Contactors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Bulletin 100-C Contactors

Bulletin 100-C Contactors

Introduction Standards Compliance and Certifications Product Selection Assignment of Contacts Bulletin 100-C/104-C Accessories
Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications Bulletin 100-C/104-C Life-Load Curves Bulletin 100-C/104-C Approximate Dimensions Renewal Parts
Product Selection

3-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Aux. Contacts Cat. No.
3-Phase kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/415V 500V 690V 1-Phase 3-Phase
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 1 0 §  100-C09Ä10
0 1 §  100-C09Ä01
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 1 0 §  100-C12Ä10
0 1 §  100-C12Ä01
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 1 0 §  100-C16Ä10
0 1 §  100-C16Ä01
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 1 0 100-C23Ä10
0 1 100-C23Ä01
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 0 100-C30Ä00
1 0 100-C30Ä10
0 1 100-C30Ä01
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 0 100-C37Ä00
1 0 100-C37Ä10
0 1 100-C37Ä01
43 85 13 22 25 22 3 7-1/2 10 15 30 30 0 0 100-C43Ä00
1 0 100-C43Ä10
0 1 100-C43Ä01
60 100 18.5 32 37 32 5 10 15 20 40 50 0 0 100-C60Ä00
1 0 100-C60Ä10
0 1 100-C60Ä01
72 100 22 40 45 40 5 15 20 25 50 60 0 0 100-C72Ä00
1 0 100-C72Ä10
0 1 100-C72Ä01
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 0 100-C85Ä00
1 0 100-C85Ä10
0 1 100-C85Ä01
97 130 30 55 55 55 10 15 30 30 75 75 0 0 100-C97Ä00
1 0 100-C97Ä10
0 1 100-C97Ä01
  
§ For screwless terminals, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C09Ä10 becomes Cat. No. 100-CR09Ä10.

Ä Coil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


4-Pole AC- and DC-Operated Contactors

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3 Contact Configuration, Main Pole Cat. No.
3-Phase kW (50 Hz)⋆  Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/415V 500V 690V 1-Phase 3-Phase ⋆ 
115V 230V 200V 230V 460V 575V N.O. N.C.
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 4 0 §  100-C09Ä400
3 1 §  100-C09Ä300
2 2 §  100-C09Ä200
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 4 0 §  100-C12Ä400
3 1 §  100-C12Ä300
2 2 §  100-C12Ä200
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 4 0 §  100-C16Ä400
3 1 §  100-C16Ä300
2 2 §  100-C16Ä200
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 4 0 100-C23Ä400
3 1 100-C23Ä300
2 2 100-C23Ä200
37 75 11 18.5/20 20 18.5 3 5 10 10 25 30 4 0 100-C40Ä400
2 2 100-C40Ä200
85 130 25 45 55 45 7-1/2 15 25 30 60 50 4 0 100-C90Ä400
2 2 100-C90Ä200
  
⋆ Three-phase ratings apply only to contactors with at least three N.O. power poles.
§ For screwless terminals, add an "R" after the letter "C" in the catalog number. Example: Cat. No. 100-C09Ä400 becomes Cat. No. 100-CR09Ä400.

Ä Coil voltage code and terminal position—see Ä Coil Voltage Code and Terminal Position


Reversing AC- and DC-Operated Contactors

Click to enlarge - 100C_104C-67-2 Click to enlarge - 100C_104C-69-2 Click to enlarge - 100C_104C-69-3

Ie [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Auxiliary Contacts
Installed per Contactor
Cat. No.
3-Phase kW (50 Hz) Hp (60 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
AC-3 AC-1 230V 400V/415V 500V 690V 1-Phase 3-Phase
115V 230V 200V 230V 460V 575V N.O. N.C.⋆ 
9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 1 1 104-C09Ä22
12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 1 1 104-C12Ä22
16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 1 1 104-C16Ä22
23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 1 1 104-C23Ä22
30 65 10 15 15 15 2 5 7-1/2 10 20 25 0 1 104-C30Ä02
1 1 104-C30Ä22
37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 0 1 104-C37Ä02
1 1 104-C37Ä22
43 85 13 22 25 22 3 7.5 10 15 30 30 0 1 104-C43Ä02
1 1 104-C43Ä22
60 100 18.5 32 37 32 5 10 15 20 40 50 0 1 104-C60Ä02
1 1 104-C60Ä22
72 100 22 40 45 40 5 15 20 25 50 60 0 1 104-C72Ä02
1 1 104-C72Ä22
85 100 25 45 55 45 7-1/2 15 25 30 60 60 0 1 104-C85Ä02
1 1 104-C85Ä22
97 130 30 55 55 55 10 15 30 30 75 75 0 1 104-C97Ä02
1 1 104-C97Ä22
  

⋆ The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock.


Ä Coil Voltage Code and Terminal Position

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60Hz:
Cat. No. 100-C09Ä10 becomes Cat. No.100-C09D10.


[V] 12 24 32 36 42 48 100 100-110 110 120 127 200 200-220 208 208-240 220-230 230 230-240 240 277 347 380 380-400 400 400-415 440 480 500 550 600
Hz
50 Hz R K V W X Y KP D P S KG L F VA T N G B M C
60 Hz Q J V X KP D KG H L A T I E N B C
50/60 Hz KJ KY KP KD KG KL§  KL§  KF KA KN KB
  
§ Not available on 100/104-C90 or -C97 contactors.

DC Voltages [V] 9 12 24 36 48 48-72 60 64 72 80 110 110-125 115 125 220 220-250 230 250
100-C09…C43 Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode DJ
Electronic with Integrated Diode EQ EJ EY ED EA
100-C60…C97 with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT
  

Coil Terminal Position

  • All contactors are delivered with the coil terminals located on the line side.


  • For load side coil terminations, insert a “U” prior to the coil voltage code.
    Ordering example: Cat. No. 100-C09UD10.


  • Click to enlarge - 100C_104C-68-1
    Cat. No.100-C09Ä10Line Side


    Click to enlarge - 100C_104C-68-2
    Cat. No.100-C09UÄ10Load Side