Catalogs >
Industrial Controls Catalog >
Motor Control, IEC >
Contactors >
Bulletin 100S-C/104S-C Safety Contactors
Bulletin 100S-C/104S-C Safety Contactors
Product Selection
3-Pole AC- and DC-Operated Contactors
| Ie [A]
|
Ratings for Switching AC Motors — AC-2, AC-3, AC-4
|
Aux. Contacts
|
Cat. No.¬ T
|
| 3Æ kW (50 Hz)
|
Hp (60 Hz)
|
|
|
| AC-3
|
AC-1
|
230V
|
400V/ 415V
|
500V
|
690V
|
1Æ
|
3Æ
|
|
|
| 115V
|
230V
|
200V
|
230V
|
460V
|
575V
|
N.O.
|
N.C.
|
| 9
|
32
|
3
|
4
|
4
|
4
|
1/2
|
1-1/2
|
2
|
2
|
5
|
7-1/2
|
0
|
5
|
100S-C09Ä05BC
|
| 1
|
4
|
100S-C09Ä14BC
|
| 12
|
32
|
4
|
5.5
|
5.5
|
5.5
|
1/2
|
2
|
3
|
3
|
7-1/2
|
10
|
0
|
5
|
100S-C12Ä05BC
|
| 1
|
4
|
100S-C12Ä14BC
|
| 16
|
32
|
5.5
|
7.5
|
7.5
|
7.5
|
1
|
3
|
5
|
5
|
10
|
15
|
0
|
5
|
100S-C16Ä05BC
|
| 1
|
4
|
100S-C16Ä14BC
|
| 23
|
32
|
7.5
|
11
|
13
|
10
|
2
|
3
|
5
|
7-1/2
|
15
|
15
|
0
|
5
|
100S-C23Ä05BC
|
| 1
|
4
|
100S-C23Ä14BC
|
| 30
|
65
|
10
|
15
|
15
|
15
|
2
|
5
|
7-1/2
|
10
|
20
|
25
|
0
|
4
|
100S-C30Ä04BC
|
| 1
|
4
|
100S-C30Ä14BC
|
| 37
|
65
|
11
|
18.5/20
|
20
|
18.5
|
3
|
5
|
10
|
10
|
25
|
30
|
0
|
4
|
100S-C37Ä04BC
|
| 1
|
4
|
100S-C37Ä14BC
|
| 43
|
85
|
13
|
22
|
25
|
22
|
3
|
7-1/2
|
10
|
15
|
30
|
30
|
0
|
4
|
100S-C43Ä04BC
|
| 1
|
4
|
100S-C43Ä14BC
|
| 60
|
100
|
18.5
|
32
|
37
|
32
|
5
|
10
|
15
|
20
|
40
|
50
|
0
|
4
|
|
100S-C60Ä04BC
|
| 1
|
4
|
|
100S-C60Ä14BC
|
| 72
|
100
|
22
|
40
|
45
|
40
|
5
|
15
|
20
|
25
|
50
|
60
|
0
|
4
|
|
100S-C72Ä04BC
|
| 1
|
4
|
|
100S-C72Ä14BC
|
| 85
|
100
|
25
|
45
|
55
|
45
|
7-1/2
|
15
|
25
|
30
|
60
|
60
|
0
|
4
|
|
100S-C85Ä04BC
|
| 1
|
4
|
|
100S-C85Ä14BC
|
|
|
| ¬ For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
|
| T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä05BC becomes Cat. No. 100S-C09Ä05C.
|
| Bifurcated front-mount auxiliary contacts on Cat. Nos. 100S-C60…C85 conform to mirror contact performance only.
|
ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position
Cat. No. 100S-C09Ä05C Line Side
|
|
Cat. No. 100S-C09UÄ05C Load Side
|
|
4-Pole AC- and DC-Operated Contactors
| Ie [A]
|
Ratings for Switching AC Motors
|
Contact Configuration
|
Cat. No.¬
|
| AC-2, AC-3, AC-4
|
Hp (60 Hz)
|
| 3Æ kW (50 Hz)T
|
Main Pole
|
Auxillary Contacts
|
| AC-3
|
AC-1
|
230V
|
400V/ 415V
|
500V
|
690V
|
1Æ
|
3Æ T
|
|
|
|
|
|
|
|
|
|
| 115V
|
230V
|
200V
|
230V
|
460V
|
575V
|
N.O.
|
N.C.
|
N.O.
|
N.C.
|
| 9
|
32
|
3
|
4
|
4
|
4
|
1/2
|
1-1/2
|
2
|
2
|
5
|
7-1/2
|
4
|
0
|
0
|
4
|
100S-C09Ä404BC
|
| 3
|
1
|
0
|
4
|
100S-C09Ä304BC
|
| 12
|
32
|
4
|
5.5
|
5.5
|
5.5
|
1/2
|
2
|
3
|
3
|
7-1/2
|
10
|
4
|
0
|
0
|
4
|
100S-C12Ä404BC
|
| 3
|
1
|
0
|
4
|
100S-C12Ä304BC
|
| 16
|
32
|
5.5
|
7.5
|
7.5
|
7.5
|
1
|
3
|
5
|
5
|
10
|
15
|
4
|
0
|
0
|
4
|
100S-C16Ä404BC
|
| 3
|
1
|
0
|
4
|
100S-C16Ä304BC
|
| 23
|
32
|
7.5
|
11
|
13
|
10
|
2
|
3
|
5
|
7-1/2
|
15
|
15
|
4
|
0
|
0
|
4
|
100S-C23Ä404BC
|
| 3
|
1
|
0
|
4
|
100S-C23Ä304BC
|
|
|
| ¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
|
| T Three-phase ratings only apply to contactors with at least three N.O. power poles.
|
| If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä404BC becomes Cat. No. 100S-C09Ä404C.
|
ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position
Reversing AC- and DC-Operated Contactors
- 3 Main Contacts
- Includes Mechanical/Electrical Interlock
- Includes Reversing Power Wiring
| Ie [A]
|
Ratings for Switching AC Motors
|
Aux. Contacts Installed per Contactor
|
Cat. No.¬ T
|
| AC-2, AC-3, AC-4
|
|
|
| 3Æ kW (50 Hz)
|
Hp (60 Hz)
|
| AC-3
|
AC-1
|
230V
|
400V/ 415V
|
500V
|
690V
|
1Æ
|
3Æ
|
|
|
| 115V
|
230V
|
200V
|
230V
|
460V
|
575V
|
N.O.
|
N.C.
|
| 9
|
32
|
3
|
4
|
4
|
4
|
1/2
|
1-1/2
|
2
|
2
|
5
|
7-1/2
|
0
|
6
|
104S-C09Ä012BC
|
| 1
|
5
|
104S-C09Ä210BC
|
| 12
|
32
|
4
|
5.5
|
5.5
|
5.5
|
1/2
|
2
|
3
|
3
|
7-1/2
|
10
|
0
|
6
|
104S-C12Ä012BC
|
| 1
|
5
|
104S-C12Ä210BC
|
| 16
|
32
|
5.5
|
7.5
|
7.5
|
7.5
|
1
|
3
|
5
|
5
|
10
|
15
|
0
|
6
|
104S-C16Ä012BC
|
| 1
|
5
|
104S-C16Ä210BC
|
| 23
|
32
|
7.5
|
11
|
13
|
10
|
2
|
3
|
5
|
7-1/2
|
15
|
15
|
0
|
6
|
104S-C23Ä012BC
|
| 1
|
5
|
104S-C23Ä210BC
|
| 30
|
65
|
10
|
15
|
15
|
15
|
2
|
5
|
7-1/2
|
10
|
20
|
25
|
0
|
5
|
104S-C30Ä010BC
|
| 1
|
5
|
104S-C30Ä210BC
|
| 37
|
65
|
11
|
18.5/20
|
20
|
18.5
|
3
|
5
|
10
|
10
|
25
|
30
|
0
|
5
|
104S-C37Ä010BC
|
| 1
|
5
|
104S-C37Ä210BC
|
| 43
|
85
|
13
|
22
|
25
|
22
|
3
|
7-1/2
|
10
|
15
|
30
|
30
|
0
|
5
|
104S-C43Ä010BC
|
| 1
|
5
|
104S-C43Ä210BC
|
| 60
|
100
|
18.5
|
32
|
37
|
32
|
5
|
10
|
15
|
20
|
40
|
50
|
0
|
5
|
§
|
104S-C60Ä010BC
|
| 1
|
5
|
§
|
104S-C60Ä210BC
|
| 72
|
100
|
22
|
40
|
45
|
40
|
5
|
15
|
20
|
25
|
50
|
60
|
0
|
5
|
§
|
104S-C72Ä010BC
|
| 1
|
5
|
§
|
104S-C72Ä210BC
|
| 85
|
100
|
25
|
45
|
55
|
45
|
7-1/2
|
15
|
25
|
30
|
60
|
60
|
0
|
5
|
§
|
104S-C85Ä010BC
|
| 1
|
5
|
§
|
104S-C85Ä210BC
|
|
|
| ¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
|
| T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C09Ä05BC becomes Cat. No. 104S-C09Ä05C.
|
| One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock.
|
| § Bifurcated front-mount auxiliary contacts on Cat. Nos. 104S-C60…C85 conform to mirror contact performance only.
|
Ä Coil Voltage Code and Terminal Position
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09Ä05BC becomes Cat. No.100S-C09D05BC.
| [V]
|
12
|
24
|
32
|
36
|
42
|
48
|
100
|
100-110
|
110
|
120
|
127
|
200
|
200-220
|
208
|
208-240
|
220-230
|
| AC, 50 Hz
|
R
|
K
|
V
|
W
|
X
|
Y
|
KP
|
—
|
D
|
P
|
S
|
KG
|
L
|
—
|
—
|
F
|
| AC, 60 Hz
|
Q
|
J
|
—
|
V
|
—
|
X
|
—
|
KP
|
—
|
D
|
—
|
—
|
KG
|
H
|
L
|
—
|
| AC, 50/60 Hz
|
|
KJ
|
—
|
—
|
—
|
KY
|
KP
|
—
|
KD
|
—
|
—
|
KG
|
KL
|
—
|
—
|
KL
|
|
|
| [V]
|
230
|
230-240
|
240
|
277
|
347
|
380
|
380-400
|
400
|
400-415
|
440
|
480
|
500
|
550
|
600
|
|
| AC, 50 Hz
|
—
|
VA
|
T
|
—
|
—
|
—
|
N
|
—
|
G
|
B
|
—
|
M
|
C
|
—
|
| AC, 60 Hz
|
—
|
—
|
A
|
T
|
I
|
E
|
—
|
—
|
—
|
N
|
B
|
—
|
—
|
C
|
| AC, 50/60 Hz
|
KF
|
—
|
KA
|
—
|
—
|
—
|
—
|
KN
|
—
|
KB
|
—
|
—
|
—
|
—
|
|
|
| [V]
|
9
|
12
|
24
|
36
|
48
|
60
|
64
|
72
|
80
|
110
|
115
|
125
|
220
|
230
|
250
|
| 100S-C09…C43
|
Standard
|
DC
|
ZR
|
ZQ
|
ZJ
|
ZW
|
ZY
|
ZZ
|
ZB
|
ZG
|
ZE
|
ZD
|
ZP
|
ZS
|
ZA
|
ZF
|
ZT
|
| with Integrated Diode
|
—
|
—
|
DJ
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
| Electronic with Integrated Diode
|
—
|
—
|
EJ
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
| 100S-C60…C85
|
with Integrated Diode
|
DR
|
DQ
|
DJ
|
DW
|
DY
|
DZ
|
DB
|
DG
|
DE
|
DD
|
DP
|
DS
|
DA
|
DF
|
DT
|
|
|
Coil Terminal Position
- All contactors are delivered with the coil terminals located on the line side.
- For load side coil terminations, insert a U prior to the coil voltage code.
Example: Cat. No. 100S-C09UD05BC.
Terminal Markings