Contactors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Bulletin 100-C Contactors

Bulletin 100-C Contactors

Introduction Standards Compliance and Certifications Product Selection Assignment of Contacts Bulletin 100-C/104-C Accessories
Bul. 100-K/104-K, 100-C/104-C, 100-D/104-D, 100S-C/104S-C, 100S-D Specifications Bulletin 100-C/104-C Life-Load Curves Bulletin 100-C/104-C Approximate Dimensions Renewal Parts
Bulletin 100-C/104-C Accessories

Auxiliary Contacts (For 100-C09…C97 contactors)

  Description Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a Connection Diagrams For Use With Standard Auxiliary Contact Cat. No.§  Bifurcated Auxiliary Contact Cat. No.
N.O. N.C.
Click to enlarge - 100-C_104-C-86-3 Auxiliary Contact Blocks for Front Mounting⋆ 
  • 2- and 4-pole

  • Quick and easy mounting without tools

  • Electronic-compatible contacts down to 17V, 5 mA

  • Mechanically linked performance between N.O. and N.C. poles and to the main contactor poles (except for L types)

  • Models with equal function with several terminal numbering choices

  • 1L = Late break N.C./early make N.O.

  • Bifurcated version for switching down to 5V, 3 mA also available
  • 0 2 Click to enlarge - 100-C_104-C-86-6 100-C all 100-FA02 100-FAB02
    C30Ä00…C97Ä00 100-FB02 100-FBB02
    1 1 100-C all 100-FA11 100-FAB11
    C30Ä00…C97Ä00 100-FB11 100-FBB11
    C09Ä10…C23Ä10 100-FC11 100-FCB11
    2 0 100-C all 100-FA20 100-FAB20
    C30Ä00…C97Ä00 100-FB20 100-FBB20
    1L 1L 100-C all 100-FAL11
    C30Ä00…C97Ä00 100-FBL11
    Click to enlarge - 100-C_104-C-86-4 0 4 100-C all 100-FA04 100-FAB04
    1 3 100-C all 100-FA13 100-FAB13
    2 2 100-C all 100-FA22 100-FAB22
    C30Ä00…C97Ä00 100-FB22 100-FBB22
    C09Ä10…C23Ä10 100-FC22 100-FCB22
    3 1 100-C all 100-FA31 100-FAB31
    C09Ä10…C23Ä10 100-FC31 100-FCB31
    4 0 100-C all 100-FA40 100-FAB40
    1+1L 1+1L 100-C all 100-FAL22
    Click to enlarge - 100-C_104-C-86-5 Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations⋆ 
  • 1- and 2-pole

  • Two-way numbering for right or left mounting on the contactor

  • Quick and easy mounting without tools

  • Electronic-compatible contacts down to 17V, 10 mA

  • Mirror contact performance to the main contactor poles

  • 1L = Late break N.C./early make N.O.
  •   
    0  
    1 Click to enlarge - 100-C_104-C-86-7 100-C all 100-SA01
      
    1  
    0 100-C all 100-SA10
      
    0  
    2 100-C all 100-SA02
    Click to enlarge - 100-C_104-C-86-8   
    1  
    1 100-C all 100-SA11
      
    2  
    0 100-C all 100-SA20
      
    1L  
    1L 100-C all 100-SAL11
    Click to enlarge - 100-C_104-C-86-9 Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations⋆ 
  • 1- and 2-pole

  • Two-way numbering for right or left mounting on the contactor

  • Quick and easy mounting without tools

  • Electronic-compatible contacts down to 17V, 10 mA

  • Mirror contact performance to the main contactor poles

  • 1L = Late break N.C./early make N.O.
  •   
    0  
    1 Click to enlarge - 100-C_104-C-86-10 100-C 100-SB01
      
    1  
    0 100-C‡  100-SB10
      
    0  
    2 100-C‡  100-SB02
    Click to enlarge - 100-C_104-C-86-11   
    1  
    1 100-C‡  100-SB11
    2  
      
    0 100-C‡  100-SB20
      
    1L  
    1L 100-C‡  100-SBL11
      
    ⋆ Max. number of auxiliary contacts that may be mounted:
        AC and 24V DC electronic coil contactors — max. 4 N.O. contacts on the front of the contactor, 2 N.O. contacts on the side, 4 N.C. front or side, 6 total.
        DC coil contactors — max. 4 N.O. contacts on the front of the contactor or max 2 N.O. contacts on the side, 4 N.C. front or side, 4 total.
    ‡ Double numbering — Left-side mounting only is recommended for Cat. No. 100-C09…100-C23 due to double numbering.
    § For screwless terminals (front mount only), insert "CR" after the "100-" in the catalog number. Example: Cat. No. 100-FA02 becomes Cat. No. 100-CRFA02.

    Control Modules (For 100-C09…C97 contactors)

      Description Connection Diagrams For Use With Cat. No.
    Click to enlarge - 100-C_104-C-87-1 Pneumatic Timing Modules
  • Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.
  • On-Delay  
    0.3…30 s Range
    Click to enlarge - 100-C_104-C-87-2 100-C or 700-CF with AC coils or DC electronic coils§    
    100-FPTA30
    2…180 s Range 100-FPTA180
    Off-Delay  
    0.3…30 s Range
    Click to enlarge - 100-C_104-C-87-3 100-C all, 700-CF all   
    100-FPTB30
    2…180 s Range 100-FPTB180
    Click to enlarge - 100-ETA3 L_gs- Electronic Timing Modules — On-Delay
    Delay of the contactor or control relay solenoid.
    The contactor or control relay is energized at the end of the delay time.
    0.1…3 s Range Click to enlarge - 100-C_104-C-87-5 100-C or 700-CF with
    110…240V,
    50/60 Hz or
    110…250V conventional DC coils
    100-ETA3
    1…30 s Range 100-ETA30
    10…180 s Range 100-ETA180
    0.1…3 s Range Click to enlarge - 100-C_104-C-87-6 100-C or 700-CF with 24…48V conventional DC coils or 24V DC electronic coils 100-ETAZJ3
    0.1…3 s Range 100-ETA3
    10…180 s Range 100-ETAZJ180
    Click to enlarge - 100-ETB3 L_gs Electronic Timing Modules — Off-Delay
    Delay of the contactor or control relay solenoid.
    After interruption of the control signal, the contactor or control relay is deenergized at the end of the delay time.
    0.3…3 s Range Click to enlarge - 100-C_104-C-87-8 100-C09…C37 or 700-CF with 24V 50/60 Hz coils 100-ETBKJ3
    1…30 s Range 100-ETBKJ30
    10…180 s Range 100-ETBKJ180
    0.3…3 s Range 100-C or 700-CF with 110…240V 50/60 Hz coils 100-ETB3
    1…30 s Range 100-ETB30
    10…180 s Range 100-ETB180
    Click to enlarge - 100-C_104-C-87-9 Electronic Timing Modules
  • Delay of the contactor solenoid. Contactor K 3 (Y) is de-energized (off) and K 2 (D) is energized (on) after the end of the set Y end time. (Switching delay at 50 ms.)

  • Continuous adjustment range

  • High repeat accuracy
  • Transition Time Y Contactor
    1…30 s Range
    Click to enlarge - 100-C_104-C-87-10 100-C with 110…240V, 50/60 Hz coils 100-ETY30
    Click to enlarge - 100-C_104-C-87-11 Mechanical Interlocks
  • For interlocking of two contactors.

  • Common interlock for all Bul. 100-C contactor sizes

  • Interlocking of different sizes possible

  • Mechanical and electrical interlocking possible in one module by means of integrated auxiliary contacts

  • 9 mm dovetail connector included
  • Mechanical only,
    without auxiliary contacts
    Click to enlarge - 100-C_104-C-87-12 100-C (except 100-C40, -C90) 100-MCA00
    Mechanical/ electrical interlock with 2 N.C. auxiliary contacts Click to enlarge - 100-C_104-C-87-13 100-C (except 100-C40, -C90) 100-MCA02
    Click to enlarge - 100-C_104-C-87-15 Mechanical Latch
  • Following contactor latching, the contactor coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66).

  • Electrical or manual release

  • 1 N.O. + 1 N.C. auxiliary contacts

  • Suitable for all Bul. 100-C contactor sizes, 9…97 A
  • Maximum command duration 0.03…10 s Click to enlarge - 100-C_104-C-87-14 100-C with AC or DC electronic coils (except 100-C90) 100-FL11Ä
      
    § Cannot be used with side-mounted auxiliary contacts on 700-CF DC relays.

    Ä Coil Voltage Code

    The cat. no. as listed is incomplete. Select a voltage suffix code from the table below to complete the cat. no. Example: 120V, 60 Hz:
    Cat. No. 100-FL11Ä becomes Cat. No. 100-FL11D.


    Voltage⋆  [V] 24 48 100 110 120 230…240 240 277 380…400 400…415 440 480
    50 Hz K Y KP D VA KA N G B
    60 Hz J D KA T N B
      
    ⋆ For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

    Control Modules (For 100-C09…C97 contactors), Continued

    Click to enlarge - 100-C_104-C-88-1 Description Voltage Range Connection Diagrams For Use With Cat. No.
    DC Interface (Electronic)
  • Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor.

  • Requires no additional surge suppression on the relay coils
  • Input: 12V DC
    Output: 110…240V AC
    Click to enlarge - 100-C_104-C-88-2 100-C with AC coils 110…240V AC 100-JE12
    Input: 24V DC
    Output: 110…240V AC
    100-JE
    Input: 48V DC
    Output: 110…240V AC
    100-JE48
    Click to enlarge - 100-C_104-C-88-3 Surge Suppressors
  • For limitation of coil switching transients.

  • Plug-in, coil mounted.

  • Suitable for 100-C contactor sizes, 9…97 A.

  • RC, varistor, and diode versions.
  • RC Module
    AC operating mechanism
    24…48V AC, 50/60 Hz Click to enlarge - 100D-92-2 100-C with AC coils §  100-FSC48
    110…280V AC, 50/60 Hz §  100-FSC280
    380…480V AC, 50/60 Hz §  100-FSC480
    Varistor Module
    AC/DC operating mechanism
    12…55V AC/ 12…77V DC Click to enlarge - 100-C_104-C-88-5 100-C with AC coils or 100-C09…-C43 with conventional DC coils §  100-FSV55
    56…136V AC/ 78…180V DC §  100-FSV136
    137…277V AC/ 181…350V DC §  100-FSV277
    278…575V AC §  100-FSV575
    Diode Module
    DC operating mechanism
    12…250V DC Click to enlarge - 100-C_104-C-88-6 100-C09…-C43 with conventional DC coils §  100-FSD250
      
    § For screwless terminals, insert "CR" after the "100-" in the catalog number. Example: Cat. No. 100-FSC48 becomes Cat. No. 100-CRFSC48.

    Assembly Components (For 100-C09…C97 contactors)

      Description For Use With Pkg. Quantity Cat. No.
    Click to enlarge - 100-C_104-C-88-7 Dovetail Connectors
  • For use in contactor and starter assemblies.

  • Single Connector — 0 mm Spacing
  • 100-C 10 100-S0
    Cat. No. 100-S0 Dovetail Connectors
  • For use in contactor and starter assemblies.

  • Dual Connector — 9 mm Spacing
  • 10 100-S9
    Click to enlarge - 100-C_104-C-88-8 Protective Covers
  • Provides protection against unintended manual operation

  • For contactors and front-mounted auxiliary contacts, pneumatic timers, and latches
  • 100-C all 1 100-SCCA
    Cat. No. 100-SCCA
    Click to enlarge - 100-C_104-C-88-9 100-FA, -FB, -FC, -FP, -FL; 10 100-SCFA
    Cat. No. 100-SCFA
    Click to enlarge - 100-C_104-C-88-10 Reversing Power Wiring Kits
  • For reversing connection with a solid-state or thermal overload relay
  •   
    100-C09…C23  
    1 105-PW23
      
    100-C30…C37  
    1 105-PW37
      
    100-C43…C55  
    1 105-PW55
    Cat. No. 105-PW23   
    100-C60…C97  
    1 105-PW85
    Click to enlarge - 100-C_104-C-88-11 DIN (#3) symmetrical hat rail
    35 x 7.5 x 1 m
    140M-D
    140M-F
    100-C all
    10 199-DR1
      

    Wye-Delta/Star-Delta Starter Kits

    Wye-Delta power wiring kits were designed to aid in the field assembly of open-transition wye-delta starters that use Bulletin 100-C contactors. These kits include line, load, and start-point (shorting) connections. Assembling a wye-delta starter requires the use of the following additional components:


    Click to enlarge - 100-C_104-C-89-1
    Cat. No. 170-PW23


    3-Phase Rating Pkg.
    Qty.
    Cat. No.
    kW (50 Hz) Hp (60 Hz) Use with Cat. No. 100-
    230V 380/415V 500V 690V 200V 230V 460V 575V Delta Wye
    1M 2M 1S
    5.5 8 8 8 5 5 10 10 C09 C09 C09 1 170-PW23
    7.5 11 11 11 5 7.5 15 15 C12 C12 C09 1 170-PW23
    10 14 15 14 7.5 10 20 20 C16 C16 C12 1 170-PW23
    14 21 21 19 7.5 10 25 25 C23 C23 C12 1 170-PW23
    18 28 28 28 10 15 30 30 C30 C30 C16 1 170-PW37
    19 35 35 32 15 20 40 40 C37 C37 C23 1 170-PW37
    30 45 45 45 25 30 60 60 C55 C55 C30 1 170-PW55
    33 58 60 56 30 40 75 75 C60 C60 C37 1 170-PW72
    39 69 67 70 40 50 100 100 C72 C72 C43 1 170-PW72
    47 82 82 81 50 60 125 125 C85 C85 C60 1 170-PW85
    50 90 90 90 50 60 125 125 C97 C97 C60 1 170-PW85
      
    Package Quantity = 1

    Marking Systems (For 100-C09…C97 contactors)

      Description Pkg. Qty.⋆  Cat. No.
    Click to enlarge - 100-C_104-C-89-2 Label Sheet
    105 self-adhesive paper labels each, 6 x 17 mm
    10 100-FMS
    Click to enlarge - 100-C_104-C-89-3 Marking Tag Sheet
    160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
    10 100-FMP
    Transparent Cover
    To be used with marking tag sheets
    100 100-FMC
    Click to enlarge - 100-FMA1 Marking Tag Adapters
    To be used with marking tag: System V4/V5
    100 100-FMA1
    Marking Tag Adapters
    To be used with marking tag: System 1492 W
    100 100-FMA2
      
    ⋆ Must be ordered in multiples of package quantities.

    Terminal Kits (For 100-C09…C97 contactors)

      Description Max. Current Ratings and Wire Sizes Pkg. Qty.⋆  Cat. No.
    Click to enlarge - 100-C_104-C-90-1 Stab Connector Kit
    Dual stab (0.250 in.) for 100-C coil terminals
    For 100-C09…C97 contactors
    20 199-SC2
    Click to enlarge - 100-C_104-C-90-2 Stab Connector Kit
    Dual stab (0.250 in.) for 100-C power terminals
    For 100-C09…C23 contactors
    100 199-SC10
    Click to enlarge - 100_CTN23 3-Pole Terminal Lug Kit
    For Cat. No. 100-C09…C23 (Line side)
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    45 A (4…16 mm2‡ , fine stranded w/ ferrule)
    45 A (4…25 mm2, coarse stranded/solid)
    40 A (#10…4 AWG, stranded/solid)
    1 100-CTN23
    3-Pole Terminal Lug Kit
    For Cat. No. 100-C09…C23 (Load side)
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    45 A (4…16 mm2‡ , fine stranded w/ ferrule)
    45 A (4…25 mm2, coarse stranded/solid)
    40 A (#10…4 AWG, stranded/solid)
    1 100-CTL23
    3-Pole Terminal Lug Kit
    For Cat. No. 100-C30…C37 (Line and load side)
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    60 A (4…16 mm2‡ , fine stranded w/ ferrule)
    60 A (4…25 mm2, coarse stranded/solid)
    55 A (#10…4 AWG, stranded/solid)
    1 100-CT37
    Click to enlarge - 100_CT43 1-Pole Terminal Lug Kit
    For Cat. No. 100-C43…C55
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    90 A (6…35 mm2, fine stranded w/ ferrule)
    90 A (6…50 mm2, coarse stranded/solid)
    75 A (#8…2 AWG, stranded/solid)
    3 100-CT43
    1-Pole Terminal Lug Kit
    For Cat. No. 100-C60…C97
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    130 A (10…70 mm2, fine stranded w/ ferrule)
    130 A (10…95 mm2, coarse stranded/solid)
    130 A (#8…2/0 AWG, stranded/solid)
    3 100-CT85
    Click to enlarge - 100CP23 3-Pole Paralleling Kit
    For Cat. No. 100-C09…C23
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    100 A (35…70 mm2, fine stranded w/ ferrule)
    100 A (35…95 mm2, coarse stranded/solid)
    100 A (#0…2/0 AWG, stranded/solid)
    2 100-CP23
    3-Pole Paralleling Kit
    For Cat. No. 100-C30…C37
    IEC @ 40 °C
    IEC @ 40 °C
    UL/CSA (Encl.)
    150 A (35…70 mm2, fine stranded w/ ferrule)
    150 A (35…95 mm2, coarse stranded/solid)
    150 A (#0…2/0 AWG, stranded/solid)
    2 100-CP37
      
    ⋆ Must be ordered in multiples of the package quantity.
    ‡ 16 mm2 max. according to IEC 60947; actual max. 25 mm2.

    SEMI-F47 Voltage Sag Immunity Module

      Description Input Voltage For Use With§  Options Cat. No.
    Click to enlarge - CSF47A30_alone2 SEMI-F47 Module
  • Meets SEMI-F47 voltage sag immunity requirements

  • Direct mounting to coil terminals of 100-C contactors and 700-CF control relays

  • Requires DC coil contactor

  • Optional 1…30 s ON-delay timer version
  • 24…240V AC 100-C60…C97
    700-CF
    without timer 100-CSF47
    110…240V AC 100-C60…C97
    700-CF
    with 1…30 s ON-delay timer 100-CSF47A30
      
    § Contactor must have DC coil at the same voltage as AC input. Example: for 24V AC control, select Cat. No. 100-C09ZJ10 (24V DC coil).