Catalogs >
Industrial Controls Catalog >
Motor Control, IEC >
Contactors >
Bulletin 100-C Contactors
Bulletin 100-C Contactors
Product Selection
3-Pole AC- and DC-Operated Contactors
| Ie [A]
|
Ratings for Switching AC Motors — AC-2, AC-3, AC-4
|
Aux. Contacts
|
Cat. No.
|
| 3-Phase kW (50 Hz)
|
Hp (60 Hz)
|
|
|
| AC-3
|
AC-1
|
230V
|
400V/415V
|
500V
|
690V
|
1-Phase
|
3-Phase
|
| 115V
|
230V
|
200V
|
230V
|
460V
|
575V
|
N.O.
|
N.C.
|
| 9
|
32
|
3
|
4
|
4
|
4
|
1/2
|
1-1/2
|
2
|
2
|
5
|
7-1/2
|
1
|
0
|
§
|
100-C09Ä10
|
| 0
|
1
|
§
|
100-C09Ä01
|
| 12
|
32
|
4
|
5.5
|
5.5
|
5.5
|
1/2
|
2
|
3
|
3
|
7-1/2
|
10
|
1
|
0
|
§
|
100-C12Ä10
|
| 0
|
1
|
§
|
100-C12Ä01
|
| 16
|
32
|
5.5
|
7.5
|
7.5
|
7.5
|
1
|
3
|
5
|
5
|
10
|
15
|
1
|
0
|
§
|
100-C16Ä10
|
| 0
|
1
|
§
|
100-C16Ä01
|
| 23
|
32
|
7.5
|
11
|
13
|
10
|
2
|
3
|
5
|
7-1/2
|
15
|
15
|
1
|
0
|
100-C23Ä10
|
| 0
|
1
|
100-C23Ä01
|
| 30
|
65
|
10
|
15
|
15
|
15
|
2
|
5
|
7-1/2
|
10
|
20
|
25
|
0
|
0
|
100-C30Ä00
|
| 1
|
0
|
100-C30Ä10
|
| 0
|
1
|
100-C30Ä01
|
| 37
|
65
|
11
|
18.5/20
|
20
|
18.5
|
3
|
5
|
10
|
10
|
25
|
30
|
0
|
0
|
100-C37Ä00
|
| 1
|
0
|
100-C37Ä10
|
| 0
|
1
|
100-C37Ä01
|
| 43
|
85
|
13
|
22
|
25
|
22
|
3
|
7-1/2
|
10
|
15
|
30
|
30
|
0
|
0
|
100-C43Ä00
|
| 1
|
0
|
100-C43Ä10
|
| 0
|
1
|
100-C43Ä01
|
| 60
|
100
|
18.5
|
32
|
37
|
32
|
5
|
10
|
15
|
20
|
40
|
50
|
0
|
0
|
100-C60Ä00
|
| 1
|
0
|
100-C60Ä10
|
| 0
|
1
|
100-C60Ä01
|
| 72
|
100
|
22
|
40
|
45
|
40
|
5
|
15
|
20
|
25
|
50
|
60
|
0
|
0
|
100-C72Ä00
|
| 1
|
0
|
100-C72Ä10
|
| 0
|
1
|
100-C72Ä01
|
| 85
|
100
|
25
|
45
|
55
|
45
|
7-1/2
|
15
|
25
|
30
|
60
|
60
|
0
|
0
|
100-C85Ä00
|
| 1
|
0
|
100-C85Ä10
|
| 0
|
1
|
100-C85Ä01
|
| 97
|
130
|
30
|
55
|
55
|
55
|
10
|
15
|
30
|
30
|
75
|
75
|
0
|
0
|
100-C97Ä00
|
| 1
|
0
|
100-C97Ä10
|
| 0
|
1
|
100-C97Ä01
|
|
|
| § For screwless terminals, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C09Ä10 becomes Cat. No. 100-CR09Ä10.
|
Ä Coil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position
4-Pole AC- and DC-Operated Contactors
| Ie [A]
|
Ratings for Switching AC Motors — AC-2, AC-3
|
Contact Configuration, Main Pole
|
Cat. No.
|
| 3-Phase kW (50 Hz)⋆
|
Hp (60 Hz)
|
|
|
| AC-3
|
AC-1
|
230V
|
400V/415V
|
500V
|
690V
|
1-Phase
|
3-Phase ⋆
|
| 115V
|
230V
|
200V
|
230V
|
460V
|
575V
|
N.O.
|
N.C.
|
| 9
|
32
|
3
|
4
|
4
|
4
|
1/2
|
1-1/2
|
2
|
2
|
5
|
7-1/2
|
4
|
0
|
§
|
100-C09Ä400
|
| 3
|
1
|
§
|
100-C09Ä300
|
| 2
|
2
|
§
|
100-C09Ä200
|
| 12
|
32
|
4
|
5.5
|
5.5
|
5.5
|
1/2
|
2
|
3
|
3
|
7-1/2
|
10
|
4
|
0
|
§
|
100-C12Ä400
|
| 3
|
1
|
§
|
100-C12Ä300
|
| 2
|
2
|
§
|
100-C12Ä200
|
| 16
|
32
|
5.5
|
7.5
|
7.5
|
7.5
|
1
|
3
|
5
|
5
|
10
|
15
|
4
|
0
|
§
|
100-C16Ä400
|
| 3
|
1
|
§
|
100-C16Ä300
|
| 2
|
2
|
§
|
100-C16Ä200
|
| 23
|
32
|
7.5
|
11
|
13
|
10
|
2
|
3
|
5
|
7-1/2
|
15
|
15
|
4
|
0
|
100-C23Ä400
|
| 3
|
1
|
100-C23Ä300
|
| 2
|
2
|
100-C23Ä200
|
| 37
|
75
|
11
|
18.5/20
|
20
|
18.5
|
3
|
5
|
10
|
10
|
25
|
30
|
4
|
0
|
100-C40Ä400
|
| 2
|
2
|
100-C40Ä200
|
| 85
|
130
|
25
|
45
|
55
|
45
|
7-1/2
|
15
|
25
|
30
|
60
|
50
|
4
|
0
|
100-C90Ä400
|
| 2
|
2
|
100-C90Ä200
|
|
|
| ⋆ Three-phase ratings apply only to contactors with at least three N.O. power poles.
|
| § For screwless terminals, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C09Ä400 becomes Cat. No. 100-CR09Ä400.
|
Ä Coil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position
Reversing AC- and DC-Operated Contactors
| Ie [A]
|
Ratings for Switching AC Motors — AC-2, AC-3, AC-4
|
Auxiliary Contacts Installed per Contactor
|
Cat. No.
|
| 3-Phase kW (50 Hz)
|
Hp (60 Hz)
|
|
|
| AC-3
|
AC-1
|
230V
|
400V/415V
|
500V
|
690V
|
1-Phase
|
3-Phase
|
| 115V
|
230V
|
200V
|
230V
|
460V
|
575V
|
N.O.
|
N.C.⋆
|
| 9
|
32
|
3
|
4
|
4
|
4
|
1/2
|
1-1/2
|
2
|
2
|
5
|
7-1/2
|
1
|
1
|
104-C09Ä22
|
| 12
|
32
|
4
|
5.5
|
5.5
|
5.5
|
1/2
|
2
|
3
|
3
|
7-1/2
|
10
|
1
|
1
|
104-C12Ä22
|
| 16
|
32
|
5.5
|
7.5
|
7.5
|
7.5
|
1
|
3
|
5
|
5
|
10
|
15
|
1
|
1
|
104-C16Ä22
|
| 23
|
32
|
7.5
|
11
|
13
|
10
|
2
|
3
|
5
|
7-1/2
|
15
|
15
|
1
|
1
|
104-C23Ä22
|
| 30
|
65
|
10
|
15
|
15
|
15
|
2
|
5
|
7-1/2
|
10
|
20
|
25
|
0
|
1
|
104-C30Ä02
|
| 1
|
1
|
104-C30Ä22
|
| 37
|
65
|
11
|
18.5/20
|
20
|
18.5
|
3
|
5
|
10
|
10
|
25
|
30
|
0
|
1
|
104-C37Ä02
|
| 1
|
1
|
104-C37Ä22
|
| 43
|
85
|
13
|
22
|
25
|
22
|
3
|
7.5
|
10
|
15
|
30
|
30
|
0
|
1
|
104-C43Ä02
|
| 1
|
1
|
104-C43Ä22
|
| 60
|
100
|
18.5
|
32
|
37
|
32
|
5
|
10
|
15
|
20
|
40
|
50
|
0
|
1
|
104-C60Ä02
|
| 1
|
1
|
104-C60Ä22
|
| 72
|
100
|
22
|
40
|
45
|
40
|
5
|
15
|
20
|
25
|
50
|
60
|
0
|
1
|
104-C72Ä02
|
| 1
|
1
|
104-C72Ä22
|
| 85
|
100
|
25
|
45
|
55
|
45
|
7-1/2
|
15
|
25
|
30
|
60
|
60
|
0
|
1
|
104-C85Ä02
|
| 1
|
1
|
104-C85Ä22
|
| 97
|
130
|
30
|
55
|
55
|
55
|
10
|
15
|
30
|
30
|
75
|
75
|
0
|
1
|
104-C97Ä02
|
| 1
|
1
|
104-C97Ä22
|
|
|
⋆ The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock.
Ä Coil Voltage Code and Terminal Position
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz:
Cat. No. 100-C09Ä10 becomes Cat. No.100-C09D10.
| [V]
|
12
|
24
|
32
|
36
|
42
|
48
|
100
|
100-110
|
110
|
120
|
127
|
200
|
200-220
|
208
|
208-240
|
220-230
|
230
|
230-240
|
240
|
277
|
347
|
380
|
380-400
|
400
|
400-415
|
440
|
480
|
500
|
550
|
600
|
| Hz
|
| 50 Hz
|
R
|
K
|
V
|
W
|
X
|
Y
|
KP
|
—
|
D
|
P
|
S
|
KG
|
L
|
—
|
—
|
F
|
—
|
VA
|
T
|
—
|
—
|
—
|
N
|
—
|
G
|
B
|
—
|
M
|
C
|
—
|
| 60 Hz
|
Q
|
J
|
—
|
V
|
—
|
X
|
—
|
KP
|
—
|
D
|
—
|
—
|
KG
|
H
|
L
|
—
|
—
|
—
|
A
|
T
|
I
|
E
|
—
|
—
|
—
|
N
|
B
|
—
|
—
|
C
|
| 50/60 Hz
|
—
|
KJ
|
—
|
—
|
—
|
KY
|
KP
|
—
|
KD
|
—
|
—
|
KG
|
KL§
|
—
|
—
|
KL§
|
KF
|
—
|
KA
|
—
|
—
|
—
|
—
|
KN
|
—
|
KB
|
—
|
—
|
—
|
—
|
|
|
| § Not available on 100/104-C90 or -C97 contactors.
|
| DC Voltages [V]
|
9
|
12
|
24
|
36
|
48
|
48-72
|
60
|
64
|
72
|
80
|
110
|
110-125
|
115
|
125
|
220
|
220-250
|
230
|
250
|
| 100-C09…C43
|
Standard
|
ZR
|
ZQ
|
ZJ
|
ZW
|
ZY
|
—
|
ZZ
|
ZB
|
ZG
|
ZE
|
ZD
|
—
|
ZP
|
ZS
|
ZA
|
—
|
ZF
|
ZT
|
| with Integrated Diode
|
—
|
—
|
DJ
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
—
|
| Electronic with Integrated Diode
|
—
|
EQ
|
EJ
|
—
|
—
|
EY
|
—
|
—
|
—
|
—
|
—
|
ED
|
—
|
—
|
—
|
EA
|
—
|
—
|
| 100-C60…C97
|
with Integrated Diode
|
DR
|
DQ
|
DJ
|
DW
|
DY
|
—
|
DZ
|
DB
|
DG
|
DE
|
DD
|
—
|
DP
|
DS
|
DA
|
—
|
DF
|
DT
|
|
|
Coil Terminal Position
All contactors are delivered with the coil terminals located on the line side.
For load side coil terminations, insert a U prior to the coil voltage code.
Ordering example: Cat. No. 100-C09UD10.
Cat. No.100-C09Ä10Line Side
|
|