Bulletin 100-C Contactors

Click to enlarge - 100Line-3-5


Click to enlarge - 100C_104C-67-2


Bulletin 100-C/104-C — IEC Contactors


The Bulletin 100-C/104-C IEC contactor family, along with a wide range of common accessories and Bulletin 193 solid-state overload relays, provides the most compact and flexible starter component system available.

Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories and/or replacement coils.

Standards Compliance and Certifications

Standards Compliance

EN/IEC 60947-4-1, 60947-5-1
IEC 60947 Type “2” Coordination
CSA C22.2 No. 14
UL 508
Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS


Certifications

CE Marked
cULus Listed (File No. E3125; Guide NLDX, NLDX7)
CCC


Product Selection

3-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Aux. Contacts Cat. No.
3-Phase kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/415V 500V 690V 1-Phase 3-Phase
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 1 0 §  100-C09Ä10
0 1 §  100-C09Ä01
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 1 0 §  100-C12Ä10
0 1 §  100-C12Ä01
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 1 0 §  100-C16Ä10
0 1 §  100-C16Ä01
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 1 0 100-C23Ä10
0 1 100-C23Ä01
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 0 100-C30Ä00
1 0 100-C30Ä10
0 1 100-C30Ä01
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 0 100-C37Ä00
1 0 100-C37Ä10
0 1 100-C37Ä01
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 0 100-C43Ä00
1 0 100-C43Ä10
0 1 100-C43Ä01
60 100 18.5 32 37 32 5 10 15 20 40 50 0 0 100-C60Ä00
1 0 100-C60Ä10
0 1 100-C60Ä01
72 100 22 40 45 40 5 15 20 25 50 60 0 0 100-C72Ä00
1 0 100-C72Ä10
0 1 100-C72Ä01
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 0 100-C85Ä00
1 0 100-C85Ä10
0 1 100-C85Ä01
97 130 30 55 55 55 10 15 30 30 75 75 0 0 100-C97Ä00
1 0 100-C97Ä10
0 1 100-C97Ä01
  
§ For screwless terminals, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C09Ä10 becomes Cat. No. 100-CR09Ä10.

Ä Coil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


4-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3 Contact Configuration, Main Pole Cat. No.
3-Phase kW (50 Hz)⋆  Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/415V 500V 690V 1-Phase 3-Phase ⋆ 
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 4 0 §  100-C09Ä400
3 1 §  100-C09Ä300
2 2 §  100-C09Ä200
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 4 0 §  100-C12Ä400
3 1 §  100-C12Ä300
2 2 §  100-C12Ä200
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 4 0 §  100-C16Ä400
3 1 §  100-C16Ä300
2 2 §  100-C16Ä200
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 4 0 100-C23Ä400
3 1 100-C23Ä300
2 2 100-C23Ä200
37 75 11 18.5/20 20 18.5 3 5 10 10 25 30 4 0 100-C40Ä400
2 2 100-C40Ä200
85 130 25 45 55 45 7-1/2 15 25 30 60 50 4 0 100-C90Ä400
2 2 100-C90Ä200
  
⋆ Three-phase ratings apply only to contactors with at least three N.O. power poles.
§ For screwless terminals, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C09Ä400 becomes Cat. No. 100-CR09Ä400.

Ä Coil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Reversing AC- and DC-Operated Contactors

Click to enlarge - 100C_104C-67-2 Click to enlarge - 100C_104C-69-2 Click to enlarge - 100C_104C-69-3

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Auxiliary Contacts
Installed per Contactor
Cat. No.
3-Phase kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/415V 500V 690V 1-Phase 3-Phase
115V 230V 200V 230V 460V 575V N.O. N.C.⋆ 
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 1 1 104-C09Ä22
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 1 1 104-C12Ä22
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 1 1 104-C16Ä22
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 1 1 104-C23Ä22
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 1 104-C30Ä02
1 1 104-C30Ä22
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 1 104-C37Ä02
1 1 104-C37Ä22
43 85 13 22 25 22 3 7.5 10 15 30 30 0 1 104-C43Ä02
1 1 104-C43Ä22
60 100 18.5 32 37 32 5 10 15 20 40 50 0 1 104-C60Ä02
1 1 104-C60Ä22
72 100 22 40 45 40 5 15 20 25 50 60 0 1 104-C72Ä02
1 1 104-C72Ä22
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 1 104-C85Ä02
1 1 104-C85Ä22
97 130 30 55 55 55 10 15 30 30 75 75 0 1 104-C97Ä02
1 1 104-C97Ä22
  

⋆ The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock.


Ä Coil Voltage Code and Terminal Position

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz:
Cat. No. 100-C09Ä10 becomes Cat. No.100-C09D10.


[V] 12 24 32 36 42 48 100 100-110 110 120 127 200 200-220 208 208-240 220-230 230 230-240 240 277 347 380 380-400 400 400-415 440 480 500 550 600
Hz
50 Hz R K V W X Y KP D P S KG L F VA T N G B M C
60 Hz Q J V X KP D KG H L A T I E N B C
50/60 Hz KJ KY KP KD KG KL§  KL§  KF KA KN KB
  
§ Not available on 100/104-C90 or -C97 contactors.

DC Voltages [V] 9 12 24 36 48 48-72 60 64 72 80 110 110-125 115 125 220 220-250 230 250
100-C09…C43 Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode DJ
Electronic with Integrated Diode EQ EJ EY ED EA
100-C60…C97 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
  

Coil Terminal Position

  • All contactors are delivered with the coil terminals located on the line side.


  • For load side coil terminations, insert a “U” prior to the coil voltage code.
    Ordering example: Cat. No. 100-C09UD10.


  • Click to enlarge - 100C_104C-68-1
    Cat. No.100-C09Ä10Line Side


    Click to enlarge - 100C_104C-68-2
    Cat. No.100-C09UÄ10Load Side

    Assignment of Contacts

    Device Combinations in Accordance with IEC 60947-1 / -4-1

    Auxiliary Contact Blocks Contactors 100-C (AC and DC Control)
      Circuit Diagram Control 100-C09_Ä10
    100-C12_Ä10
    100-C16_Ä10
    100-C23_Ä10
    100-C09_Ä01
    100-C12_Ä01
    100-C16_Ä01
    100-C23_Ä01
    100-C30_Ä00
    100-C37_Ä00
    100-C43_Ä00
    100-C60_Ä00
    100-C72_Ä00
    100-C85_Ä00
    100-C97_Ä00
    100-C09_Ä400
    100-C12_Ä400
    100-C16_Ä400
    100-C23_Ä400
    100-C40_Ä400
    100-C90_Ä400
    100-C09_Ä300
    100-C12_Ä300
    100-C16_Ä300
    100-C23_Ä300
    100-C09_Ä200
    100-C12_Ä200
    100-C16_Ä200
    100-C23_Ä200
    100-C40_Ä200
    100-C90_Ä200
    Click to enlarge - 100-C_3pol_10_Dia Click to enlarge - 100-C_3pol_01_Dia Click to enlarge - 100-C_3pol_00_Dia Click to enlarge - 100-C_4pol_400_Dia Click to enlarge - 100-C_3pol_300_Dia Click to enlarge - 100-C_2pol_200_Dia
    Front Mounting ⋆ 
    100-FA02,
    100-FAB02
    Click to enlarge - 100-FA02_Dia AC/DC 10 + 02 = 12 01 + 02 = 03 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02
    100-FA11,
    100-FAB11
    Click to enlarge - 100-FA11_Dia AC/DC 10 + 11 = 21 01 + 11 = 12 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11
    100-FB11,
    100-FBB11
    Click to enlarge - 100-FB11_Dia AC/DC 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11
    100-FC11,
    100-FCB11
    Click to enlarge - 100-FC11_Dia AC/DC 10 + 11 = 21
    100-FA20,
    100-FAB20
    Click to enlarge - 100-FA20_Dia AC/DC 10 + 20 = 30 01 + 20 = 21 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20
    100-FBL11 ‡  Click to enlarge - 100-FBL11_Dia AC/DC 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11
    100-FA22,
    100-FAB22
    Click to enlarge - 100-FA22_Dia AC/DC 10 + 22 = 32 01 + 22 = 23 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22
    100-FB22,
    100-FBB22
    Click to enlarge - 100-FB22_Dia AC/DC 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22
    100-FC22,
    100-FCB22
    Click to enlarge - 100-FC22_Dia AC/DC 10 + 22 = 32
    100-FA31,
    100-FAB31
    Click to enlarge - 100-FA31_Dia AC/DC 10 + 31 = 41 01 + 31 = 32 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31
    100-FA40,
    100-FAB40
    Click to enlarge - 100-FA40_Dia AC/DC 10 + 40 = 50 01 + 40 = 41 00 + 40 = 40 00 + 40 = 40 00 + 40 = 40 00 + 40 = 40
    100-FAL22 ‡  Click to enlarge - 100-FAL22_Dia AC/DC 10 + L22 = L32 01 + L22 = L23 00 + L22 = L22 00 + L22 = L22 00 + L22 = L22 00 + L22 = L22
    100-FA04,
    100-FAB04
    Click to enlarge - 100-FA04_Dia AC/DC 10 + 04 = 14 01 + 04 = 05 00 + 04 = 04 00 + 04 = 04 00 + 04 = 04 00 + 04 = 04
    100-FA13,
    100-FAB13
    Click to enlarge - 100-FA13_Dia AC/DC 10 + 13 = 23 01 + 13 = 14 00 + 13 = 13 00 + 13 = 13 00 + 13 = 13 00 + 13 = 13
    100-FB02,
    100-FBB02
    Click to enlarge - 100-FB02_Dia AC/DC 10 + 02 = 12 01 + 02 = 03 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02
    100-FB20,
    100-FBB20
    Click to enlarge - 100-FB20_Dia AC/DC 10 + 20 = 30 01 + 20 = 21 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20
    100-FC31,
    100-FCB31
    Click to enlarge - 100-FC31_Dia AC/DC 10 + 31 = 41 01 + 31 = 32 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31
      
    ⋆ Up to 8 auxiliary contacts possible: contactor + front mounted (AC max. 4 N.C. / DC max. 4 N.C.), side mounted (AC max. 2 N.O. / DC max. 2 N.O. and max. 2 N.C.).
    ‡ Early make and/or late break.
    § Double numbering: because of double numbering only left-side mounting is recommended.

    Auxiliary Contact Blocks Contactors 100-C (AC and DC Control)
      Circuit Diagram Control 100-C09_Ä10
    100-C12_Ä10
    100-C16_Ä10
    100-C23_Ä10
    100-C09_Ä01
    100-C12_Ä01
    100-C16_Ä01
    100-C23_Ä01
    100-C30_Ä00
    100-C37_Ä00
    100-C43_Ä00
    100-C60_Ä00
    100-C72_Ä00
    100-C85_Ä00
    100-C97_Ä00
    100-C09_Ä400
    100-C12_Ä400
    100-C16_Ä400
    100-C23_Ä400
    100-C40_Ä400
    100-C90_Ä400
    100-C09_Ä300
    100-C12_Ä300
    100-C16_Ä300
    100-C23_Ä300
    100-C09_Ä200
    100-C12_Ä200
    100-C16_Ä200
    100-C23_Ä200
    100-C40_Ä200
    100-C90_Ä200
    Click to enlarge - 100-C_3pol_10_Dia Click to enlarge - 100-C_3pol_01_Dia Click to enlarge - 100-C_3pol_00_Dia Click to enlarge - 100-C_4pol_400_Dia Click to enlarge - 100-C_3pol_300_Dia Click to enlarge - 100-C_2pol_200_Dia
    Side Mounting ⋆ 
    100-SB01 Click to enlarge - 100-SB01_Dia AC/DC 10 + 01 = 11 01 + 01 = 02 §  00 + 01 = 01 00 + 01 = 01 00 + 01 = 01 00 + 01 = 01
    100-SB10 Click to enlarge - 100-SB10_Dia AC/DC 10 + 10 = 20 §  01 + 10 = 11 00 + 10 = 10 00 + 10 = 10 00 + 10 = 10 00 + 10 = 10
    100-SB02 Click to enlarge - 100-SB02_Dia AC/DC 10 + 02 = 12 §  00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02
    100-SB11 Click to enlarge - 100-SB11_Dia AC/DC 10 + 11 = 21 §  01 + 11 = 12 §  00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11
    100-SB20 Click to enlarge - 100-SB20_Dia AC/DC 10 + 20 = 30 §  01 + 20 = 21 §  00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20
    100-SBL11 ‡  Click to enlarge - 100-SBL11_Dia AC/DC 10 + L11 = L21 §  01 + L11 = L12 §  00 + L11 = L11 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11
      
    ⋆ Up to 8 auxiliary contacts possible: contactor + front mounted (AC max. 4 N.C. / DC max. 4 N.C.), side mounted (AC max. 2 N.O. / DC max. 2 N.O. and max. 2 N.C.).
    ‡ Early make and/or late break.
    § Double numbering: because of double numbering only left-side mounting is recommended.

    Bulletin 100-C/104-C Accessories

    Auxiliary Contacts (For 100-C09…C97 contactors)

      Description Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a Connection Diagrams For Use With Standard Auxiliary Contact Cat. No.§  Bifurcated Auxiliary Contact Cat. No.
    N.O. N.C.
    Click to enlarge - 100-C_104-C-86-3 Auxiliary Contact Blocks for Front Mounting⋆ 
  • 2- and 4-pole

  • Quick and easy mounting without tools

  • Electronic-compatible contacts down to 17V, 5 mA

  • Mechanically linked performance between N.O. and N.C. poles and to the main contactor poles (except for L types)

  • Models with equal function with several terminal numbering choices

  • 1L = Late break N.C./early make N.O.

  • Bifurcated version for switching down to 5V, 3 mA also available
  • 0 2 Click to enlarge - 100-C_104-C-86-6 100-C all 100-FA02 100-FAB02
    C30Ä00…C97Ä00 100-FB02 100-FBB02
    1 1 100-C all 100-FA11 100-FAB11
    C30Ä00…C97Ä00 100-FB11 100-FBB11
    C09Ä10…C23Ä10 100-FC11 100-FCB11
    2 0 100-C all 100-FA20 100-FAB20
    C30Ä00…C97Ä00 100-FB20 100-FBB20
    1L 1L 100-C all 100-FAL11
    C30Ä00…C97Ä00 100-FBL11
    Click to enlarge - 100-C_104-C-86-4 0 4 100-C all 100-FA04 100-FAB04
    1 3 100-C all 100-FA13 100-FAB13
    2 2 100-C all 100-FA22 100-FAB22
    C30Ä00…C97Ä00 100-FB22 100-FBB22
    C09Ä10…C23Ä10 100-FC22 100-FCB22
    3 1 100-C all 100-FA31 100-FAB31
    C09Ä10…C23Ä10 100-FC31 100-FCB31
    4 0 100-C all 100-FA40 100-FAB40
    1+1L 1+1L 100-C all 100-FAL22
    Click to enlarge - 100-C_104-C-86-5 Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations⋆ 
  • 1- and 2-pole

  • Two-way numbering for right or left mounting on the contactor

  • Quick and easy mounting without tools

  • Electronic-compatible contacts down to 17V, 10 mA

  • Mirror contact performance to the main contactor poles

  • 1L = Late break N.C./early make N.O.
  •   
    0  
    1 Click to enlarge - 100-C_104-C-86-7 100-C all 100-SA01
      
    1  
    0 100-C all 100-SA10
      
    0  
    2 100-C all 100-SA02
    Click to enlarge - 100-C_104-C-86-8   
    1  
    1 100-C all 100-SA11
      
    2  
    0 100-C all 100-SA20
      
    1L  
    1L 100-C all 100-SAL11
    Click to enlarge - 100-C_104-C-86-9 Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations⋆ 
  • 1- and 2-pole

  • Two-way numbering for right or left mounting on the contactor

  • Quick and easy mounting without tools

  • Electronic-compatible contacts down to 17V, 10 mA

  • Mirror contact performance to the main contactor poles

  • 1L = Late break N.C./early make N.O.
  •   
    0  
    1 Click to enlarge - 100-C_104-C-86-10 100-C 100-SB01
      
    1  
    0 100-C‡  100-SB10
      
    0  
    2 100-C‡  100-SB02
    Click to enlarge - 100-C_104-C-86-11   
    1  
    1 100-C‡  100-SB11
    2  
      
    0 100-C‡  100-SB20
      
    1L  
    1L 100-C‡  100-SBL11
      
    ⋆ Max. number of auxiliary contacts that may be mounted:
        AC and 24V DC electronic coil contactors — max. 4 N.O. contacts on the front of the contactor, 2 N.O. contacts on the side, 4 N.C. front or side, 6 total.
        DC coil contactors — max. 4 N.O. contacts on the front of the contactor or max 2 N.O. contacts on the side, 4 N.C. front or side, 4 total.
    ‡ Double numbering — Left-side mounting only is recommended for Cat. No. 100-C09…100-C23 due to double numbering.
    § For screwless terminals (front mount only), insert "CR" after the "100-" in the catalog number. Example: Cat. No. 100-FA02 becomes Cat. No. 100-CRFA02.

    Control Modules (For 100-C09…C97 contactors)

      Description Connection Diagrams For Use With Cat. No.
    Click to enlarge - 100-C_104-C-87-1 Pneumatic Timing Modules
  • Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.
  • On-Delay  
    0.3…30 s Range
    Click to enlarge - 100-C_104-C-87-2 100-C or 700-CF with AC coils or DC electronic coils§    
    100-FPTA30
    1.8…180 s Range 100-FPTA180
    Off-Delay  
    0.3…30 s Range
    Click to enlarge - 100-C_104-C-87-3 100-C all, 700-CF all   
    100-FPTB30
    1.8…180 s Range 100-FPTB180
    Click to enlarge - 100-ETA3 L_gs- Electronic Timing Modules — On-Delay
    Delay of the contactor or control relay solenoid.
    The contactor or control relay is energized at the end of the delay time.
    0.1…3 s Range Click to enlarge - 100-C_104-C-87-5 100-C or 700-CF with
    110…240V,
    50/60 Hz or
    110…250V DC coils
    100-ETA3
    1…30 s Range 100-ETA30
    10…180 s Range 100-ETA180
    0.1…3 s Range Click to enlarge - 100-C_104-C-87-6 100-C or 700-CF with 24…48V DC coils 100-ETAZJ3
    0.1…3 s Range 100-ETA3
    10…180 s Range 100-ETAZJ180
    Click to enlarge - 100-ETB3 L_gs Electronic Timing Modules — Off-Delay
    Delay of the contactor or control relay solenoid.
    After interruption of the control signal, the contactor or control relay is deenergized at the end of the delay time.
    0.3…3 s Range Click to enlarge - 100-C_104-C-87-8 100-C09…C37 or 700-CF with 24V 50/60 Hz coils 100-ETBKJ3
    1…30 s Range 100-ETBKJ30
    10…180 s Range 100-ETBKJ180
    0.3…3 s Range 100-C or 700-CF with 110…240V 50/60 Hz coils 100-ETB3
    1…30 s Range 100-ETB30
    10…180 s Range 100-ETB180
    Click to enlarge - 100-C_104-C-87-9 Electronic Timing Modules
  • Delay of the contactor solenoid. Contactor K 3 (Y) is de-energized (off) and K 2 (D) is energized (on) after the end of the set Y end time. (Switching delay at 50 ms.)

  • Continuous adjustment range

  • High repeat accuracy
  • Transition Time Y Contactor
    1…30 s Range
    Click to enlarge - 100-C_104-C-87-10 100-C with 110…240V, 50/60 Hz coils 100-ETY30
    Click to enlarge - 100-C_104-C-87-11 Mechanical Interlocks
  • For interlocking of two contactors.

  • Common interlock for all Bul. 100-C contactor sizes

  • Interlocking of different sizes possible

  • Mechanical and electrical interlocking possible in one module by means of integrated auxiliary contacts

  • 9 mm dovetail connector included
  • Mechanical only,
    without auxiliary contacts
    Click to enlarge - 100-C_104-C-87-12 100-C (except 100-C40, -C90) 100-MCA00
    Mechanical/ electrical interlock with 2 N.C. auxiliary contacts Click to enlarge - 100-C_104-C-87-13 100-C (except 100-C40, -C90) 100-MCA02
    Click to enlarge - 100-C_104-C-87-15 Mechanical Latch
  • Following contactor latching, the contactor coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66).

  • Electrical or manual release

  • 1 N.O. + 1 N.C. auxiliary contacts

  • Suitable for all Bul. 100-C contactor sizes, 9…97 A
  • Maximum command duration 0.03…10 s Click to enlarge - 100-C_104-C-87-14 100-C with AC or 24V DC electronic coils (except 100-C90) 100-FL11Ä
      
    § Cannot be used with side-mounted auxiliary contacts on 700-CF DC relays.

    Ä Coil Voltage Code

    The cat. no. as listed is incomplete. Select a voltage suffix code from the table below to complete the cat. no. Example: 120V, 60 Hz:
    Cat. No. 100-FL11Ä becomes Cat. No. 100-FL11D.


    Voltage⋆  [V] 24 48 100 110 120 230…240 240 277 380…400 400…415 440 480
    50 Hz K Y KP D VA KA N G B
    60 Hz J D KA T N B
      
    ⋆ For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

    Control Modules (For 100-C09…C97 contactors), Continued

    Click to enlarge - 100-C_104-C-88-1 Description Voltage Range Connection Diagrams For Use With Cat. No.
    DC Interface (Electronic)
  • Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor.

  • Requires no additional surge suppression on the relay coils
  • Input: 12V DC
    Output: 110…240V AC
    Click to enlarge - 100-C_104-C-88-2 100-C with AC coils 110…240V AC 100-JE12
    Input: 18…30V DC
    Output: 110…240V AC
    100-JE
    Input: 48V DC
    Output: 110…240V AC
    100-JE48
    Click to enlarge - 100-C_104-C-88-3 Surge Suppressors
  • For limitation of coil switching transients.

  • Plug-in, coil mounted.

  • Suitable for 100-C contactor sizes, 9…97 A.

  • RC, varistor, and diode versions.
  • RC Module
    AC operating mechanism
    24…48V AC, 50/60 Hz Click to enlarge - 100D-92-2 100-C with AC coils §  100-FSC48
    110…280V AC, 50/60 Hz §  100-FSC280
    380…480V AC, 50/60 Hz §  100-FSC480
    Varistor Module
    AC/DC operating mechanism
    12…55V AC/ 12…77V DC Click to enlarge - 100-C_104-C-88-5 100-C with AC coils or 100-C09…-C43 with DC coils §  100-FSV55
    56…136V AC/ 78…180V DC §  100-FSV136
    137…277V AC/ 181…350V DC §  100-FSV277
    278…575V AC §  100-FSV575
    Diode Module
    DC operating mechanism
    12…250V DC Click to enlarge - 100-C_104-C-88-6 100-C09…-C43 with DC coils §  100-FSD250
      
    § For screwless terminals, insert "CR" after the "100-" in the catalog number. Example: Cat. No. 100-FSC48 becomes Cat. No. 100-CRFSC48.

    Assembly Components (For 100-C09…C97 contactors)

      Description For Use With Pkg. Quantity Cat. No.
    Click to enlarge - 100-C_104-C-88-7 Dovetail Connectors
  • For use in contactor and starter assemblies.

  • Single Connector — 0 mm Spacing
  • 100-C 10 100-S0
    Cat. No. 100-S0 Dovetail Connectors
  • For use in contactor and starter assemblies.

  • Dual Connector — 9 mm Spacing
  • 10 100-S9
    Click to enlarge - 100-C_104-C-88-8 Protective Covers
  • Provides protection against unintended manual operation

  • For contactors and front-mounted auxiliary contacts, pneumatic timers, and latches
  • 100-C all 1 100-SCCA
    Cat. No. 100-SCCA
    Click to enlarge - 100-C_104-C-88-9 100-FA, -FB, -FC, -FP, -FL; 10 100-SCFA
    Cat. No. 100-SCFA
    Click to enlarge - 100-C_104-C-88-10 Reversing Power Wiring Kits
  • For reversing connection with a solid-state or thermal overload relay
  •   
    100-C09…C23  
    1 105-PW23
      
    100-C30…C37  
    1 105-PW37
      
    100-C43  
    1 105-PW43
    Cat. No. 105-PW23   
    100-C60…C97  
    1 105-PW85
    Click to enlarge - 100-C_104-C-88-11 DIN (#3) symmetrical hat rail
    35 x 7.5 x 1 m
    140M-D
    140M-F
    100-C all
    10 199-DR1
      

    Wye-Delta/Star-Delta Starter Kits

    Wye-Delta power wiring kits were designed to aid in the field assembly of open-transition wye-delta starters that use Bulletin 100-C contactors. These kits include line, load, and start-point (shorting) connections. Assembling a wye-delta starter requires the use of the following additional components:


    Click to enlarge - 100-C_104-C-89-1
    Cat. No. 170-PW23


    3-Phase Rating Pkg.
    Qty.
    Cat. No.
    kW (50 Hz) Hp (60 Hz) Use with Cat. No. 100-
    230V 380/415V 500V 690V 200V 230V 460V 575V Delta Wye
    1M 2M 1S
    5.5 8 8 8 5 5 10 10 C09 C09 C09 1 170-PW23
    7.5 11 11 11 5 7.5 15 15 C12 C12 C09 1 170-PW23
    10 14 15 14 7.5 10 20 20 C16 C16 C12 1 170-PW23
    14 21 21 19 7.5 10 25 25 C23 C23 C12 1 170-PW23
    18 28 28 28 10 15 30 30 C30 C30 C16 1 170-PW37
    19 35 35 32 15 20 40 40 C37 C37 C23 1 170-PW37
    23 40 40 41 20 25 50 50 C43 C43 C30 1 170-PW43
    33 58 60 56 30 40 75 75 C60 C60 C37 1 170-PW72
    39 69 67 70 40 50 100 100 C72 C72 C43 1 170-PW72
    47 82 82 81 50 60 125 125 C85 C85 C60 1 170-PW85
    50 90 90 90 50 60 125 125 C97 C97 C60 1 170-PW85
      
    Package Quantity = 1

    Marking Systems (For 100-C09…C97 contactors)

      Description Pkg. Qty.⋆  Cat. No.
    Click to enlarge - 100-C_104-C-89-2 Label Sheet
    105 self-adhesive paper labels each, 6 x 17 mm
    10 100-FMS
    Click to enlarge - 100-C_104-C-89-3 Marking Tag Sheet
    160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
    10 100-FMP
    Transparent Cover
    To be used with marking tag sheets
    100 100-FMC
    Click to enlarge - 100-FMA1 Marking Tag Adapters
    To be used with marking tag: System V4/V5
    100 100-FMA1
    Marking Tag Adapters
    To be used with marking tag: System 1492 W
    100 100-FMA2
      
    ⋆ Must be ordered in multiples of package quantities.

    Terminal Kits (For 100-C09…C97 contactors)

      Description Max. Current Ratings and Wire Sizes Pkg. Qty.⋆  Cat. No.
    Click to enlarge - 100-C_104-C-90-1 Stab Connector Kit
    Dual stab (0.250 in.) for 100-C coil terminals
    For 100-C09…C97 contactors
    20 199-SC2
    Click to enlarge - 100-C_104-C-90-2 Stab Connector Kit
    Dual stab (0.250 in.) for 100-C power terminals
    For 100-C09…C23 contactors
    100 199-SC10
    Click to enlarge - 100_CTN23 3-Pole Terminal Lug Kit
    For Cat. No. 100-C09…C23 (Line side)
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    45 A (4…16 mm2‡ , fine stranded w/ ferrule)
    45 A (4…25 mm2, coarse stranded/solid)
    40 A (#10…4 AWG, stranded/solid)
    1 100-CTN23
    3-Pole Terminal Lug Kit
    For Cat. No. 100-C09…C23 (Load side)
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    45 A (4…16 mm2‡ , fine stranded w/ ferrule)
    45 A (4…25 mm2, coarse stranded/solid)
    40 A (#10…4 AWG, stranded/solid)
    1 100-CTL23
    3-Pole Terminal Lug Kit
    For Cat. No. 100-C30…C37 (Line and load side)
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    60 A (4…16 mm2‡ , fine stranded w/ ferrule)
    60 A (4…25 mm2, coarse stranded/solid)
    55 A (#10…4 AWG, stranded/solid)
    1 100-CT37
    Click to enlarge - 100_CT43 1-Pole Terminal Lug Kit
    For Cat. No. 100-C43
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    90 A (6…35 mm2, fine stranded w/ ferrule)
    90 A (6…50 mm2, coarse stranded/solid)
    75 A (#8…2 AWG, stranded/solid)
    3 100-CT43
    1-Pole Terminal Lug Kit
    For Cat. No. 100-C60…C97
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    130 A (10…70 mm2, fine stranded w/ ferrule)
    130 A (10…95 mm2, coarse stranded/solid)
    130 A (#8…2/0 AWG, stranded/solid)
    3 100-CT85
    Click to enlarge - 100CP23 3-Pole Paralleling Kit
    For Cat. No. 100-C09…C23
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    100 A (35…70 mm2, fine stranded w/ ferrule)
    100 A (35…95 mm2, coarse stranded/solid)
    100 A (#0…2/0 AWG, stranded/solid)
    2 100-CP23
    3-Pole Paralleling Kit
    For Cat. No. 100-C30…C37
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    150 A (35…70 mm2, fine stranded w/ ferrule)
    150 A (35…95 mm2, coarse stranded/solid)
    150 A (#0…2/0 AWG, stranded/solid)
    2 100-CP37
      
    ⋆ Must be ordered in multiples of the package quantity.
    ‡ 16 mm2 max. according to IEC 60947; actual max. 25 mm2.

    SEMI-F47 Voltage Sag Immunity Module

      Description Input Voltage For Use With§  Options Cat. No.
    Click to enlarge - CSF47A30_alone2 SEMI-F47 Module
  • Meets SEMI-F47 voltage sag immunity requirements

  • Direct mounting to coil terminals of 100-C contactors and 700-CF control relays

  • Requires DC coil contactor

  • Optional 1…30 s ON-delay timer version
  • 24…240V AC 100-C09…C97
    700-CF
    without timer 100-CSF47
    110…240V AC 100-C09…C97
    700-CF
    with 1…30 s ON-delay timer 100-CSF47A30
      
    § Contactor must have DC coil at the same voltage as AC input. Example: for 24V AC control, select Cat. No. 100-C09ZJ10 (24V DC coil).

    Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications

      100-KR 100/104-K 100/104-C, 100S/104S-C
      05 09 05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
    Coil Type : Conventional X X X X X X X X X X X X X X X
      Electronic — EI
    AC-1 Active Power Load (50 Hz);
    Ambient temperature 40 °C
        Ie £ 500V [A] 10 10 20 20 20 32 32 32 32 (40)⋆  65 65 75 75 85 100
    690V [A] 10 10 20 20 20 32 32 32 32 (40)⋆  65 65 75 75 85 100
    1000V [A]
    230V [kW] 4 4 8 8 8 13 13 13 13 26 26 30 30 34 40
    240V [kW] 4 4 8.3 8.3 8.3 13 13 13 13 27 27 31 31 35 42
    400V [kW] 6.9 6.9 14 14 14 22 22 22 22 45 45 52 52 59 69
    415V [kW] 7 7 14 14 14 23 23 23 23 47 47 54 54 61 72
    500V [kW] 8.7 8.7 17 17 17 28 28 28 28 56 56 65 65 74 87
    690V [kW] 12 12 24 24 24 38 38 38 38 78 78 90 90 102 120
    1000V [kW]
    Ambient temperature 60 °C
        Ie £ 500V [A] 10 10 16 16 16 32 32 32 32 65 65 60 60 80 100
    690V [A] 10 10 16 16 16 32 32 32 32 65 65 60 60 80 100
    1000V [A]
    230V [kW] 4 4 6.4 6.4 6.4 13 13 13 13 26 26 24 24 25 40
    240V [kW] 4 4 6.7 6.7 6.7 13 13 13 13 27 27 25 25 26 42
    400V [kW] 6.9 6.9 11 11 11 22 22 22 22 45 45 42 42 44 69
    415V [kW] 7 7 12 12 12 23 23 23 23 47 47 43 43 45 72
    500V [kW] 8.7 8.7 14 14 14 28 28 28 28 56 56 52 52 55 87
    690V [kW] 12 12 19 19 19 38 38 38 38 78 78 72 72 75 120
    1000V [kW]
    Switching of 3-phase Motors; (50 Hz)
    Ambient temperature 60 °C, AC-2, AC-3
      230V [A] 6.3 8.5 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
    240V [A] 6.3 8.5 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
    400V [A] 4.9 8.5 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
    415V [A] 4.9 8.5 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
    500V [A] 3.9 6.8 3.9 6.8 9.2 7 10 14 20 25 30 29 30 38 55
    690V [A] 2.8 4.9 2.8 4.9 6.7 5 7 9 12 18 21 9 21 25 34
    1000V [A]
    230V [kW] 1.5 2.2 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
    240V [kW] 1.5 2.2 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
    400V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 11 15 18.5 18.5 18.5 22 32
    415V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 11 15 20 20 20 22 32
    500V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 13 15 20 18.5 20 25 37
    690V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 10 15 18.5 7.5 18.5 22 32
    1000V [kW]
    Load Carrying Capacity per UL/CSA
    General Purpose Current (enclosed)
      [A] 9 9 12 15 18 25 25 30 30 55 60 60 60 75 90
    Rated power (enclosed)
        1-phase 115V [A] 7.2 7.2 9.8 9.8 13.8 9.8 9.8 16 24 24 34 34 34 34 56
    230V [A] 6.9 8 8 10 12 10 12 17 17 28 28 28 28 40 50
    115V [Hp] 1/3 1/3 0.5 0.5 0.75 0.5 0.5 1 2 2 3 3 3 3 5
    230V [Hp] 3/4 1 1 1.5 2 1.5 2 3 3 5 5 5 5 7.5 10
        3-phase 200V [A] 6.9 7.8 6.9 7.8 11 7.8 11 17.5 17.5 25.3 32.2 32.2 32.2 32.2 48.3
    230V [A] 6 6.8 6 6.8 9.6 6.8 9.6 15.2 22 28 28 28 28 42 54
    460V [A] 4.8 7.6 4.8 7.6 11 7.6 11 14 21 27 34 34 34 40 52
    575V [A] 3.9 6.1 3.9 6.1 9 9 11 17 17 27 32 17 32 32 52
    200V [Hp] 1.5 2 1.5 2 3 2 3 5 5 7.5 10 10 10 10 15
    230V [Hp] 1.5 2 1.5 2 3 2 3 5 7.5 10 10 10 10 15 20
    460V [Hp] 3 5 3 5 7.5 5 7.5 10 15 20 25 25 25 30 40
    575V [Hp] 3 5 3 5 7.5 7.5 10 15 15 25 30 15 30 30 50
      
    ⋆ Values in ( ) with increased cross-section and cable lug

      100/104-C, 100S/104S-C 100/104-D, 100S-D
      72 85 90*200 90*400 97 115 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X X X
    Electronic — EI X X X X X X X X X
    AC-1 Active Power Load (50 Hz);
    Ambient temperature 40 °C
        Ie £ 500V [A] 100 100 130 130 130 250 250 250 250 250 350 350 450 540 800 1000
    690V [A] 100 100 130 130 130 250 250 250 250 250 350 350 450 540 800 1000
    1000V [A] 250 250 250 250 250 350 350 450 540
    230V [kW] 40 40 52 52 52 100 100 100 100 100 139 139 179 199 319 398
    240V [kW] 42 42 54 54 54 104 104 104 104 104 145 145 187 208 333 416
    400V [kW] 69 69 90 90 90 173 173 173 173 173 242 242 312 346 554 693
    415V [kW] 72 72 93 93 93 180 180 180 180 180 252 252 323 359 575 719
    500V [kW] 87 87 113 113 113 217 217 217 217 217 303 303 390 433 693 866
    690V [kW] 120 120 155 155 155 299 299 299 299 299 418 418 538 598 956 1195
    1000V [kW] 433 433 433 433 433 606 606 779 866
    Ambient temperature 60 °C
        Ie £ 500V [A] 100 100 110 110 110 210 210 210 210 210 300 300 380 425
    690V [A] 100 100 110 110 110 210 210 210 210 210 300 300 380 425
    1000V [A] 210 210 210 210 210 300 300 380 425
    230V [kW] 40 40 44 44 44 84 84 84 84 84 120 120 151 169
    240V [kW] 42 42 46 46 46 87 87 87 87 87 125 125 158 177
    400V [kW] 69 69 76 76 76 145 145 145 145 145 208 208 263 294
    415V [kW] 72 72 79 79 79 151 151 151 151 151 216 216 273 305
    500V [kW] 87 87 95 95 95 182 182 182 182 182 260 260 329 368
    690V [kW] 120 120 131 131 131 251 251 251 251 251 359 359 454 508
    1000V [kW] 364 364 364 364 364 520 520 658 736
    Switching of 3-phase Motors; (50 Hz)
    Ambient temperature 60 °C, AC-2, AC-3
      230V [A] 72 85 85 85 96 115 140 140 180 180 210 250 300 420 630 860
    240V [A] 72 85 85 85 95 115 140 140 180 180 210 250 300 420 630 860
    400V [A] 72 85 85 85 97 115 140 140 180 180 210 250 300 420 630 860
    415V [A] 72 85 85 85 97 115 (130)§  140 (155)§  140 (155)§  180 (189)§  180 (189)§  210 (227)§  250 (258)§  300 (315)§  420 630 860
    500V [A] 67 80 80 80 78 115 115 140 140 180 210 250 300 420 630 753
    690V [A] 42 49 22 49 57 115 115 140 140 180 210 250 300 420 492
    1000V [A] 46 55 55 65 65 80 95 115 160
    230V [kW] 22 25 25 25 30 37 45 45 57 57 67 80 97 135 200 250
    240V [kW] 22 25 25 25 30 38 47 47 60 60 70 83 101 141 200 250
    400V [kW] 40 45 45 45 55 64 78 78 101 101 118 140 170 238 355 500
    415V [kW] 40 45 45 45 55 66 (75)§  82 (90)§  82 (90)§  105 (110)§  105 (110)§  122 (132)§  145 (150)§  176 (185)§  250 355 500
    500V [kW] 45 55 55 55 55 80 80 98 98 126 147 177 213 298 450 560
    690V [kW] 40 45 18.5 45 55 111 111 135 135 176 205 250 293 424 500
    1000V [kW] 63 75 75 90 90 110 132 160 225
    Load Carrying Capacity per UL/CSA
    General Purpose Current (enclosed)
        [A] 90 100 125 130 120 220 220 220 220 220 300 300 340 420 630 860
    Rated power (enclosed)
        1-phase 115V [A] 56 80 80 80 100 100 135 135
    230V [A] 68 68 68 68 88 110 136 136 176 176 216
    115V [Hp] 5 7.5 7.5 7.5 10 10 15 15
    230V [Hp] 15 15 15 15 20 25 30 30 40 40 50
        3-phase 200V [A] 62.1 78.2 78.2 78.2 92 120 120 120 150 150 177 221 285 414 552 692
    230V [A] 68 80 80 80 80 104 130 130 154 154 192 248 312 420 602 720
    460V [A] 65 77 65 77 96 96 124 124 180 180 180 240 302 414 590 702
    575V [A] 62 62 22 52 77 99 125 125 144 144 192 242 289 382 562 651
    200V [Hp] 20 25 25 25 30 40 40 40 50 50 60 75 100 150 200 250
    230V [Hp] 25 30 30 30 30 40 50 50 60 60 75 100 125 175 250 300
    460V [Hp] 50 60 50 60 75 75 100 100 150 150 150 200 250 350 500 600
    575V [Hp] 60 60 20 50 75 100 125 125 150 150 200 250 300 400 600 700
      
    § 415 V: values in ( ) AC-2 and AC-3 lifespan -25 %

      100/104-K 100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 43 60
    Coil Type : Conventional X X X X X X X X X X X
    Electronic — EI
    Switching of 3-phase Motors, (50Hz); Ambient temperature 60 °C, AC-4
      230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
    240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
    400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
    415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
    500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 38 55
    690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 25 34
    1000V [A]
    230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
    240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
    400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 22 32
    415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 22 32
    500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 25 37
    690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 22 32
    1000V [kW]
    AC-4 at approximately 200,000 operations
      230V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
    240V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
    400/415V [A] 2 3.6 3.6 4.3 6.6 9 9 12 14 16.5 25.5
    500V [A] 1.9 3.2 3.2 4.3 6.6 9 9 12 14 16.5 25.5
    690V [A] 4.3 6.6 9 9 12 14 16.5 25.5
    1000V [A]
    230V⋆  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 3.7 4 6.3
    240V⋆  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 4 4 7.5
    400V⋆  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
    415V⋆  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
    500V⋆  [kW] 0.75 1.5 1.5 2.2 3.7 5.5 5.5 7.5 7.5 10 15
    690V⋆  [kW] 3 5.5 7.5 7.5 10 11 15 22
    1000V⋆  [kW]
    Max. switching frequency Ops/h 250 250 250 250 250 220 200 200 200 200 120
    Wye-Delta (60 Hz)
      200V [Hp] 2.2 3 5 5 5 7½ 7½ 10 15 20 30
    230V [Hp] 2.2 3 5 5 7½ 10 10 15 20 25 40
    460V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
    575V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
    UL/CSA Elevator Duty§ 
      200V [A] 7.8 11.0 11.0 17.5 25.3 25.3 32.2 32.2
    230V [A] 6.8 9.6 15.2 15.2 22.0 28.0 28.0 42.0
    460V [A] 7.6 11.0 14.0 21.0 27.0 27.0 34.0 40.0
    575V [A] 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0
    200V [Hp] 2 3 3 5 7½ 7½ 10 10
    230V [Hp] 2 3 5 5 7½ 10 10 15
    460V [Hp] 5 7½ 10 15 20 20 25 30
    575V [Hp] 5 7½ 10 15 20 25 30 40
    Star-Delta Starting (50 Hz)
      £ 230V [A] 11.3 20 20 21 26 35 46 61 66 76 107
    £ 240V [A] 11.3 20 20 21 26 35 46 61 66 76 107
    400V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
    415V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
    500V [A] 6.8 12.4 12.4 12 17 24 35 43 52 66 95
    690V [A] 4.9 8.9 8.9 8.6 12 16 21 31 36 43 59
    1000V [A]
    230V⋆  [kW] 3 5.5 5.5 5.5 7.5 10 13 17 20 22 32
    240V⋆  [kW] 3 5.5 5.5 5.5 7.5 10 13 18.5 20 22 32
    400V⋆  [kW] 4 7.5 10 7.5 10 13 20 25 32 40 55
    415V⋆  [kW] 4 7.5 11 7.5 11 15 22 25 37 40 55
    500V⋆  [kW] 4 7.5 7.5 7.5 11 15 22 25 32 45 63
    690V⋆  [kW] 4 7.5 7.5 7.5 10 13 18.5 25 32 40 55
    1000V⋆  [kW]
      
    ⋆ Power ratings at 50 Hz: Preferred values according to IEC 60072-1 § Approval pending on Cat. No. 100-D210…D860.

      100/104-C, 100S/104S-C 100/104-D, 100S-D
    72 85 97 115 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X
    Electronic — EI X X X X X X X X X
    Switching of 3-phase Motors, (50 Hz)
    Ambient temperature 60 °C, AC-4
      230V [A] 72 85 96 115 140 140 180 180 210 250 300 420
    240V [A] 72 85 95 115 140 140 180 180 210 250 300 420
    400V [A] 72 85 97 115 140 140 180 180 210 250 300 420
    415V [A] 72 85 97 115 (130)‡  140 (155)‡  140 (155)‡  180 (189)§  180 (189)§  210 (227)‡  250 (258)‡  300 (315)‡  420
    500V [A] 67 80 78 115 115 140 140 170 210 250 300 360
    690V [A] 42 49 57 115 115 140 140 170 210 250 300 360
    1000V [A] 46 55 55 65 65 80 95 115 160
    230V [kW] 22 25 30 37 45 45 57 57 67 80 97 135
    240V [kW] 22 25 30 39 47 47 60 60 70 83 101 141
    400V [kW] 40 45 55 63 78 78 100 100 118 140 170 238
    415V [kW] 40 45 55 66 (75)‡  82 (90)‡  82 (90)‡  105 (110)‡  105 (110)‡  125 (132)‡  145 (150)‡  176 (185)‡  250
    500V [kW] 45 55 55 80 80 98 98 119 147 177 213 255
    690V [kW] 40 45 55 110 110 135 135 167 205 250 293 356
    1000V [kW] 63 75 75 90 90 110 132 160 225
    AC-4 at approximately 200,000 operations
      230V [A] 31 38 44 53 60 60 67 67 85 105 140 170
    240V [A] 31 38 44 53 60 60 67 67 85 105 140 170
    400/415V [A] 31 38 44 53 60 60 67 67 85 105 140 170
    500V [A] 31 38 44 53 60 60 67 67 85 105 140 170
    690V [A] 31 38 44 53 60 60 67 67 85 105 140 170
    1000V [A] 25 37 37 43 43 60 72 85 105
    230V⋆  [kW] 7.5 11 11 15 17 17 20 20 25 32 45 55
    240V⋆  [kW] 7.5 11 11 15 18.5 18.5 22 22 25 32 45 55
    400V⋆  [kW] 15 20 22 25 32 32 37 37 45 55 75 90
    415V⋆  [kW] 17 20 22 25 32 32 37 37 50 55 80 100
    500V⋆  [kW] 20 25 30 32 40 40 45 45 55 75 100 110
    690V⋆  [kW] 25 32 37 45 55 55 63 63 80 100 132 160
    1000V⋆  [kW] 30 50 50 55 55 80 100 110 150
    Max. switching frequency Ops/h 120 120 120 120 120 120 100 100 120 100 70 70
    Wye-Delta (60 Hz)
      200V [Hp] 40 50 50 60 60 60 75 75 100 125 175 250
    230V [Hp] 50 60 60 60 75 75 100 100 125 175 200 250
    460V [Hp] 100 125 125 125 175 175 200 200 250 350 450 600
    575V [Hp] 100 125 125 150 200 200 250 250 300 450 500 650
    UL/CSA Elevator Duty‡ 
      200V [A] 48.3 62.1 TBD 78 92 92 120 120 150 150 177 221
    230V [A] 54.0 68.0 TBD 80 104 104 130 130 130 154 192 248
    460V [A] 52.0 65.0 TBD 77 96 96 124 124 156 180 180 240
    575V [A] 52.0 62.0 TBD 77 77 77 99 99 125 144 192 242
    200V [Hp] 15 20 TBD 25 30 30 40 40 50 50 60 75
    230V [Hp] 20 25 TBD 30 40 40 50 50 50 60 75 100
    460V [Hp] 40 50 TBD 60 75 75 100 100 125 150 150 200
    575V [Hp] 50 60 TBD 75 75 75 100 100 125 150 200 250
    Star-Delta Starting (50 Hz)
      £ 230V [A] 125 147 166 199 242 242 312 312 364 433 520 727
    £ 240V [A] 125 147 165 199 242 242 312 312 364 433 520 727
    400V [A] 125 147 168 199 242 242 312 312 364 433 520 727
    415V [A] 125 147 168 199 (225)‡  242 (268)‡  242 (268)‡  312 (332)‡  312 (332)‡  364 (393)‡  433 (447)‡  520 (546)‡  727
    500V [A] 116 139 135 199 199 242 312 312 364 433 520 727
    690V [A] 73 85 99 199 199 242 312 312 364 433 520 727
    1000V [A] 80 95 95 113 113 139 165 200 277
    230V⋆  [kW] 37 45 50 63 75 75 90 90 110 132 160 220
    240V⋆  [kW] 40 50 50 66 80 80 100 100 125 150 160 250
    400V⋆  [kW] 63 80 90 110 132 132 160 160 200 250 300 425
    415V⋆  [kW] 63 80 90 114 (132)‡  132 (160)‡  132 (160)‡  160 160 220 250 315 (335)‡  425
    500V⋆  [kW] 80 90 90 132 132 160 200 200 250 315 375 530
    690V⋆  [kW] 63 80 90 192 200 220 300 300 355 425 530 750
    1000V⋆  [kW] 110 132 132 160 160 200 220 280 400
      
    ‡ 415V: Values in ( ) AC-3 and AC-4 lifespan -25%
    § Approval pending on Cat. No. 100-D210…D860.

      100/104-K 100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 43 60
    Coil Type : Conventional X X X X X X X X X X X
    Electronic — EI
    Switching of Power Transformers,
    AC-6a (50 Hz)
    Inrush Current = n  
    Rated transformer current  
        n = 30 £ 230V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 240V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 400V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 415V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 500V [A] 1.8 3.2 3.2 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 690V [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
    £ 1000V [A]
    230V [kVA] 1.2 2 2 4.3 4.3 4.3 4.3 8 8 9.2 16
    240V [kVA] 1.2 2 2 4.5 4.5 4.5 4.5 8.3 8.3 10 17
    400V [kVA] 1.7 2.8 3.4 7.5 7.5 7.5 7.5 14 14 16 28
    415V [kVA] 1.7 2.8 3.4 7.8 7.8 7.8 7.8 14 14 17 29
    500V [kVA] 1.7 2.8 3.4 9.4 9.4 9.4 9.4 17 17 20 35
    690V [kVA] 2 4 5 13 13 13 13 24 24 27 49
    1000V [kVA]
        n = 20 £ 690V [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
        n = 15 £ 690V [A] 22 22 22 22 40 40 46 82
    60 Hz Peak Inrush/peak rated transformer current
      n = 30 [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
    200V [kVA] 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.1
    208V [kVA] 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.7
    240V [kVA] 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17.0
    480V [kVA] 9.1 9.1 9.1 9.1 16.6 16.6 19.1 33.9
    600V [kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.4
    660V [kVA] 12.5 12.5 12.5 12.5 22.9 22.9 26.3 46.6
    60 Hz Peak Inrush/peak rated transformer current
      n = 20 [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
    200V [kVA] 5.6 5.6 5.6 5.6 10.4 10.4 12.0 21.2
    208V [kVA] 5.9 5.9 5.9 5.9 10.8 10.8 12.4 22.1
    240V [kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5
    480V [kVA] 13.6 13.6 13.6 13.6 24.9 24.9 28.7 51.0
    600V [kVA] 16.9 16.9 16.9 16.9 31.2 31.2 35.9 63.7
    660V [kVA] 18.6 18.6 18.6 18.6 34.3 34.3 39.4 70.1
    60 Hz Peak Inrush/peak rated transformer current
      n=15 [A] 22 22 22 22 40 40 46 82
    200V [kVA] 7.5 7.5 7.5 7.5 13.9 13.9 15.9 28.4
    208V [kVA] 7.8 7.8 7.8 7.8 14.4 14.4 16.6 29.5
    240V [kVA] 9.0 9.0 9.0 9.0 16.6 16.6 19.1 34.1
    480V [kVA] 18.1 18.1 18.1 18.1 33.3 33.3 38.2 68.2
    600V [kVA] 22.6 22.6 22.6 22.6 41.6 41.6 47.8 85.2
    660V [kVA] 24.9 24.9 24.9 24.9 45.7 45.7 52.6 93.7
      

      100/104-C, 100S/104S-C 100/104-D, 100S-D
    72 85 97 115 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X
    Electronic — EI X X X X X X X X X
    Switching of Power Transformers,
    AC-6a (50 Hz)
    Inrush Current
    Rated transformer current
        n = 30 £ 230V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    £ 240V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    £ 400V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    £ 415V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    £ 500V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    £ 690V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    £ 1000V [A] 46 70 70 85 85 105 125 150 210
    230V [kVA] 16 16 19.3 24 28 28 34 34 42 50 60 84
    240V [kVA] 17 17 20.2 26 29 29 35 35 44 52 62 87
    400V [kVA] 28 28 33.6 42 48 48 59 59 73 87 104 145
    415V [kVA] 29 29 34.9 43 50 50 61 61 75 90 108 151
    500V [kVA] 35 35 42 52 61 61 74 74 91 108 130 182
    690V [kVA] 49 49 58 72 84 84 102 102 125 149 179 251
    1000V [kVA] 80 121 121 147 147 182 217 260 364
        n = 20 £ 690V [A] 61.3 61.3 72.8 90 105 105 128 128 158 188 225 315
        n = 15 £ 690V [A] 82 82 97 120 140 140 170 170 210 250 300 420
    60 Hz Peak Inrush/peak rated transformer current
      n = 30 [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
    200V [kVA] 14.4 14.4 16.8 20.8 24.2 24.2 29.4 29.4 36.4 43.3 52.0 72.7
    208V [kVA] 14.7 14.7 17.5 21.6 25.2 25.2 30.6 30.6 37.8 45.0 54.0 75.7
    240V [kVA] 17.0 17.0 20.2 24.9 29.1 29.1 35.3 35.3 43.6 52.0 62.4 87.3
    480V [kVA] 33.9 33.9 40.3 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
    600V [kVA] 42.4 42.4 50.4 62.4 72.7 72.7 88.3 88.3 109 130 156 218
    660V [kVA] 46.6 46.6 55.4 68.6 80.0 80.0 97.2 97.2 120 143 171 240
    60 Hz Peak Inrush/peak rated transformer current
      n = 20 [A] 61.3 61.3 72.8 90 105 105 128 128 158 188 225 315
    200V [kVA] 21.2 21.2 25.2 31.2 36.4 36.4 44.3 44.3 54.7 65.1 77.9 109
    208V [kVA] 22.1 22.1 26.2 32.4 37.8 37.8 46.1 46.1 56.9 67.7 81.1 113
    240V [kVA] 25.5 25.5 30.3 37.4 43.6 43.6 53.2 53.2 65.7 78.2 93.5 131
    480V [kVA] 51.0 51.0 60.5 74.8 87.3 87.3 106 106 131 156 187 262
    600V [kVA] 63.7 63.7 75.7 93.5 109 109 133 133 164 195 234 327
    660V [kVA] 70.1 70.1 83.2 103 120 120 146 146 131 215 257 360
    60 Hz Peak Inrush/peak rated transformer current
      n=15 [A] 82 82 97 120 140 140 170 170 210 250 300 420
    200V [kVA] 28.4 28.4 33.6 41.6 48.5 48.5 58.9 58.9 72.7 86.6 104 145
    208V [kVA] 29.5 29.5 34.9 43.2 50.4 50.4 61.2 61.2 75.7 90.1 108 151
    240V [kVA] 34.1 34.1 40.3 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
    480V [kVA] 68.2 68.2 80.6 99.8 116 116 141 141 175 208 249 349
    600V [kVA] 85.2 85.2 100.8 125 145 145 177 177 218 260 312 436
    660V [kVA] 93.7 93.7 110.9 137 160 160 194 194 240 286 343 480
      

      100/104-K 100/104-C, 100S/104S-C
      05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
    Coil Type : Conventional X X X X X X X X X X X X X
    Electronic — EI
    Switching of 3-phase Capacitors, AC-6b (50 Hz)⋆ 
    Single capacitor 40 °C 230V [kVar] 8 8 8.5 9 14 14 24 28
    240V [kVar] 8 8 8.5 9 14 14 25 29
    400V [kVar] 8 8 10 12.5 20 24 35 48
    415V [kVar] 8 8 10 12.5 20 25 35 50
    500V [kVar] 8 8 10 12.5 20 25 35 50
    690V [kVar] 8 8 10 12.5 20 25 35 50
    1000V [kVar]
        60 °C 230V [kVar] 8 8 8.5 9 12.5 12.5 18 28
    240V [kVar] 8 8 8.5 9 12.5 12.5 18 29
    400V [kVar] 8 8 10 12.5 20 21.5 30 42
    415V [kVar] 8 8 10 12.5 20 22 30 42
    500V [kVar] 8 8 10 12.5 20 25 30 42
    690V [kVar] 8 8 10 12.5 20 25 30 42
    1000V [kVar]
    Group capacitors 40 °C 230V [kVar] 5 5 8 9 12.5 14 20 28
    240V [kVar] 5 5 8 9 12.5 14 20 29
    400V [kVar] 5 5 8 10 15 20 25 40
    415V [kVar] 5 5 8 10 15 20 25 40
    500V [kVar] 5 5 8 10 15 20 25 40
    690V [kVar] 5 5 8 10 15 20 25 40
    1000V [kVar]
        60 °C 230V [kVar] 5 5 8 9 12.5 12.5 18 28
    240V [kVar] 5 5 8 9 12.5 12.5 18 29
    400V [kVar] 5 5 8 10 15 20 25 40
    415V [kVar] 5 5 8 10 15 20 25 40
    500V [kVar] 5 5 8 10 15 20 25 40
    690V [kVar] 5 5 8 10 15 20 25 40
    1000V [kVar]
    60 Hz Single Capacitor — 40 °C
      200V [kVar] 5 5 8 9 12.5 14 20 28
    230V [kVar] 5 5 8 9 12.5 14 20 29
    460V [kVar] 5 5 8 10 15 20 25 40
    600V [kVar] 5 5 8 10 15 20 25 40
    60 Hz Group Capacitors — 40 °C
      200V [kVar] 5 5 8 9 12.5 12.5 18 28
    230V [kVar] 5 5 8 9 12.5 12.5 18 29
    460V [kVar] 5 5 8 10 15 20 25 40
    600V [kVar] 5 5 8 10 15 20 25 40
    Switching of Lamps
    Gas discharge lamps AC-5a, 40 °C open [A] 18 18 18 22.5 25 28 29 40.5 45 65 65 77 81
      enclosed [A] 14.5 14.5 14.5 22.5 25 28 29 37 41 54 54 57 77
    Individually compensated:
    Max. capacitance at expected
    Short-circuit current of 10 kA [mF] 750 750 750 1 000 1 000 1 000 1 000 2 700 2 700 3 200 4 000
    20 kA [mF] 400 400 400 500 500 500 500 1 350 1 350 1 600 2 000
    50 kA [mF] 200 200 200 200 540 540 640 800
    Filament AC-5b 230/240V [A] 5 9 9 12 16 18 22 30 37 18 25 43 60
    Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
    AC-7a 230V [A] 20 20 20 32 32 32 32 45 45 63
    400V [A] 20 20 20 32 32 32 32 45 45 63
    440V [A] 32 32 32 32 45 45 63
    Switching of Motor Load for Home Appliances (50 Hz)
    AC-7b 230V [A] 6 11 11 10.5 14 19 23 30
    400V [A] 6 11 11 9 12 16 20 30
    440V [A] 7.5 10 13.5 18 27
      
    ⋆ Inductance of leads between capacitors in parallel: min. 6 mH (100-C09…C30 contactors: min 30 mH)

      100/104-C, 100S/104S-C 100/104-D, 100S-D
    72 85 90*200 90*400 97 115 140 140 180 180 210 250 300 420 630 860
    Coil Type : Conventional X X X X X X X X
    Electronic — EI X X X X X X X X X
    Switching of 3-phase Capacitors, AC-6b (50 Hz)
    Single capacitor 40°C 230V [kVar] 28 28 28 45 70 70 70 70 98 98 125 139
    240V [kVar] 29 29 29 47 73 73 73 73 102 102 131 145
    400V [kVar] 48 48 48 78 121 121 121 121 170 170 218 242
    415V [kVar] 50 50 50 81 126 126 126 126 176 176 226 252
    500V [kVar] 55 60 60 97 152 152 152 152 212 212 273 303
    690V [kVar] 55 60 60 134 209 209 209 209 293 293 376 418
    1000V [kVar] 194 303 303 303 303 424 424 546 606
        60 °C 230V [kVar] 28 28 28 38 59 59 59 59 84 84 106 119
    240V [kVar] 29 29 29 39 61 61 61 61 87 87 111 124
    400V [kVar] 48 48 48 65 102 102 102 102 145 145 184 206
    415V [kVar] 50 50 50 68 106 106 106 106 151 151 191 214
    500V [kVar] 50 55 55 82 127 127 127 127 182 182 230 258
    690V [kVar] 50 55 55 113 176 176 176 176 251 251 318 356
    1000V [kVar] 164 255 255 255 255 364 364 461 515
    Group capacitors 40°C 230V [kVar] 28 28 28 45 70 70 70 70 98 98 125 139
    240V [kVar] 29 29 29 47 73 73 73 73 102 102 131 145
    400V [kVar] 48 48 48 56 76 76 111 111 170 170 218 242
    415V [kVar] 50 50 50 56 76 76 112 112 170 176 226 252
    500V [kVar] 50 50 50