 15 20 25 40
500V [kVar] 5 5 8 10 15 20 25 40
690V [kVar] 5 5 8 10 15 20 25 40
1000V [kVar]
    60 °C 230V [kVar] 5 5 8 9 12.5 12.5 18 28
240V [kVar] 5 5 8 9 12.5 12.5 18 29
400V [kVar] 5 5 8 10 15 20 25 40
415V [kVar] 5 5 8 10 15 20 25 40
500V [kVar] 5 5 8 10 15 20 25 40
690V [kVar] 5 5 8 10 15 20 25 40
1000V [kVar]
60 Hz Single Capacitor — 40 °C
  200V [kVar] 5 5 8 9 12.5 14 20 28
230V [kVar] 5 5 8 9 12.5 14 20 29
460V [kVar] 5 5 8 10 15 20 25 40
600V [kVar] 5 5 8 10 15 20 25 40
60 Hz Group Capacitors — 40 °C
  200V [kVar] 5 5 8 9 12.5 12.5 18 28
230V [kVar] 5 5 8 9 12.5 12.5 18 29
460V [kVar] 5 5 8 10 15 20 25 40
600V [kVar] 5 5 8 10 15 20 25 40
Switching of Lamps
Gas discharge lamps AC-5a, 40 °C open [A] 18 18 18 22.5 25 28 29 40.5 45 65 65 77 81
  enclosed [A] 14.5 14.5 14.5 22.5 25 28 29 37 41 54 54 57 77
Individually compensated:
Max. capacitance at expected
Short-circuit current of 10 kA [mF] 750 750 750 1 000 1 000 1 000 1 000 2 700 2 700 3 200 4 000
20 kA [mF] 400 400 400 500 500 500 500 1 350 1 350 1 600 2 000
50 kA [mF] 200 200 200 200 540 540 640 800
Filament AC-5b 230/240V [A] 5 9 9 12 16 18 22 30 37 18 25 43 60
Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
AC-7a 230V [A] 20 20 20 32 32 32 32 45 45 63
400V [A] 20 20 20 32 32 32 32 45 45 63
440V [A] 32 32 32 32 45 45 63
Switching of Motor Load for Home Appliances (50 Hz)
AC-7b 230V [A] 6 11 11 10.5 14 19 23 30
400V [A] 6 11 11 9 12 16 20 30
440V [A] 7.5 10 13.5 18 27
  
¬ Inductance of leads between capacitors in parallel: min. 6 mH (100-C09…C30 contactors: min 30 mH)

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X X
Switching of 3-phase Capacitors, AC-6b (50 Hz)
Single capacitor 40°C 230V [kVar] 28 28 45 45 70 70 70 70 98 98 125 139
240V [kVar] 29 29 47 47 73 73 73 73 102 102 131 145
400V [kVar] 48 48 78 78 121 121 121 121 170 170 218 242
415V [kVar] 50 50 81 81 126 126 126 126 176 176 226 252
500V [kVar] 55 60 97 97 152 152 152 152 212 212 273 303
690V [kVar] 55 60 134 134 209 209 209 209 293 293 376 418
1000V [kVar] 194 194 303 303 303 303 424 424 546 606
    60 °C 230V [kVar] 28 28 38 38 59 59 59 59 84 84 106 119
240V [kVar] 29 29 39 39 61 61 61 61 87 87 111 124
400V [kVar] 48 48 65 65 102 102 102 102 145 145 184 206
415V [kVar] 50 50 68 68 106 106 106 106 151 151 191 214
500V [kVar] 50 55 82 82 127 127 127 127 182 182 230 258
690V [kVar] 50 55 113 113 176 176 176 176 251 251 318 356
1000V [kVar] 164 164 255 255 255 255 364 364 461 515
Group capacitors 40°C 230V [kVar] 28 28 42 45 70 70 70 70 98 98 125 139
240V [kVar] 29 29 43 47 73 73 73 73 102 102 131 145
400V [kVar] 48 48 44 56 76 76 111 111 170 170 218 242
415V [kVar] 50 50 44 56 76 76 112 112 170 176 226 252
500V [kVar] 50 50 44 56 76 76 113 113 172 212 273 303
690V [kVar] 50 50 45 57 78 78 114 114 174 247 356 418
1000V [kVar] 46 58 79 79 116 116 177 251 361 606
    60°C 230V [kVar] 28 28 38 38 59 59 59 59 84 84 106 119
240V [kVar] 29 29 39 39 61 61 61 61 87 87 111 124
400V [kVar] 48 48 44 56 76 76 102 102 145 145 184 206
415V [kVar] 50 50 44 56 76 76 106 106 151 151 191 214
500V [kVar] 50 50 44 56 76 76 113 113 172 182 230 258
690V [kVar] 50 50 45 57 78 78 114 114 174 247 318 356
1000V [kVar] 46 58 79 79 116 116 177 251 361 515
60 Hz Single Capacitor — 40 °C
  200V [kVar] 28 28 39 39 61 61 61 61 85 85 109 121
230V [kVar] 29 29 45 45 70 70 70 70 98 98 125 139
460V [kVar] 50 50 89 89 139 139 139 139 195 195 251 279
600V [kVar] 50 50 116 116 182 182 182 182 255 255 327 364
60 Hz Group Capacitors — 40 °C
  200V [kVar] 28 28 39 39 61 61 61 61 85 85 109 121
230V [kVar] 29 29 42 45 70 70 70 70 98 98 125 139
460V [kVar] 50 50 44 56 76 76 112 112 171 195 251 279
600V [kVar] 50 50 45 57 77 77 114 114 173 246 327 364
Switching of Lamps
Gas discharge lamps AC-5a, 40 °C open [A] 85 90 115 115 144 144 225 225 225 225 315 315 405 450
enclosed [A] 81 90 95 95 122 122 189 189 189 189 270 270 342 383
Individually compensated:
Max. capacitance at expected
Short-circuit current of 10 kA [mF] 4 000 4 700
20 kA [mF] 2 000 2 350
50 kA [mF] 800 940
Filament AC-5b 230/240V [A] 70 76 60 75 107 120 140 140 170 170 210 250 300 420
Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
AC-7a 230V [A]
400V [A]
440V [A]
Switching of Motor Load for Home Appliances (50 Hz)
AC-7b 230V [A]
400V [A]
440V [A]
  

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X
Electronic — EI
Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)
AC-8a 400V [A] 11 18 18 12 16 22 32 38 45 63 72
500V [A] 10 15 15 12 16 22 32 38 45 63 72
690V [A] 8 10 14 20 28 35 42 56
- automatic reset of overload release
AC-8b 400V [A] 5.5 7 9.3 12 13 14 16 24
500V [A] 5.5 7 9.3 12 13 14 16 24
690V [A] 5.5 7 9.3 12 13 14 16 24
Switching of DC Loads
Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C
    1 pole 24V [A] 6 9 9 25 25 32 32 45 45 45 45 50 70
48/60V [A] 4/1 6/1.5 6/1.5 20 20 20 20 25 25 25 25 30 40
110V [A] 0.6 1 1 6 6 6 6 8 8 10 10 9 11
220V [A] 0.2 0.3 0.3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2
440V [A] 0.08 0.1 0.1 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.5
    2 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 45 45 50 70
48/60V [A] 6 8 8 25 25 32 32 45 45 45 45 50 70
110V [A] 4 6 6 25 25 32 32 45 45 45 45 50 70
220V [A] 0.8 1.2 1.2 8 8 8 10 10 10 10 10 10 15
440V [A] 0.2 0.3 0.3 1 1 1 1 1 1 1 1 1 1.5
    3 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 45 63 90
48/60V [A] 6 9 9 25 25 32 32 45 45 45 63 90
110V [A] 6 9 9 25 25 32 32 45 45 45 63 90
220V [A] 3 4 4 25 25 32 32 45 45 45 50 70
440V [A] 0.4 0.6 0.6 3 3 3 3 3.5 3.5 3.5 4 5
Shunt-wound Motors
Starting, reverse current braking, reversing, stepping DC-3, 60 °C
    3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 90
48/60V [A] 4 6 6 25 25 32 32 45 45 50 70
110V [A] 2 3 3 20 20 25 25 30 30 35 70
220V [A] 0.8 1.2 1.2 6 6 6 10 15 15 20 25
440V [A] 0.15 0.2 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Series-wound Motors
Starting, reverse current braking, reversing, stepping DC-5, 60 °C
    3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 90
48/60V [A] 2 3 3 25 25 32 32 45 45 50 70
110V [A] 0.6 1 1 20 20 25 25 30 30 35 70
220V [A] 0.1 0.1 0.1 6 6 6 10 15 15 20 25
440V [A] 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Short Time Withstand ICW, 60 °C
  10 s [A] 60 96 96 170 170 170 215 300 304 304 304 375 700
Resistance and Power Dissipation
Main current circuit resistance [mW] 2.2 2.2 2.2 2.7 2.7 2.7 2 2 2 2 1.5 1.5 0.9
Power dissipation by all circuits at
Ie AC-3/400V
[W] 0.3 0.9 0.9 0.66 1.2 2.1 3.2 5.4 8.2 11.3 8.4 8.3 9.7
Total power dissipation
At Ie AC-3/400V AC control [W] 2.1 2.7 2.7 3.3 3.8 4.7 6.2 8.4 11.2 26.1 37.4 11.5 11
DC control [W] 2.9 3.5 3.5 6.7 7.2 8.1 12.4 14.6 17.4 32.6 43.9 18.4 11
Lifespan
Mechanical AC control [Mil. operations] 15 15 15 13 13 13 13 13 13 10 10 12 10
Mechanical DC control [Mil. operations] 15 15 15 13 13 13 13 13 13 10 10 13 10
Electrical AC-3 (400 V) [Mil. operations] 0.7 0.7 0.7 1.3 1.3 1.3 1.3 1.3 1.3 1 1
Weight
AC Non-Reversing kg (lbs.) 0.16 (0.35) 0.16 (0.35) 0.16 (0.35) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.48 (1.06) 0.49 (1.08) 0.51 (1.12) 1.45 (3.20)
Reversing kg (lbs.) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 1.08 (2.39) 1.08 (2.39) 1.15 (2.54) 3.14 (6.92)
DC Non-Reversing kg (lbs.) 0.2 (0.44) 0.2 (0.44) 0.2 (0.44) 0.6 (1.32) 0.6 (1.32) 0.6 (1.32) 0.73 (1.61) 0.85 (1.87) 0.85 (1.87) 1.0 (2.20) 1.47 (3.24)
Reversing kg (lbs.) 1.27 (2.81) 1.27 (2.81) 1.27 (2.81) 1.53 (3.39) 1.81 (4.0) 1.81 (4.0) 2.13 (4.7) 3.22 (7.1)
  

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 90*200 90*400 95 110 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X X
Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)
AC-8a 400V [A] 85 100
500V [A] 85 100
690V [A] 67 80
- automatic reset of overload release
AC-8b 400V [A] 30 35
500V [A] 30 35
690V [A] 30 35
Switching of DC Loads
Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C
    1 pole 24V [A] 80 80 80 80 135 135 210 210 210 210 300 300 380 425
48/60V [A] 40 40 40 40 135 135 210 210 210 210 300 300 380 425
110V [A] 11 11 11 11 135 135 210 210 210 210 300 300 380 425
220V [A] 2 2 1.8 1.8 3 3 3.3 3.3 3.3 3.3 4.9 4.9 4.9 5.2
440V [A] 0.5 0.5 0.5 0.5 0.6 0.6 0.75 0.75 0.75 0.75 1 1 1 1.2
    2 poles in series 24V [A] 80 80 80 80 135 135 210 210 210 210 300 300 380 425
48/60V [A] 80 80 80 80 135 135 210 210 210 210 300 300 380 425
110V [A] 80 80 80 80 135 135 210 210 210 210 300 300 380 425
220V [A] 15 15 15 15 135 135 210 210 210 210 300 300 380 425
440V [A] 1.5 1.5 1.5 1.5 3 3 3.3 3.3 3.3 3.3 4.9 4.9 4.9 5.2
    3 poles in series 24V [A] 90 100 100 135 135 210 210 210 210 300 300 380 425
48/60V [A] 90 100 100 135 135 210 210 210 210 300 300 380 425
110V [A] 90 100 100 135 135 210 210 210 210 300 300 380 425
220V [A] 80 80 80 135 135 210 210 210 210 300 300 380 425
440V [A] 5 5 5 11 11 11 11 11 11 14 14 14 15
Shunt-wound Motors
Starting, reverse current braking, reversing, stepping DC-3, 60 °C
    3 poles in series 24V [A] 90 100 135 135 210 210 210 210 300