Bulletin 100S-C/104S-C Safety Contactors

Introduction Standards Compliance and Certifications Product Selection Terminal Markings Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications Bulletin 100S-C/104S-C Approximate Dimensions
Product Selection

3-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Aux. Contacts Cat. No.¬ T 
3Æ kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66a-3 Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ   Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 0 5 100S-C09Ä05BC
1 4 100S-C09Ä14BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 0 5 100S-C12Ä05BC
1 4 100S-C12Ä14BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 0 5 100S-C16Ä05BC
1 4 100S-C16Ä14BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 0 5 100S-C23Ä05BC
1 4 100S-C23Ä14BC
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 4 100S-C30Ä04BC
1 4 100S-C30Ä14BC
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 4 100S-C37Ä04BC
1 4 100S-C37Ä14BC
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 4 100S-C43Ä04BC
1 4 100S-C43Ä14BC
60 100 18.5 32 37 32 5 10 15 20 40 50 0 4 ‡  100S-C60Ä04BC
1 4 ‡  100S-C60Ä14BC
72 100 22 40 45 40 5 15 20 25 50 60 0 4 ‡  100S-C72Ä04BC
1 4 ‡  100S-C72Ä14BC
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 4 ‡  100S-C85Ä04BC
1 4 ‡  100S-C85Ä14BC
  
¬ For other contact configurations and full product details, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä05BC becomes Cat. No. 100S-C09Ä05C.
‡ Bifurcated front-mount auxiliary contacts on Cat. Nos. 100S-C60…C85 conform to mirror contact performance only.

ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Click to enlarge - 100C_104C-68-1
Cat. No.
100S-C09Ä05C
Line Side


Click to enlarge - 100C_104C-68-2
Cat. No.
100S-C09UÄ05C
Load Side


4-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors Contact Configuration Cat. No.¬ ‡ 
AC-2, AC-3, AC-4 Hp (60 Hz)
3Æ kW (50 Hz)T  Main Pole Auxillary Contacts
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ T  Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
      Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C. N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 4 0 0 4 100S-C09Ä404BC
3 1 0 4 100S-C09Ä304BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 4 0 0 4 100S-C12Ä404BC
3 1 0 4 100S-C12Ä304BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 4 0 0 4 100S-C16Ä404BC
3 1 0 4 100S-C16Ä304BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 4 0 0 4 100S-C23Ä404BC
3 1 0 4 100S-C23Ä304BC
  
¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T Three-phase ratings only apply to contactors with at least three N.O. power poles.
‡ If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09Ä404BC becomes Cat. No. 100S-C09Ä404C.

ÄCoil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Reversing AC- and DC-Operated Contactors


Click to enlarge - 100S-C_104S-C-77-2


Ie [A] Ratings for Switching AC Motors Aux. Contacts
Installed per Contactor
Cat. No.¬ T 
AC-2, AC-3, AC-4 Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
3Æ kW (50 Hz) Hp (60 Hz)
AC-3 AC-1 230V 400V/
415V
500V 690V 1Æ 3Æ   Click to enlarge - 100S-C_104S-C-77-5
115V 230V 200V 230V 460V 575V N.O. N.C. ‡ 
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 0 6 104S-C09Ä012BC
1 5 104S-C09Ä210BC
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 0 6 104S-C12Ä012BC
1 5 104S-C12Ä210BC
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 0 6 104S-C16Ä012BC
1 5 104S-C16Ä210BC
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 0 6 104S-C23Ä012BC
1 5 104S-C23Ä210BC
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 5 104S-C30Ä010BC
1 5 104S-C30Ä210BC
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 5 104S-C37Ä010BC
1 5 104S-C37Ä210BC
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 5 104S-C43Ä010BC
1 5 104S-C43Ä210BC
60 100 18.5 32 37 32 5 10 15 20 40 50 0 5 §  104S-C60Ä010BC
1 5 §  104S-C60Ä210BC
72 100 22 40 45 40 5 15 20 25 50 60 0 5 §  104S-C72Ä010BC
1 5 §  104S-C72Ä210BC
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 5 §  104S-C85Ä010BC
1 5 §  104S-C85Ä210BC
  
¬ For other contact configurations, please contact your local Rockwell Automation sales office or Allen-Bradley distributor.
T If standard cross-stamped front-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C09Ä05BC becomes Cat. No. 104S-C09Ä05C.
‡ One of the N.C. auxiliary contacts is supplied as part of the mechanical/electrical interlock.
§ Bifurcated front-mount auxiliary contacts on Cat. Nos. 104S-C60…C85 conform to mirror contact performance only.

Ä Coil Voltage Code and Terminal Position

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz: Cat. No. 100S-C09Ä05BC becomes Cat. No.100S-C09D05BC.

[V] 12 24 32 36 42 48 100 100-110 110 120 127 200 200-220 208 208-240 220-230
AC, 50 Hz R K V W X Y KP D P S KG L F
AC, 60 Hz Q J V X KP D KG H L
AC, 50/60 Hz KJ KY KP KD KG KL KL
  
[V] 230 230-240 240 277 347 380 380-400 400 400-415 440 480 500 550 600  
AC, 50 Hz VA T N G B M C
AC, 60 Hz A T I E N B C
AC, 50/60 Hz KF KA KN KB
  

[V] 9 12 24 36 48 60 64 72 80 110 115 125 220 230 250
100S-C09…C43 Standard DC ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode DJ
Electronic with Integrated Diode EJ
100S-C60…C85 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
  

Coil Terminal Position


Terminal Markings