Specifications

Bul. 100-K/104-K, 100-C/104-C, 100-D/104-D, 100S-C/104S-C, 100S-D Specifications

  100-KR 100/104-K 100/104-C, 100S/104S-C
  05 09 05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X X X
  Electronic — EI
AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
    Ie £ 500V [A] 10 10 20 20 20 32 32 32 32 (40)⋆  65 65 75 75 85 100
690V [A] 10 10 20 20 20 32 32 32 32 (40)⋆  65 65 75 75 85 100
1000V [A]
230V [kW] 4 4 8 8 8 13 13 13 13 26 26 30 30 34 40
240V [kW] 4 4 8.3 8.3 8.3 13 13 13 13 27 27 31 31 35 42
400V [kW] 6.9 6.9 14 14 14 22 22 22 22 45 45 52 52 59 69
415V [kW] 7 7 14 14 14 23 23 23 23 47 47 54 54 61 72
500V [kW] 8.7 8.7 17 17 17 28 28 28 28 56 56 65 65 74 87
690V [kW] 12 12 24 24 24 38 38 38 38 78 78 90 90 102 120
1000V [kW]
Ambient temperature 60 °C
    Ie £ 500V [A] 10 10 16 16 16 32 32 32 32 65 65 60 60 80 100
690V [A] 10 10 16 16 16 32 32 32 32 65 65 60 60 80 100
1000V [A]
230V [kW] 4 4 6.4 6.4 6.4 13 13 13 13 26 26 24 24 25 40
240V [kW] 4 4 6.7 6.7 6.7 13 13 13 13 27 27 25 25 26 42
400V [kW] 6.9 6.9 11 11 11 22 22 22 22 45 45 42 42 44 69
415V [kW] 7 7 12 12 12 23 23 23 23 47 47 43 43 45 72
500V [kW] 8.7 8.7 14 14 14 28 28 28 28 56 56 52 52 55 87
690V [kW] 12 12 19 19 19 38 38 38 38 78 78 72 72 75 120
1000V [kW]
Switching of 3-phase Motors; (50 Hz)
Ambient temperature 60 °C, AC-2, AC-3
  230V [A] 6.3 8.5 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
240V [A] 6.3 8.5 6.3 11.3 11.3 12 15 20 26.5 35 38 38 38 44 62
400V [A] 4.9 8.5 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
415V [A] 4.9 8.5 4.9 8.5 11.5 9 12 16 23 30 37 37 37 43 60
500V [A] 3.9 6.8 3.9 6.8 9.2 7 10 14 20 25 30 29 30 38 55
690V [A] 2.8 4.9 2.8 4.9 6.7 5 7 9 12 18 21 9 21 25 34
1000V [A]
230V [kW] 1.5 2.2 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
240V [kW] 1.5 2.2 1.5 3 3 3 4 5.5 7.5 10 11 11 11 13 18.5
400V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 11 15 18.5 18.5 18.5 22 32
415V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 11 15 20 20 20 22 32
500V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 13 15 20 18.5 20 25 37
690V [kW] 2.2 4 2.2 4 5.5 4 5.5 7.5 10 15 18.5 7.5 18.5 22 32
1000V [kW]
Load Carrying Capacity per UL/CSA
General Purpose Current (enclosed)
  [A] 9 9 12 15 18 25 25 30 30 55 60 60 60 75 90
Rated power (enclosed)
    1-phase 115V [A] 7.2 7.2 9.8 9.8 13.8 9.8 9.8 16 24 24 34 34 34 34 56
230V [A] 6.9 8 8 10 12 10 12 17 17 28 28 28 28 40 50
115V [Hp] 1/3 1/3 0.5 0.5 0.75 0.5 0.5 1 2 2 3 3 3 3 5
230V [Hp] 3/4 1 1 1.5 2 1.5 2 3 3 5 5 5 5 7.5 10
    3-phase 200V [A] 6.9 7.8 6.9 7.8 11 7.8 11 17.5 17.5 25.3 32.2 32.2 32.2 32.2 48.3
230V [A] 6 6.8 6 6.8 9.6 6.8 9.6 15.2 22 28 28 28 28 42 54
460V [A] 4.8 7.6 4.8 7.6 11 7.6 11 14 21 27 34 34 34 40 52
575V [A] 3.9 6.1 3.9 6.1 9 9 11 17 17 27 32 17 32 32 52
200V [Hp] 1.5 2 1.5 2 3 2 3 5 5 7.5 10 10 10 10 15
230V [Hp] 1.5 2 1.5 2 3 2 3 5 7.5 10 10 10 10 15 20
460V [Hp] 3 5 3 5 7.5 5 7.5 10 15 20 25 25 25 30 40
575V [Hp] 3 5 3 5 7.5 7.5 10 15 15 25 30 15 30 30 50
  
⋆ Values in ( ) with increased cross-section and cable lug

  100/104-C, 100S/104S-C 100/104-D, 100S-D
  72 85 90*200 90*400 97 115 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X
AC-1 Active Power Load (50 Hz);
Ambient temperature 40 °C
    Ie £ 500V [A] 100 100 130 130 130 250 250 250 250 250 350 350 450 540 800 1000
690V [A] 100 100 130 130 130 250 250 250 250 250 350 350 450 540 800 1000
1000V [A] 250 250 250 250 250 350 350 450 540
230V [kW] 40 40 52 52 52 100 100 100 100 100 139 139 179 199 319 398
240V [kW] 42 42 54 54 54 104 104 104 104 104 145 145 187 208 333 416
400V [kW] 69 69 90 90 90 173 173 173 173 173 242 242 312 346 554 693
415V [kW] 72 72 93 93 93 180 180 180 180 180 252 252 323 359 575 719
500V [kW] 87 87 113 113 113 217 217 217 217 217 303 303 390 433 693 866
690V [kW] 120 120 155 155 155 299 299 299 299 299 418 418 538 598 956 1195
1000V [kW] 433 433 433 433 433 606 606 779 866
Ambient temperature 60 °C
    Ie £ 500V [A] 100 100 110 110 110 210 210 210 210 210 300 300 380 425
690V [A] 100 100 110 110 110 210 210 210 210 210 300 300 380 425
1000V [A] 210 210 210 210 210 300 300 380 425
230V [kW] 40 40 44 44 44 84 84 84 84 84 120 120 151 169
240V [kW] 42 42 46 46 46 87 87 87 87 87 125 125 158 177
400V [kW] 69 69 76 76 76 145 145 145 145 145 208 208 263 294
415V [kW] 72 72 79 79 79 151 151 151 151 151 216 216 273 305
500V [kW] 87 87 95 95 95 182 182 182 182 182 260 260 329 368
690V [kW] 120 120 131 131 131 251 251 251 251 251 359 359 454 508
1000V [kW] 364 364 364 364 364 520 520 658 736
Switching of 3-phase Motors; (50 Hz)
Ambient temperature 60 °C, AC-2, AC-3
  230V [A] 72 85 85 85 96 115 140 140 180 180 210 250 300 420 630 860
240V [A] 72 85 85 85 95 115 140 140 180 180 210 250 300 420 630 860
400V [A] 72 85 85 85 97 115 140 140 180 180 210 250 300 420 630 860
415V [A] 72 85 85 85 97 115 (130)§  140 (155)§  140 (155)§  180 (189)§  180 (189)§  210 (227)§  250 (258)§  300 (315)§  420 630 860
500V [A] 67 80 80 80 78 115 115 140 140 180 210 250 300 420 630 753
690V [A] 42 49 22 49 57 115 115 140 140 180 210 250 300 420 492
1000V [A] 46 55 55 65 65 80 95 115 160
230V [kW] 22 25 25 25 30 37 45 45 57 57 67 80 97 135 200 250
240V [kW] 22 25 25 25 30 38 47 47 60 60 70 83 101 141 200 250
400V [kW] 40 45 45 45 55 64 78 78 101 101 118 140 170 238 355 500
415V [kW] 40 45 45 45 55 66 (75)§  82 (90)§  82 (90)§  105 (110)§  105 (110)§  122 (132)§  145 (150)§  176 (185)§  250 355 500
500V [kW] 45 55 55 55 55 80 80 98 98 126 147 177 213 298 450 560
690V [kW] 40 45 18.5 45 55 111 111 135 135 176 205 250 293 424 500
1000V [kW] 63 75 75 90 90 110 132 160 225
Load Carrying Capacity per UL/CSA
General Purpose Current (enclosed)
    [A] 90 100 125 130 120 220 220 220 220 220 300 300 340 420 630 860
Rated power (enclosed)
    1-phase 115V [A] 56 80 80 80 100 100 135 135
230V [A] 68 68 68 68 88 110 136 136 176 176 216
115V [Hp] 5 7.5 7.5 7.5 10 10 15 15
230V [Hp] 15 15 15 15 20 25 30 30 40 40 50
    3-phase 200V [A] 62.1 78.2 78.2 78.2 92 120 120 120 150 150 177 221 285 414 552 692
230V [A] 68 80 80 80 80 104 130 130 154 154 192 248 312 420 602 720
460V [A] 65 77 65 77 96 96 124 124 180 180 180 240 302 414 590 702
575V [A] 62 62 22 52 77 99 125 125 144 144 192 242 289 382 562 651
200V [Hp] 20 25 25 25 30 40 40 40 50 50 60 75 100 150 200 250
230V [Hp] 25 30 30 30 30 40 50 50 60 60 75 100 125 175 250 300
460V [Hp] 50 60 50 60 75 75 100 100 150 150 150 200 250 350 500 600
575V [Hp] 60 60 20 50 75 100 125 125 150 150 200 250 300 400 600 700
  
§ 415 V: values in ( ) AC-2 and AC-3 lifespan -25 %

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X X
Electronic — EI
Switching of 3-phase Motors, (50Hz); Ambient temperature 60 °C, AC-4
  230V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
240V [A] 6.3 11.3 11.3 12 15 20 26.5 35 38 44 62
400V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
415V [A] 4.9 8.5 11.5 9 12 16 23 30 37 43 60
500V [A] 3.9 6.8 9.2 7 10 14 20 25 30 38 55
690V [A] 2.8 4.9 6.7 5 7 9 12 18 21 25 34
1000V [A]
230V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
240V [kW] 1.5 3 3 3 4 5.5 7.5 10 11 13 18.5
400V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 18.5 22 32
415V [kW] 2.2 4 5.5 4 5.5 7.5 11 15 20 22 32
500V [kW] 2.2 4 5.5 4 5.5 7.5 13 15 20 25 37
690V [kW] 2.2 4 5.5 4 5.5 7.5 10 15 18.5 22 32
1000V [kW]
AC-4 at approximately 200,000 operations
  230V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
240V [A] 2.3 3.9 3.9 4.3 6.6 9 9 12 14 16.5 25.5
400/415V [A] 2 3.6 3.6 4.3 6.6 9 9 12 14 16.5 25.5
500V [A] 1.9 3.2 3.2 4.3 6.6 9 9 12 14 16.5 25.5
690V [A] 4.3 6.6 9 9 12 14 16.5 25.5
1000V [A]
230V⋆  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 3.7 4 6.3
240V⋆  [kW] 0.37 0.75 0.75 0.75 1.5 2.2 2.2 3 4 4 7.5
400V⋆  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
415V⋆  [kW] 0.75 1.5 1.5 1.8 3 4 4 5.5 6.3 7.5 13
500V⋆  [kW] 0.75 1.5 1.5 2.2 3.7 5.5 5.5 7.5 7.5 10 15
690V⋆  [kW] 3 5.5 7.5 7.5 10 11 15 22
1000V⋆  [kW]
Max. switching frequency Ops/h 250 250 250 250 250 220 200 200 200 200 120
Wye-Delta (60 Hz)
  200V [Hp] 2.2 3 5 5 5 7ยฝ 7ยฝ 10 15 20 30
230V [Hp] 2.2 3 5 5 7ยฝ 10 10 15 20 25 40
460V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
575V [Hp] 5 7.5 10 10 15 20 25 30 40 50 75
UL/CSA Elevator Duty§ 
  200V [A] 7.8 11.0 11.0 17.5 25.3 25.3 32.2 32.2
230V [A] 6.8 9.6 15.2 15.2 22.0 28.0 28.0 42.0
460V [A] 7.6 11.0 14.0 21.0 27.0 27.0 34.0 40.0
575V [A] 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0
200V [Hp] 2 3 3 5 7ยฝ 7ยฝ 10 10
230V [Hp] 2 3 5 5 7ยฝ 10 10 15
460V [Hp] 5 7ยฝ 10 15 20 20 25 30
575V [Hp] 5 7ยฝ 10 15 20 25 30 40
Star-Delta Starting (50 Hz)
  £ 230V [A] 11.3 20 20 21 26 35 46 61 66 76 107
£ 240V [A] 11.3 20 20 21 26 35 46 61 66 76 107
400V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
415V [A] 8.5 15.5 15.5 16 21 28 40 52 64 74 104
500V [A] 6.8 12.4 12.4 12 17 24 35 43 52 66 95
690V [A] 4.9 8.9 8.9 8.6 12 16 21 31 36 43 59
1000V [A]
230V⋆  [kW] 3 5.5 5.5 5.5 7.5 10 13 17 20 22 32
240V⋆  [kW] 3 5.5 5.5 5.5 7.5 10 13 18.5 20 22 32
400V⋆  [kW] 4 7.5 10 7.5 10 13 20 25 32 40 55
415V⋆  [kW] 4 7.5 11 7.5 11 15 22 25 37 40 55
500V⋆  [kW] 4 7.5 7.5 7.5 11 15 22 25 32 45 63
690V⋆  [kW] 4 7.5 7.5 7.5 10 13 18.5 25 32 40 55
1000V⋆  [kW]
  
⋆ Power ratings at 50 Hz: Preferred values according to IEC 60072-1 § Approval pending on Cat. No. 100-D210…D860.

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 97 115 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X
Electronic — EI X X X X X X X X X
Switching of 3-phase Motors, (50 Hz)
Ambient temperature 60 °C, AC-4
  230V [A] 72 85 96 115 140 140 180 180 210 250 300 420
240V [A] 72 85 95 115 140 140 180 180 210 250 300 420
400V [A] 72 85 97 115 140 140 180 180 210 250 300 420
415V [A] 72 85 97 115 (130)‡  140 (155)‡  140 (155)‡  180 (189)§  180 (189)§  210 (227)‡  250 (258)‡  300 (315)‡  420
500V [A] 67 80 78 115 115 140 140 170 210 250 300 360
690V [A] 42 49 57 115 115 140 140 170 210 250 300 360
1000V [A] 46 55 55 65 65 80 95 115 160
230V [kW] 22 25 30 37 45 45 57 57 67 80 97 135
240V [kW] 22 25 30 39 47 47 60 60 70 83 101 141
400V [kW] 40 45 55 63 78 78 100 100 118 140 170 238
415V [kW] 40 45 55 66 (75)‡  82 (90)‡  82 (90)‡  105 (110)‡  105 (110)‡  125 (132)‡  145 (150)‡  176 (185)‡  250
500V [kW] 45 55 55 80 80 98 98 119 147 177 213 255
690V [kW] 40 45 55 110 110 135 135 167 205 250 293 356
1000V [kW] 63 75 75 90 90 110 132 160 225
AC-4 at approximately 200,000 operations
  230V [A] 31 38 44 53 60 60 67 67 85 105 140 170
240V [A] 31 38 44 53 60 60 67 67 85 105 140 170
400/415V [A] 31 38 44 53 60 60 67 67 85 105 140 170
500V [A] 31 38 44 53 60 60 67 67 85 105 140 170
690V [A] 31 38 44 53 60 60 67 67 85 105 140 170
1000V [A] 25 37 37 43 43 60 72 85 105
230V⋆  [kW] 7.5 11 11 15 17 17 20 20 25 32 45 55
240V⋆  [kW] 7.5 11 11 15 18.5 18.5 22 22 25 32 45 55
400V⋆  [kW] 15 20 22 25 32 32 37 37 45 55 75 90
415V⋆  [kW] 17 20 22 25 32 32 37 37 50 55 80 100
500V⋆  [kW] 20 25 30 32 40 40 45 45 55 75 100 110
690V⋆  [kW] 25 32 37 45 55 55 63 63 80 100 132 160
1000V⋆  [kW] 30 50 50 55 55 80 100 110 150
Max. switching frequency Ops/h 120 120 120 120 120 120 100 100 120 100 70 70
Wye-Delta (60 Hz)
  200V [Hp] 40 50 50 60 60 60 75 75 100 125 175 250
230V [Hp] 50 60 60 60 75 75 100 100 125 175 200 250
460V [Hp] 100 125 125 125 175 175 200 200 250 350 450 600
575V [Hp] 100 125 125 150 200 200 250 250 300 450 500 650
UL/CSA Elevator Duty‡ 
  200V [A] 48.3 62.1 TBD 78 92 92 120 120 150 150 177 221
230V [A] 54.0 68.0 TBD 80 104 104 130 130 130 154 192 248
460V [A] 52.0 65.0 TBD 77 96 96 124 124 156 180 180 240
575V [A] 52.0 62.0 TBD 77 77 77 99 99 125 144 192 242
200V [Hp] 15 20 TBD 25 30 30 40 40 50 50 60 75
230V [Hp] 20 25 TBD 30 40 40 50 50 50 60 75 100
460V [Hp] 40 50 TBD 60 75 75 100 100 125 150 150 200
575V [Hp] 50 60 TBD 75 75 75 100 100 125 150 200 250
Star-Delta Starting (50 Hz)
  £ 230V [A] 125 147 166 199 242 242 312 312 364 433 520 727
£ 240V [A] 125 147 165 199 242 242 312 312 364 433 520 727
400V [A] 125 147 168 199 242 242 312 312 364 433 520 727
415V [A] 125 147 168 199 (225)‡  242 (268)‡  242 (268)‡  312 (332)‡  312 (332)‡  364 (393)‡  433 (447)‡  520 (546)‡  727
500V [A] 116 139 135 199 199 242 312 312 364 433 520 727
690V [A] 73 85 99 199 199 242 312 312 364 433 520 727
1000V [A] 80 95 95 113 113 139 165 200 277
230V⋆  [kW] 37 45 50 63 75 75 90 90 110 132 160 220
240V⋆  [kW] 40 50 50 66 80 80 100 100 125 150 160 250
400V⋆  [kW] 63 80 90 110 132 132 160 160 200 250 300 425
415V⋆  [kW] 63 80 90 114 (132)‡  132 (160)‡  132 (160)‡  160 160 220 250 315 (335)‡  425
500V⋆  [kW] 80 90 90 132 132 160 200 200 250 315 375 530
690V⋆  [kW] 63 80 90 192 200 220 300 300 355 425 530 750
1000V⋆  [kW] 110 132 132 160 160 200 220 280 400
  
‡ 415V: Values in ( ) AC-3 and AC-4 lifespan -25%
§ Approval pending on Cat. No. 100-D210…D860.

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 43 60
Coil Type : Conventional X X X X X X X X X X X
Electronic — EI
Switching of Power Transformers,
AC-6a (50 Hz)
Inrush Current = n  
Rated transformer current  
    n = 30 £ 230V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 240V [A] 2.9 5.4 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 400V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 415V [A] 2.4 4.1 5.4 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 500V [A] 1.8 3.2 3.2 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 690V [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
£ 1000V [A]
230V [kVA] 1.2 2 2 4.3 4.3 4.3 4.3 8 8 9.2 16
240V [kVA] 1.2 2 2 4.5 4.5 4.5 4.5 8.3 8.3 10 17
400V [kVA] 1.7 2.8 3.4 7.5 7.5 7.5 7.5 14 14 16 28
415V [kVA] 1.7 2.8 3.4 7.8 7.8 7.8 7.8 14 14 17 29
500V [kVA] 1.7 2.8 3.4 9.4 9.4 9.4 9.4 17 17 20 35
690V [kVA] 2 4 5 13 13 13 13 24 24 27 49
1000V [kVA]
    n = 20 £ 690V [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
    n = 15 £ 690V [A] 22 22 22 22 40 40 46 82
60 Hz Peak Inrush/peak rated transformer current
  n = 30 [A] 10.9 10.9 10.9 10.9 20 20 23 40.8
200V [kVA] 3.8 3.8 3.8 3.8 6.9 6.9 8.0 14.1
208V [kVA] 3.9 3.9 3.9 3.9 7.2 7.2 8.3 14.7
240V [kVA] 4.5 4.5 4.5 4.5 8.3 8.3 9.6 17.0
480V [kVA] 9.1 9.1 9.1 9.1 16.6 16.6 19.1 33.9
600V [kVA] 11.3 11.3 11.3 11.3 20.8 20.8 23.9 42.4
660V [kVA] 12.5 12.5 12.5 12.5 22.9 22.9 26.3 46.6
60 Hz Peak Inrush/peak rated transformer current
  n = 20 [A] 16.3 16.3 16.3 16.3 30 30 34.5 61.3
200V [kVA] 5.6 5.6 5.6 5.6 10.4 10.4 12.0 21.2
208V [kVA] 5.9 5.9 5.9 5.9 10.8 10.8 12.4 22.1
240V [kVA] 6.8 6.8 6.8 6.8 12.5 12.5 14.3 25.5
480V [kVA] 13.6 13.6 13.6 13.6 24.9 24.9 28.7 51.0
600V [kVA] 16.9 16.9 16.9 16.9 31.2 31.2 35.9 63.7
660V [kVA] 18.6 18.6 18.6 18.6 34.3 34.3 39.4 70.1
60 Hz Peak Inrush/peak rated transformer current
  n=15 [A] 22 22 22 22 40 40 46 82
200V [kVA] 7.5 7.5 7.5 7.5 13.9 13.9 15.9 28.4
208V [kVA] 7.8 7.8 7.8 7.8 14.4 14.4 16.6 29.5
240V [kVA] 9.0 9.0 9.0 9.0 16.6 16.6 19.1 34.1
480V [kVA] 18.1 18.1 18.1 18.1 33.3 33.3 38.2 68.2
600V [kVA] 22.6 22.6 22.6 22.6 41.6 41.6 47.8 85.2
660V [kVA] 24.9 24.9 24.9 24.9 45.7 45.7 52.6 93.7
  

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 97 115 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X
Electronic — EI X X X X X X X X X
Switching of Power Transformers,
AC-6a (50 Hz)
Inrush Current
Rated transformer current
    n = 30 £ 230V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
£ 240V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
£ 400V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
£ 415V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
£ 500V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
£ 690V [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
£ 1000V [A] 46 70 70 85 85 105 125 150 210
230V [kVA] 16 16 19.3 24 28 28 34 34 42 50 60 84
240V [kVA] 17 17 20.2 26 29 29 35 35 44 52 62 87
400V [kVA] 28 28 33.6 42 48 48 59 59 73 87 104 145
415V [kVA] 29 29 34.9 43 50 50 61 61 75 90 108 151
500V [kVA] 35 35 42 52 61 61 74 74 91 108 130 182
690V [kVA] 49 49 58 72 84 84 102 102 125 149 179 251
1000V [kVA] 80 121 121 147 147 182 217 260 364
    n = 20 £ 690V [A] 61.3 61.3 72.8 90 105 105 128 128 158 188 225 315
    n = 15 £ 690V [A] 82 82 97 120 140 140 170 170 210 250 300 420
60 Hz Peak Inrush/peak rated transformer current
  n = 30 [A] 40.8 40.8 48.5 60 70 70 85 85 105 125 150 210
200V [kVA] 14.4 14.4 16.8 20.8 24.2 24.2 29.4 29.4 36.4 43.3 52.0 72.7
208V [kVA] 14.7 14.7 17.5 21.6 25.2 25.2 30.6 30.6 37.8 45.0 54.0 75.7
240V [kVA] 17.0 17.0 20.2 24.9 29.1 29.1 35.3 35.3 43.6 52.0 62.4 87.3
480V [kVA] 33.9 33.9 40.3 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
600V [kVA] 42.4 42.4 50.4 62.4 72.7 72.7 88.3 88.3 109 130 156 218
660V [kVA] 46.6 46.6 55.4 68.6 80.0 80.0 97.2 97.2 120 143 171 240
60 Hz Peak Inrush/peak rated transformer current
  n = 20 [A] 61.3 61.3 72.8 90 105 105 128 128 158 188 225 315
200V [kVA] 21.2 21.2 25.2 31.2 36.4 36.4 44.3 44.3 54.7 65.1 77.9 109
208V [kVA] 22.1 22.1 26.2 32.4 37.8 37.8 46.1 46.1 56.9 67.7 81.1 113
240V [kVA] 25.5 25.5 30.3 37.4 43.6 43.6 53.2 53.2 65.7 78.2 93.5 131
480V [kVA] 51.0 51.0 60.5 74.8 87.3 87.3 106 106 131 156 187 262
600V [kVA] 63.7 63.7 75.7 93.5 109 109 133 133 164 195 234 327
660V [kVA] 70.1 70.1 83.2 103 120 120 146 146 131 215 257 360
60 Hz Peak Inrush/peak rated transformer current
  n=15 [A] 82 82 97 120 140 140 170 170 210 250 300 420
200V [kVA] 28.4 28.4 33.6 41.6 48.5 48.5 58.9 58.9 72.7 86.6 104 145
208V [kVA] 29.5 29.5 34.9 43.2 50.4 50.4 61.2 61.2 75.7 90.1 108 151
240V [kVA] 34.1 34.1 40.3 49.9 58.2 58.2 70.7 70.7 87.3 104 125 175
480V [kVA] 68.2 68.2 80.6 99.8 116 116 141 141 175 208 249 349
600V [kVA] 85.2 85.2 100.8 125 145 145 177 177 218 260 312 436
660V [kVA] 93.7 93.7 110.9 137 160 160 194 194 240 286 343 480
  

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X
Electronic — EI
Switching of 3-phase Capacitors, AC-6b (50 Hz)⋆ 
Single capacitor 40 °C 230V [kVar] 8 8 8.5 9 14 14 24 28
240V [kVar] 8 8 8.5 9 14 14 25 29
400V [kVar] 8 8 10 12.5 20 24 35 48
415V [kVar] 8 8 10 12.5 20 25 35 50
500V [kVar] 8 8 10 12.5 20 25 35 50
690V [kVar] 8 8 10 12.5 20 25 35 50
1000V [kVar]
    60 °C 230V [kVar] 8 8 8.5 9 12.5 12.5 18 28
240V [kVar] 8 8 8.5 9 12.5 12.5 18 29
400V [kVar] 8 8 10 12.5 20 21.5 30 42
415V [kVar] 8 8 10 12.5 20 22 30 42
500V [kVar] 8 8 10 12.5 20 25 30 42
690V [kVar] 8 8 10 12.5 20 25 30 42
1000V [kVar]
Group capacitors 40 °C 230V [kVar] 5 5 8 9 12.5 14 20 28
240V [kVar] 5 5 8 9 12.5 14 20 29
400V [kVar] 5 5 8 10 15 20 25 40
415V [kVar] 5 5 8 10 15 20 25 40
500V [kVar] 5 5 8 10 15 20 25 40
690V [kVar] 5 5 8 10 15 20 25 40
1000V [kVar]
    60 °C 230V [kVar] 5 5 8 9 12.5 12.5 18 28
240V [kVar] 5 5 8 9 12.5 12.5 18 29
400V [kVar] 5 5 8 10 15 20 25 40
415V [kVar] 5 5 8 10 15 20 25 40
500V [kVar] 5 5 8 10 15 20 25 40
690V [kVar] 5 5 8 10 15 20 25 40
1000V [kVar]
60 Hz Single Capacitor — 40 °C
  200V [kVar] 5 5 8 9 12.5 14 20 28
230V [kVar] 5 5 8 9 12.5 14 20 29
460V [kVar] 5 5 8 10 15 20 25 40
600V [kVar] 5 5 8 10 15 20 25 40
60 Hz Group Capacitors — 40 °C
  200V [kVar] 5 5 8 9 12.5 12.5 18 28
230V [kVar] 5 5 8 9 12.5 12.5 18 29
460V [kVar] 5 5 8 10 15 20 25 40
600V [kVar] 5 5 8 10 15 20 25 40
Switching of Lamps
Gas discharge lamps AC-5a, 40 °C open [A] 18 18 18 22.5 25 28 29 40.5 45 65 65 77 81
  enclosed [A] 14.5 14.5 14.5 22.5 25 28 29 37 41 54 54 57 77
Individually compensated:
Max. capacitance at expected
Short-circuit current of 10 kA [mF] 750 750 750 1 000 1 000 1 000 1 000 2 700 2 700 3 200 4 000
20 kA [mF] 400 400 400 500 500 500 500 1 350 1 350 1 600 2 000
50 kA [mF] 200 200 200 200 540 540 640 800
Filament AC-5b 230/240V [A] 5 9 9 12 16 18 22 30 37 18 25 43 60
Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
AC-7a 230V [A] 20 20 20 32 32 32 32 45 45 63
400V [A] 20 20 20 32 32 32 32 45 45 63
440V [A] 32 32 32 32 45 45 63
Switching of Motor Load for Home Appliances (50 Hz)
AC-7b 230V [A] 6 11 11 10.5 14 19 23 30
400V [A] 6 11 11 9 12 16 20 30
440V [A] 7.5 10 13.5 18 27
  
⋆ Inductance of leads between capacitors in parallel: min. 6 mH (100-C09…C30 contactors: min 30 mH)

  100/104-C, 100S/104S-C 100/104-D, 100S-D
72 85 90*200 90*400 97 115 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X
Switching of 3-phase Capacitors, AC-6b (50 Hz)
Single capacitor 40°C 230V [kVar] 28 28 28 45 70 70 70 70 98 98 125 139
240V [kVar] 29 29 29 47 73 73 73 73 102 102 131 145
400V [kVar] 48 48 48 78 121 121 121 121 170 170 218 242
415V [kVar] 50 50 50 81 126 126 126 126 176 176 226 252
500V [kVar] 55 60 60 97 152 152 152 152 212 212 273 303
690V [kVar] 55 60 60 134 209 209 209 209 293 293 376 418
1000V [kVar] 194 303 303 303 303 424 424 546 606
    60 °C 230V [kVar] 28 28 28 38 59 59 59 59 84 84 106 119
240V [kVar] 29 29 29 39 61 61 61 61 87 87 111 124
400V [kVar] 48 48 48 65 102 102 102 102 145 145 184 206
415V [kVar] 50 50 50 68 106 106 106 106 151 151 191 214
500V [kVar] 50 55 55 82 127 127 127 127 182 182 230 258
690V [kVar] 50 55 55 113 176 176 176 176 251 251 318 356
1000V [kVar] 164 255 255 255 255 364 364 461 515
Group capacitors 40°C 230V [kVar] 28 28 28 45 70 70 70 70 98 98 125 139
240V [kVar] 29 29 29 47 73 73 73 73 102 102 131 145
400V [kVar] 48 48 48 56 76 76 111 111 170 170 218 242
415V [kVar] 50 50 50 56 76 76 112 112 170 176 226 252
500V [kVar] 50 50 50 56 76 76 113 113 172 212 273 303
690V [kVar] 50 50 50 57 78 78 114 114 174 247 356 418
1000V [kVar] 58 79 79 116 116 177 251 361 606
    60°C 230V [kVar] 28 28 28 38 59 59 59 59 84 84 106 119
240V [kVar] 29 29 29 39 61 61 61 61 87 87 111 124
400V [kVar] 48 48 48 56 76 76 102 102 145 145 184 206
415V [kVar] 50 50 50 56 76 76 106 106 151 151 191 214
500V [kVar] 50 50 50 56 76 76 113 113 172 182 230 258
690V [kVar] 50 50 50 57 78 78 114 114 174 247 318 356
1000V [kVar] 58 79 79 116 116 177 251 361 515
60 Hz Single Capacitor — 40 °C
  200V [kVar] 28 28 28 39 61 61 61 61 85 85 109 121
230V [kVar] 29 29 29 45 70 70 70 70 98 98 125 139
460V [kVar] 50 50 50 89 139 139 139 139 195 195 251 279
600V [kVar] 50 50 50 116 182 182 182 182 255 255 327 364
60 Hz Group Capacitors — 40 °C
  200V [kVar] 28 28 28 39 61 61 61 61 85 85 109 121
230V [kVar] 29 29 29 45 70 70 70 70 98 98 125 139
460V [kVar] 50 50 50 56 76 76 112 112 171 195 251 279
600V [kVar] 50 50 50 57 77 77 114 114 173 246 327 364
Switching of Lamps
Gas discharge lamps AC-5a, 40 °C open [A] 85 90 115 115 115 144 225 225 225 225 315 315 405 450
enclosed [A] 81 90 95 95 100 122 189 189 189 189 270 270 342 383
Individually compensated:
Max. capacitance at expected
Short-circuit current of 10 kA [mF] 4 000 4 700 4 700
20 kA [mF] 2 000 2 350 2 350
50 kA [mF] 800 940 940
Filament AC-5b 230/240V [A] 70 76 60 75 90 120 140 140 170 170 210 250 300 420
Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz)
AC-7a 230V [A]
400V [A]
440V [A]
Switching of Motor Load for Home Appliances (50 Hz)
AC-7b 230V [A]
400V [A]
440V [A]
  

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60
Coil Type : Conventional X X X X X X X X X X X X X
Electronic — EI
Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)
AC-8a 400V [A] 11 18 18 12 16 22 32 38 45 63 72
500V [A] 10 15 15 12 16 22 32 38 45 63 72
690V [A] 8 10 14 20 28 35 42 56
- automatic reset of overload release
AC-8b 400V [A] 5.5 7 9.3 12 13 14 16 24
500V [A] 5.5 7 9.3 12 13 14 16 24
690V [A] 5.5 7 9.3 12 13 14 16 24
Switching of DC Loads
Non-inductive or slightly inductive loads or resistance furnaces DC-1, 60 °C
    1 pole 24V [A] 6 9 9 25 25 32 32 45 45 45 45 50 70
48/60V [A] 4/1 6/1.5 6/1.5 20 20 20 20 25 25 25 25 30 40
110V [A] 0.6 1 1 6 6 6 6 8 8 10 10 9 11
220V [A] 0.2 0.3 0.3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2
440V [A] 0.08 0.1 0.1 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.5
    2 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 45 45 50 70
48/60V [A] 6 8 8 25 25 32 32 45 45 45 45 50 70
110V [A] 4 6 6 25 25 32 32 45 45 45 45 50 70
220V [A] 0.8 1.2 1.2 8 8 8 10 10 10 10 10 10 15
440V [A] 0.2 0.3 0.3 1 1 1 1 1 1 1 1 1 1.5
    3 poles in series 24V [A] 6 9 9 25 25 32 32 45 45 45 63 90
48/60V [A] 6 9 9 25 25 32 32 45 45 45 63 90
110V [A] 6 9 9 25 25 32 32 45 45 45 63 90
220V [A] 3 4 4 25 25 32 32 45 45 45 50 70
440V [A] 0.4 0.6 0.6 3 3 3 3 3.5 3.5 3.5 4 5
Shunt-wound Motors
Starting, reverse current braking, reversing, stepping DC-3, 60 °C
    3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 90
48/60V [A] 4 6 6 25 25 32 32 45 45 50 70
110V [A] 2 3 3 20 20 25 25 30 30 35 70
220V [A] 0.8 1.2 1.2 6 6 6 10 15 15 20 25
440V [A] 0.15 0.2 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Series-wound Motors
Starting, reverse current braking, reversing, stepping DC-5, 60 °C
    3 poles in series 24V [A] 5 9 9 25 25 32 32 45 45 63 90
48/60V [A] 2 3 3 25 25 32 32 45 45 50 70
110V [A] 0.6 1 1 20 20 25 25 30 30 35 70
220V [A] 0.1 0.1 0.1 6 6 6 10 15 15 20 25
440V [A] 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Short Time Withstand ICW, 60 °C
  10 s [A] 60 96 96 170 170 170 215 300 304 304 304 375 700
Resistance and Power Dissipation
Main current circuit resistance [mW] 2.2 2.2 2.2 2.7 2.7 2.7 2 2 2 2 1.5 1.5 0.9
Power dissipation by all circuits at Ie AC-3/400V [W] 0.3 0.9 0.9 0.66 1.2 2.1 3.2 5.4 8.2 11.3 8.4 8.3 9.7
Total power dissipation
At Ie AC-3/400V AC [W] 2.1 2.7 2.7 3.3 3.8 4.7 6.2 8.4 11.2 26.1 37.4 11.5 11
DC [W] 2.9 3.5 3.5 6.7 7.2 8.1 12.4 14.6 17.4 32.6 43.9 18.4 11
Lifespan
Mechanical AC control [Mil. operations] 15 15 15 13 13 13 13 13 13 10 10 12 6
Mechanical DC control [Mil. operations] 15 15 15 13 13 13 13 13 13 10 10 13 6
Electrical AC-3 (400 V) [Mil. operations] 0.7 0.7 0.7 1.3 1.3 1.3 1.3 1.3 1.3 1 1
Weight
AC Non-Rev. kg (lbs.) 0.16 (0.35) 0.16 (0.35) 0.16 (0.35) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.48 (1.06) 0.49 (1.08) 0.63 (1.39) 0.63 (1.39) 0.51 (1.12) 1.45 (3.20)
Rev. kg (lbs.) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 1.08 (2.39) 1.08 (2.39) 1.15 (2.54) 3.14 (6.92)
DC Non-Rev. kg (lbs.) 0.2 (0.44) 0.2 (0.44) 0.2 (0.44) 0.6 (1.32) 0.6 (1.32) 0.6 (1.32) 0.73 (1.61) 0.85 (1.87) 0.85 (1.87) 1.12 (2.46) 1.12 (2.46) 1.0 (2.20) 1.47 (3.24)
Rev. kg (lbs.) 1.27 (2.81) 1.27 (2.81) 1.27 (2.81) 1.53 (3.39) 1.81 (4.0) 1.81 (4.0) 2.13 (4.7) 3.22 (7.1)
  

  100/104-C, 100S/104S-C 100/104-D, 100S-D
  72 85 90*200 90*400 97 115 140 140 180 180 210 250 300 420 630 860
Coil Type : Conventional X X X X X X X X
Electronic — EI X X X X X X X X X
Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz)
AC-8a 400V [A] 85 100 115 192 210 210
500V [A] 85 100 115 192 192 210
690V [A] 67 80 90 192 192 210
- automatic reset of overload release
AC-8b 400V [A] 30 35 35
500V [A] 30 35 35
690V [A] 30 35 35
Switching of DC Loads
Non-inductive or slightly inductive loads or resistance furnaces DC-1, 60 °C
    1 pole 24V [A] 80 80 80 80 80 135 210 210 210 210 300 300 380 425
48/60V [A] 40 40 40 40 40 135 210 210 210 210 300 300 380 425
110V [A] 11 11 11 11 11 135 210 210 210 210 300 300 380 425
220V [A] 2 2 1.8 1.8 2 3 3.3 3.3 3.3 3.3 4.9 4.9 4.9 5.2
440V [A] 0.5 0.5 0.5 0.5 0.5 0.6 0.75 0.75 0.75 0.75 1 1 1 1.2
    2 poles in series 24V [A] 80 80 80 80 80 135 210 210 210 210 300 300 380 425
48/60V [A] 80 80 80 80 80 135 210 210 210 210 300 300 380 425
110V [A] 80 80 80 80 80 135 210 210 210 210 300 300 380 425
220V [A] 15 15 15 15 15 135 210 210 210 210 300 300 380 425
440V [A] 1.5 1.5 1.5 1.5 1.5 3 3.3 3.3 3.3 3.3 4.9 4.9 4.9 5.2
    3 poles in series 24V [A] 90 100 100 100 135 210 210 210 210 300 300 380 425
48/60V [A] 90 100 100 100 135 210 210 210 210 300 300 380 425
110V [A] 90 100 100 100 135 210 210 210 210 300 300 380 425
220V [A] 80 80 80 80 135 210 210 210 210 300 300 380 425
440V [A] 5 5 5 5 11 11 11 11 11 14 14 14 15
Shunt-wound Motors
Starting, reverse current braking, reversing, stepping DC-3, 60 °C
    3 poles in series 24V [A] 90 100 100 135 210 210 210 210 300 300 380 425
48/60V [A] 70 80 80 135 210 210 210 210 300 300 380 425
110V [A] 70 80 80 135 210 210 210 210 300 300 380 425
220V [A] 25 30 30 135 210 210 210 210 300 300 380 425
440V [A] 0.6 0.6 0.6 3 3.5 3.5 3.5 3.5 4.1 4.1 4.1 5.8
Series-wound Motors
Starting, reverse current braking, reversing, stepping DC-5, 60 °C
    3 poles in series 24V [A] 90 100 100 135 210 210 210 210 300 300 380 425
48/60V [A] 70 80 80 135 210 210 210 210 300 300 380 425
110V [A] 70 80 80 135 210 210 210 210 300 300 380 425
220V [A] 25 30 30 135 210 210 210 210 300 300 380 425
440V [A] 0.6 0.6 0.6 1.2 2.1 2.1 2.1 2.1 2.4 2.4 2.4 3
Short Time Withstand ICW, 60 °C
  10 s [A] 700 700 700 700 840 1040 1240 1360 1480 1480 2360 2520 2840 4700 6300 7000
Resistance and Power Dissipation
Main current circuit resistance 230V [mW] 0.9 0.9 0.8 0.7 0.6 0.4 0.42 0.42 0.42 0.42 0.22 0.22 0.18 0.15 0.19 0.14
Power dissipation by all circuits at
Ie AC-3/400V
460V [W] 14 19.5 13.5 11.8 17 14.5 24.6 24.6 40.8 40.8 29.4 41.7 48.6 79.5 78.4 103.2
Total power dissipation
At Ie AC-3/400V AC control [W] 13.8 17.5 36 56.3 26 24.5 (20.5) 34.6 30.6 50.8 46.8 35.4 47.7 54.6 86.5 105.4 133.2
DC control [W] 13.8 17.5 32.5 52.8 23 22.5 (20.5) 32.6 30.6 48.8 46.8 35.4 47.7 54.6 86.5 105.4 133.2
Lifespan
Mechanical AC control 600V [Mil. operations] 6 6 6 6 6 10 10 10 10 10 10 10 10 10 2 2
DC control 600V [Mil. operations] 6 6 6 6 6 10 10 10 10 10 10 10 10 10 2 2
Electrical AC-3 (400 V) 600V [Mil. operations] 1 1 1 1 1 1 1 1 1 1 1 1
Weight
AC Non-Reversing kg (lbs.) 1.45 (3.2) 1.45 (3.2) 1.45 (3.2) 3.3 (7.28)
[3.8 (8.38)]⋆ 
3.3 (7.28) 3.8 (8.38) 3.3 (7.28) 3.8 (8.38) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 28.6 (63) 28.6 (63)
Reversing kg (lbs.) 3.14 (6.92) 3.14 (6.92) 3.14 (6.92)
DC Non-Reversing kg (lbs.) 1.47 (3.24) 1.47 (3.24) 1.47 (3.24) 3.3 (7.28)
[3.8 (8.38)]⋆ 
3.3 (7.28) 3.8 (8.38) 3.3 (7.28) 3.8 (8.38) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 7.5 (16.53) 28.6 (63) 28.6 (63)
Reversing kg (lbs.) 3.22 (7.1) 3.22 (7.1) 3.22 (7.1)
  
⋆ Values in brackets refer to electronic coil (EI) version.

  100-KR 100/104-K 100/104-C, 100S/104S-C
  05 09 05 09 12 09 12 16 23 30 37 40 43 60 72 85 97
Coil Type : Conventional X X X X X X X X X X X X X X X X X
Electr. — EI
Conductor Cross Sections - Main Contacts
Terminal type
Click to enlarge - 100-K_Push-In Click to enlarge - 140M-29-1 ⋆  Click to enlarge - 140M-29-1 ⋆  Click to enlarge - 140M-29-2 ‡  Click to enlarge - 140M-29-2 § 
Click to enlarge - 140M-29-4   (1) conductor [mm2] 0.50…2.5 0.75…2.5 1…4 2.5…10 2.5…16 2.5…35 2.5…35
(2) conductors [mm2] 0.50…2.5 0.75…2.5 1…4 2.5…10 2.5…10 2.5…25 2.5…35
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 (1) conductor [mm2] 0.75…2.5♣  1…4 1.5…6 2.5…16 2.5…25 2.5…50 2.5…50
(2) conductors [mm2] 0.75…2.5♣  1…2.5+ 1…4 1.5…6 2.5…16 2.5…16 2.5…35 2.5…50
Click to enlarge - Contactors_2-30-9 b max. [mm]
c max. [mm]
s max. [mm]
Æ min. [mm]
Recommended torque [N•m]   1.2 1.5…2.0 2.5…3.5 2.5…3.5 4.5…6
Cross section per UL/CSA [AWG]   18…14♣  18…12 16…10 14…4 14…6 14…4 14…1
Recommended torque [lb-in]   10.6 13.3…17.7 22…31 22…31 40…53
With terminal lug kit
Cross section per UL/CSA [AWG]  
Recommended torque [lb-in]  
With Frame Terminal Block
Click to enlarge - 140M-29-4   top opening [mm2]
bottom opening [mm2]
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 top opening [mm2]
bott. opening [mm2]
Click to enlarge - Contractors2_30-13 b max.
s top
s bottom
[mm2]
Recommended torque [N•m]  
Cross section per UL/CSA top [AWG]  
bottom [AWG]  
Recommended torque [lb-in]  
  
⋆ Pozidriv No. 2 / Blade No. 3 screw
‡ Pozidriv No. 2 / Blade No. 4 screw
§ Hexagonal socket screw
♣ Fine- or coarse-stranded only

  100/104-D, 100S-D
115 140 180 210 250 300 420 630 860
Coil Type : Conventional X X X
Electronic — EI X X X X X X X X X
Conductor Cross Sections - Main Contacts
Terminal type
Click to enlarge - Contractors2_31-1 Click to enlarge - Contractors2_31-1 Click to enlarge - Contractors2_31-1
Click to enlarge - 140M-29-4   (1) conductor [mm2]
(2) conductors [mm2]
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 (1) conductor [mm2]
(2) conductors [mm2]
Click to enlarge - Contactors_2-30-9 b max. [mm] 25 30 52 52
c max. [mm] 12.5 15 22 22
s max. [mm] 5 6 2 x 8 2 x 8
Æ min. [mm] 8.3 10.5 13 13
Recommended torque [Nm] 22 43 68 68
Cross section per UL/CSA [AWG]
Recommended torque [lb-in] 195 380 600 600
With terminal lug kit 100-DL180§  100-DL420§  100-DL630 100-DL860
Cross section per UL/CSA [AWG] 6…300 MCM (2x) 4…350 MCM (2X) 2/0…500MCM (4X) 2/0…500MCM
Recommended torque [lb-in] 88…106 375 400 400
With Frame Terminal Block     100-DTB180§  100-DTB420⋆ 
Click to enlarge - 140M-29-4   top opening [mm2] 16…35 25…185∆ 
  bottom opening [mm2] 16…95 25…185
Click to enlarge - 140M-29-5 Click to enlarge - 140M-29-6 top opening [mm2] 16…50 25…240
Click to enlarge - 140M-29-6 bottom opening [mm2] 16…120 25…240
Click to enlarge - Contractors2_30-13 b max.
s top
s bottom
[mm]
[mm]
[mm]
20
3…9
3…14
25
6…20
6…20
Recommended torque [Nm] 14 25
Cross section per UL/CSA top [AWG] 6…1 / 0 AWG 4 AWG…600 MCM
bottom [AWG] 6 AWG…250 MCM 4 AWG…600 MCM
Recommended torque [lb-in] 124 220
     
  ⋆ Pozidriv No. 2 / Blade No. 3 screw
‡ Pozidriv No. 2 / Blade No. 4 screw
§ Hexagonal socket screw
♣ Hexagonal screw

Short-Circuit Coordination Data§ 

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60 72 85 90*200 90*400 97
Coil Type : Conventional X X X X X X X X X X X X X X X X X X
Electronic – El
Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating)
Per IEC 60947-4-1 (contactor and fuses only)
    DIN Fuses - gG, gL 50 kA Available Fault Current
    Type "1" (690V) [A] 35 35 35 50 50 50 80 125 125 160 160 160 250 250 250 250 250 250
    Type "2" (400V) [A] 16 20 20 25 35 35 40 80 80 63 80 100 160 160 160 160 100 200
    Type "2" (690V) [A] 25 35 35 40 80 80 63 80 100 160 160 160 160 100 200
    BS88 Fuses 65 kA Available Fault Current
    Type "1" (415V) [A] 25 32 40 50 63 80 80 100 160 160 TBD
    Type "2" (415V) [A] 20 25 32 50 63 80 80 100 125 160 TBD
Per UL 508 and CSA 22.2 No. 14
(contactor and fuses or circuit breaker only)
    UL Class K5 and RK5 Fuses 5 kA Available Fault Current
    UL Listed Combination (600V) [A] 40 40 40 35 40 70 90 110 125 125 125 150 200
    UL Class K5 and RK5 Fuses 10 kA Available Fault Current
    UL Listed Combination (600V) [A] 250 300 300 300 350
    UL Class L Fuses 18 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Class L Fuses 30 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Class L Fuses 42 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Class CC and CSA HRCI-MISC Fuses 50 kA Available Fault Current
    UL Listed Combination (600V) [A] 30 30 30
    UL Class J and CSA HRCI-J Fuses 50 kA Available Fault Current
    UL Listed Combination (600V) [A] 30 30 30
    UL Class CC and CSA HRCI-MISC Fuses 100 kA Available Fault Current
     UL verified combination to IEC 60947-4-1 "Type 2" [A] 20♣  20 30 40
    UL Class J and CSA HRCI-J Fuses 100 kA Available Fault Current
     UL verified combination to IEC 60947-4-1 "Type 2" [A] 20♣  20 30 40 50 50 70 80 100 150 TBD
    UL Inverse-Time Circuit Breaker 5 kA Available Fault Current
    UL Listed Combination (480V) [A] 30 30 50 50 125 125 125 250
    UL Listed Combination (600V) [A] 125 125 125 250
    UL Inverse-Time Circuit Breaker 10 kA Available Fault Current
    UL Listed Combination (600V) [A] 250 250 250
    UL Inverse-Time Circuit Breaker 18 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Inverse-Time Circuit Breaker 30 kA Available Fault Current
    UL Listed Combination (600V) [A] 50 50 50 110 110 110 TBD
    UL Inverse-Time Circuit Breaker 42 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Inverse-Time Circuit Breaker 50 kA Available Fault Current
    UL Listed Combination (480V) [A] 50 50 50
    UL Inverse-Time Circuit Breaker 65 kA Available Fault Current
    UL Listed Combination (480V) [A] 110 110 110 TBD
  
♣ 15 A max. fuse for Type 2 coordination.
§ See www.ab.com/certifications/ul508a for complete short-circuit current ratings.

  100/104-D, 100S-D
115 140/180 140 180 210 250 300 420 630 860
Coil Type : Conventional X X
Electronic – El X X X X X X X X X
Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating)  
Per IEC 60947-4-1 (contactor and fuses only)  
    DIN Fuses - gG, gL [kVar] 50 kA Available Fault Current
    Type "1" (690V) [A] 250 315 315 355 500 500 630 630 ‡  ‡ 
    Type "2" (400V) [A] 200 250 250 315 400 400 500 500 ‡  ‡ 
    Type "2" (690V) [A] 200 250 250 315 400 400 500 500 ‡  ‡ 
    BS88 Fuses 65 kA Available Fault Current
    Type "1" (415V) [A] 200 250 250 250 355 355 450 630 ‡  ‡ 
    Type "2" (415V) [A] 200 250 250 250 355 355 450 560 ‡  ‡ 
Per UL 508 and CSA 22.2 No. 14
(contactor and fuses or circuit breaker only)
  
    UL Class K5 and RK5 Fuses 5 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Class K5 and RK5 Fuses 10 kA Available Fault Current
    UL Listed Combination (600V) [A] 250 350/450 350 450 500
    UL Class L Fuses 18 kA Available Fault Current
    UL Listed Combination (600V) [A] 700 700 1000
    UL Class L Fuses 30 kA Available Fault Current
    UL Listed Combination (600V) [A] 2000
    UL Class L Fuses 42 kA Available Fault Current
    UL Listed Combination (600V) [A] 2500
    UL Class CC and CSA HRCI-MISC Fuses 50 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Class J and CSA HRCI-J Fuses 50 kA Available Fault Current
    UL Listed Combination (600V) [A]
    UL Class CC and CSA HRCI-MISC Fuses 100 kA Available Fault Current
     UL verified combination to IEC 60947-4-1 "Type 2" [A]
    UL Class J and CSA HRCI-J Fuses 100 kA Available Fault Current
     UL verified combination to IEC 60947-4-1 "Type 2" [A] 200 250/300 250 300 400 400 500 600 ‡  ‡ 
    UL Inverse-Time Circuit Breaker 5 kA Available Fault Current
    UL Listed Combination (480V) [A]
    UL Listed Combination (600V) [A]
    UL Inverse-Time Circuit Breaker 10 kA Available Fault Current
    UL Listed Combination (600V) [A] 150 200/250 200 250 300
    UL Inverse-Time Circuit Breaker 18 kA Available Fault Current
    UL Listed Combination (600V) [A] 400 400 600
    UL Inverse-Time Circuit Breaker 30 kA Available Fault Current
    UL Listed Combination (600V) [A] 125 200 200 200 250 400 400 600 1200
    UL Inverse-Time Circuit Breaker 42 kA Available Fault Current
    UL Listed Combination (600V) [A] 1200
    UL Inverse-Time Circuit Breaker 50 kA Available Fault Current
    UL Listed Combination (480V) [A]
    UL Inverse-Time Circuit Breaker 65 kA Available Fault Current
    UL Listed Combination (480V) [A] 125 200 200 200 250 400 400 600 ‡  ‡ 
     
  ‡ To be determined.

Coil Data

  100/104-K 100/104-C, 100S/104S-C
  05 09 12 09 12 16 23 30 37 40*200 40*400 43 60 72 85 90*200 90*400 97
Coil Type Conventional X X X X X X X X X X X X X X X X X X
Electronic — EI
Operating Limits
50 Hz, 60 Hz, 50/60 Hz pick-up [x Us] 0.85…1.1 0.85…1.1 0.85….1.1 0.85….1.1
dropout [x Us] 0.2…0.75 0.3…0.6 0.3…0.6 0.3…0.6
DC (conventional) pick-up [x Us] 0.8…1.1
0.7…1.25♣ 
0.8…1.1 0.8…1.1 0.8…1.1
dropout [x Us] 0.1…0.75 0.1…0.6 0.1…0.6 0.1…0.6
DC (electronic) pick-up [x Us] 0.7…1.25
dropout [x Us] 0.4
Coil Consumption
50 Hz, 60 Hz, 50/60 Hz pick-up [VA/W] 35/32 70/50 70/50 80/60 130/90 130/90 200/110 400/240
hold-in [VA/W] 5/1.8 8/2.6 9/3 9/3 12/3.6 10/3.2 16/4.5 24/9
DC (conventional) pick-up [W] cold 3.0, warm 2.6 6.5 9.2 9.2 10.1 10.1 200 325
hold-in [W] cold 3.0, warm 2.6 6.5 9.2 9.2 10.1 10.1 4.5 5.5
DC (electronic) pick-up (avg/peak) [W] 10/17 10/17 16/25
hold-in [W] 1.7 1.7 2.5
Operating Times
AC closing delay [ms] 15…40 15…30 15…30 15…30 15…30 15…30 20…40 20…40
opening delay [ms] 15…33 10…60 10…60 10…60 10…60 10…60 10…60 20…40
With RC module opening delay [ms] 15…28 10…60 10…60 10…60 10…60 10…60 10…60 20…40
DC (conventional) closing delay [ms] 18…40 40…70 40…70 50…80 50…80 50…80 20…40 15…25 20…25 20…25
opening delay [ms] 6…12 7…15 7…15 7…15 7…15 7…15
With integ. diode opening delay [ms] 8…12 14…20 17…23 17…23 17…23 £ 220V 20…35 £ 220V 20…35
With external diode opening delay [ms] 35…50 70…95 80…125 80…125 80…125
DC (electronic) closing delay [ms] 25…50
opening delay [ms] 25…50
Max. Ripple ± 15%
Min. OFF time [ms] 200
  
♣ For 9, 12, 24, and 110V DC coils

  100/104-D, 100S-D
115 140/180 115 140 180 210 250 300 420 630 860
Coil Type Conventional X X
Electronic — EI X X X X X X X X X
Operating Limits
50 Hz, 60 Hz, 50/60 Hz pick-up [x Us] 0.85…1.1 0.85…1.1 0.8…1.1
dropout [x Us] 0.3…0.6 0.3…0.5 0.1…0.8
DC control pick-up [x Us] 0.85…1.1 0.85…1.1 0.85…1.1
dropout [x Us] 0.3…0.6 0.3…0.5 0.1…0.8
Coil Consumption
50 Hz, 60 Hz, 50/60 Hz pick-up [VA/W] 650/310 380/240⋆  490/270⋆  1915/1720
hold-in [VA/W] 50/10 13/6 18/7 33/30
DC control pick-up [W] 540 265⋆  340⋆  1980⋆ 
hold-in [W] 8 6 7 30
Operating Times
AC closing delay [ms] 20…47 20…45 60…100
opening delay [ms] 6…12 25…110 70…145
With RC module opening delay [ms] 9…18
DC closing delay [ms] 27…47 25…50 60…100
opening delay [ms] 12…20 35…110 70…145
Integrated diode opening delay [ms] 12…20
External diode opening delay [ms]
  
⋆ Electronic coil drives are designed to minimize power requirements, but this control may exhibit a higher inrush (540 W, < 10 ms) when energizing. This must be taken into account for the proper sizing of supply devices, all-or-nothing relays and cross-sections of coil supply lines. Please contact your local Rockwell Automation sales office or Allen‑Bradley distributor for detailed information.

Auxiliary Contacts, Auxiliary Contact Blocks, and Pneumatic Timers

  100-K 100-C, 100S-C 100-D, 100S-D
Internal Front-mounted Internal Front-mounted Front-mounted (Bifurcated) Side-mounted Side-mounted
Convent'l Bifurcated Electronically
compatible
Switching of AC Loads X
AC-12 Ith at 40 °C [A] 10 10 20 10 10 10 16 10 0.1
at 60 °C [A] 6 6 20 6 6 6 12 6 at 250V
AC-15 at rated voltage of  
  24V [A] 6 3 10 6 3 6 5.5 3 (1…100 mA)
at
3…125V
42/48V [A] 6 3 10 6 3 6 5.5 3
120V [A] 6 3 10 6 3 6 5.5 3
230V [A] 3 2 10 5.5 3 5.5 5.5 3
240V [A] 3 2 10 5 3 5 5 3
400V [A] 1.8 1.2 6 3 2 3 3 2
415V [A] 1.8 1.2 6 3 2 3 2.5 2
500V [A] 1.4 1.0 2.5 1.6 1.2 1.6 1.6 1.2
690V [A] 1.0 0.6 1 1 0.7 1 1 0.7
Switching of DC Loads
DC-12 L/R< 1 ms resistive loads at  
  24V DC [A] 6 12 12 6 6 16 16
48V DC [A] 4 9 9 3.2 3.2 9 9
110V DC [A] 0.6 3.5 3.5 0.45 0.45 3.5 3.5
220V DC [A] 0.2 0.55 0.55 0.18 0.18 0.55 0.55
440V DC [A] 0.08 0.2 0.2 0.1 0.1 0.2 0.2
DC-14 L/R< 15 ms inductive loads
with economy resistor in series at
 
  24V DC [A] 4 9 9 2 2 9 9
48V DC [A] 2.5 5 5 1.6 1.6 5 5
110V DC [A] 0.4 2 2 0.3 0.3 2 2
220V DC [A] 0.12 0.4 0.4 0.12 0.12 0.4 0.4
440V DC [A] 0.05 0.16 0.16 0.05 0.05 0.16 0.1
DC-13 switching electromagnets at  
  24V DC [A] 2.8 2.3 5 5 2.5 5 5 5 (1…100 mA)
at
3…125V
  48V DC [A] 1.2 1 3 3 1.5 2.5 2 2
  110V DC [A] 0.55 0.55 1.2 1.2 0.6 0.68 0.7 0.7
  220V DC [A] 0.27 0.27 0.6 0.6 0.3 0.32 0.25 0.25
  440V DC [A] 0.15 0.15 0.3 0.15 0.15 0.15 0.12 0.12
Fuse gG
Short-circuit protection with no welding of contacts per IEC 60947-5-1
  Click to enlarge - 100_104-M_110-1 [A] 10 10 20 10 10 10 16 16
  Click to enlarge - 100_104-M_110-2 [A] 10 10 20 10 10 10 16 16
Protective Separation per IEC 60947-1, Annex N between load
and auxiliary
circuit 320V
between load and auxiliary
circuit 440V
between load and auxiliary
circuit 440V
Min. switching capacity according to IEC 60947-5-4 15V/
10 mA
15V/
2 mA
17V/10 mA 17V/5 mA 5V/3 mA 17V/10 mA 17V/10 mA 5V/2 mA
(1 Mio. ops.)
3V/1 mA
Failure rate   <10-8
(less than 1 failure to 100 Mio. operations)
Load Carrying Capacity per UL/CSA
Rated voltage AC [V] max. 600 max. 600 max. 600 max. 250
Continuous rating 40 °C [A] 10 10 10 10 10 10 General
purpose
0.1
Switching capacity AC [A] A 600 B 600 A 600 Heavy pilot duty
(A 600)
0.1
Rated voltage DC [V] max. 600 max. 600 max. 600 max. 250
Switching capacity DC [A] Q 600 P 600 Q 600 Q 600 Standard pilot duty
(P 600)
Standard pilot duty
(Q 600)
0.1
  

General

  100-K 100-C, 100S-C 100-D, 100S-D
  05…12 09…97 115…420
Rated Isolation Voltage Ui      
IEC [V] 690 690 1000
UL, CSA [V] 600 600 600
Rated Impulse Voltage Withstand Uimp [kV] 6 6 12
Rated Voltage Ue  
AC 50/60 Hz [V] 230, 240, 400, 415, 460, 500, 575, 690 115, 200, 230, 240, 400, 415, 460, 500, 575, 690 230, 240, 400, 415, 500, 690, 1000
DC [V] 24, 48, 110, 220, 440 24, 48, 110, 220, 440 24, 48, 110, 220, 440
Insulation Class of the Coil Class F per IEC 60085
Class 105 insulation system per UL 508
Class F per IEC 60085 Class B per VDE 0660,
Table 22
Rated coil frequency AC 50/60 Hz, DC AC 50/60 Hz, DC AC 50 Hz, 50/60 Hz, DC
Ambient Temperature  
Storage [°C] -55…+80 -55…+80 -40…+80
Operation at rated voltage [°C] -25…+60 -25…+60 -25…+60
at 70 °C 15% current reduction against 60°C values
Climatic Withstand IEC 60068-2-30 IEC 60068-2-1 / -2 / -30 IEC 60068-2-30
Max. Altitude of Installation Site [m] 2000 NN, per IEC 60947-4 2000 NN, per IEC 60947-1 2000 NN, per IEC 60947-4
Protection Class IP2X IP2X IP00 IEC 60529 / DIN 40 050
Single contactor cover IP10 IEC 60529 / DIN 40 050
Contactor with frame terminal block IP20 IEC 60529 / DIN 40 050
Auxiliary contact IP2X IP2X IP20 IEC 60529 / DIN 40 050
Protection against Accidental Contact Finger and back-of-hand proof
per VDE 0106, part 100
Finger and back-of-hand proof
per VDE 0106, part 100
Resistance to Shock IEC 60068-2 IEC 60068-2-27 IEC 60068-2-27
Resistance to Vibration IEC 60068-2 IEC 60068-2-6 IEC 60068-2-6
Mechanically Linked Contacts
IEC 60947-5-1, Annex L
100-K… (on main device) 100- / 100S-C09…C43 + 100-FA/-FB/-FC, (except L11, L22), 100- / 100S-C09…C43 + 100-FAB/-FBB/-FCB
Mirror Contacts
IEC 60947-4 Annex F
100-K… + 100-KF… 100- / 100S-C09…C97 + 100-FA/-FB/-FC, (except L11, L22), 100- / 100S-C09…C97 + 100-SA/SB, 100- / 100S-C09…C97 + 100-FAB/-FBB/-FCB 100-D… + 2 x 100-DS1-11
100S-D… + 2 x 100S-DS1-11
Standards Compliance IEC/EN 60947-1/-4-1/-5-1; UL 508;
CSA 22.2. No. 14
IEC/EN 60947-1/-4-1/-5-1; UL 508;
CSA 22.2. No. 14
IEC/EN 60947-1/-4-1/-5-1; UL 508;
CSA 22.2. No. 14
Certifications CE, cULus
CCC
CE, cULus, CCC CE, cULus, CCC
  

Bul. 100-K/104-K Life-Load Curves

Electrical life; Ue = 400…460V AC

AC-3

Switching of squirrel-cage motors while starting

AC-1

Non- or slightly inductive loads, resistance furnaces

Click to enlarge - 100-K_001


Electrical life; Ue = 400…460V AC

AC-4

Stepping of squirrel-cage motors

Click to enlarge - 100-K_002

Bulletin 100-C/104-C Life-Load Curves

Electrical Life in Utilization Category

Bulletin 100-C/104-C IEC contactors are designed for superior performance in a wide variety of applications. When selecting IEC products, the user must give consideration to the specific load, utilization category and required electrical life of the application. The life-load curves shown here are based on Rockwell Automation tests according to the requirements defined in IEC 60947-4-1. Since contact life in application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here.

To find the contactor’s estimated electrical life, follow these guidelines:

1. Identify the appropriate utilization category from the table below.

2. Choose the graph for the utilization category selected.

3. Locate the intersection of the life-load curve for the appropriate contactor with the application’s operational current (Ie) found on the horizontal axis.

4. Read the estimated contact life along the vertical axis.


Contact Life for Mixed Utilization Categories AC-3 and AC-4:

In many applications, the utilization category cannot be defined as either purely AC-3 or AC-4. In those applications, the electrical life of the contactor can be estimated from the following equation:

Lmixed = Lac3/[1 + Pac4*(Lac3/Lac4 – 1)], where:

Lmixed = Approximate contact life in operations for a mixed AC-3/AC-4 utilization category application

Lac3 = Approximate contact life in operations for a pure AC-3 utilization category (from the AC-3 life-load curves)

Lac4 = Approximate contact life in operations for a pure AC-4 utilization category (from the AC-4 life-load curves)

Pac4 = Percentage of AC-4 operations


Test Conditions Making Breaking
I/Ie U/Ue cosf Ic/Ie Ur/Ue cosf
AC-1 Resistance Furnaces:
Non inductive or slightly inductive loads
1 1 0.95 1 1 0.95
AC-2 Slip-ring motors:
Starting and reversing
2.5 1 0.65 2.5 1 0.65
AC-3 Squirrel-cage motors:
Starting and stopping of running motors
Ie < 17 A
Ie > 17 A
6
6
1
1
0.65
0.35
1
1
0.17
0.17
0.65
0.35
AC-4 Squirrel-cage motors:
Starting, plugging⋆ , inching‡ 
Ie < 17 A
Ie > 17 A
6
6
1
1
0.65
0.35
6
6
1
1
0.65
0.35
AC-15 Soleniods:
Contactors, valves and lifting magnets
10 1 0.7 1 1 0.4
  
Ie  Rated operational current  I    Making Current
Ue  Rated voltage      Ic    Breaking Current
Ur  Recovery voltage      U    Off-load voltage
⋆ Plugging is understood as stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running.
‡ Inching (jogging) is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism.

Life-Load Curves

AC-1

40 °C Non- or slightly inductive loads, resistance furnaces; Ue = 230…690V

Click to enlarge - Elek_ld_Ausg4 1


AC-2

Switching of slip-ring motors; Ue = 230…400…460V

Click to enlarge - Elek_ld_Ausg4 2


AC-3

Switching of squirrel-cage motors while starting; Ue = 230…400…460V

Click to enlarge - Elek_ld_Ausg4 3


Switching of squirrel-cage motors while starting; Ue = 500…575V

Click to enlarge - Elek_ld_Ausg4 4


AC-3

Switching of squirrel-cage motors while starting; Ue = 690V

Click to enlarge - Elek_ld_Ausg4 5


AC-4

Switching of squirrel-cage motors; Ue = 230…690V

Click to enlarge - Elek_ld_Ausg4 6


AC-3 & AC-4

10% AC-4 Mixed operation of squirrel-cage motors; Ue = 230…400…460V

Click to enlarge - Elek_ld_Ausg4 8


Heavy Duty Starting and Regular Short-time Operation

Bulletin 100-C Contactors

Click to enlarge - ANLAUFZT_Ausg2


Maximum Operating Rates

AC-1

40 °C Non- or slilghtly inductive loads, resistance furnaces; Ue = 230…690V

Click to enlarge - SCH_HAEU_Ausg4-1 1


AC-2

Stepping of slip-ring motors; Ue = 230…460V

Click to enlarge - SCH_HAEU_Ausg4-1 2


Maximum Operating Rates

AC-3

Switching of squirrel-cage motors while starting; Ue = 230…460V

Relative operating time 40%, Starting time tA = 0.25 s

Click to enlarge - SCH_HAEU_Ausg4-1 3


AC-4

Inching of squirrel-cage motors; Ue = 230…460V

Starting time tA = 0.25 s

Click to enlarge - SCH_HAEU_Ausg4-1 4

Bulletin 100-D/104-D/100S-D/104S-D Life-Load Curves

AC-3, AC-1

Click to enlarge - 100-D_AC-1_3_4c


AC-4

Click to enlarge - 100-D_AC-4_4c


Life-Load Curves

AC-3 90% & AC-4 10%

Click to enlarge - 100-D_AC-3-4_4c

Bulletin 100-L Specifications

Ratings

Type of Load Max (A) Max AC Volts Poles to Load‡ 
1 for 1Æ 3 for 3Æ
Tungsten 20 277 480/277
15 347 600/347
Ballast 20 277 480/277
15 347 600/347
General Use
Resistance Heating
30 600 600
  
‡ 20A, 250V DC max. with 3 poles in series.

Click to enlarge - 100L-76-3


Click to enlarge - 100L-76-4


Click to enlarge - 100L-76-5

Bulletin 100-G Specifications

Electrical Data

Cat. No. 100-G550... 100-G700... 100-G860... 100-G1000 100-G1200
AC-1, Three-phase Switching - IEC
Ambient temperature: 40 °C
         
        Ie £ 690V [A] 760 1000 1100 1200 1350
230V [kW] 303 398 438 478 538
240V [kW] 316 416 457 499 561
400V [kW] 527 693 762 831 935
415V [kW] 546 719 791 863 970
500V [kW] 658 866 953 1039 1169
690V [kW] 908 1195 1315 1434 1613
Ambient temperature: 60 °C          
        Ie £ 690V [A] 605 800 870 960 1,085
230V [kW] 241 319 347 382 432
240V [kW] 251 333 362 399 451
400V [kW] 419 554 603 665 752
415V [kW] 435 575 625 690 780
500V [kW] 524 693 753 831 940
690V [kW] 723 956 1040 1147 1297
Continuous Current - UL/CSA
General Purpose Rating 40 °C
[A] 520 700 810 1215
Switching of 3-phase Motors - IEC          
AC-2, AC-3   230/240V [A] 550 700 860 1000 1200
50 Hz/60 °C 400/415V [A] 550 700 860 1000 1200
500V [A] 550 700 860 1000 1200
690V [A] 500 630 700 860 1000
230V [kW] 179 228 280 326 391
240V [kW] 187 238 293 340 408
400V [kW] 312 414 509 592 710
415V [kW] 324 430 528 628 737
500V [kW] 407 518 636 756 888
690V [kW] 510 657 730 897 1043
AC-4 at 200000 operations          
50 Hz   230/240V [A] 140 180 210 260 300
400/415V [A] 140 180 210 260 300
230V [kW] 45 57 67 83 97
240V [kW] 47 60 70 87 101
400V [kW] 78 101 118 146 170
415V [kW] 81 105 122 151 176
AC-4, Squirrel-cage motors with reversing and
jogging at 20,000 (25,000), operations
         
    230/240V [A] 360 430 520 (630) (700)
400/415V⋆  [A] 350 420 520 (630) (700)
230V [kW] 116 139 170 (205) (228)
240V [kW] 120 151 177 (214) (245)
400V [kW] 198 238 295 (357) (414)
415V [kW] 206 247 300 (359) (424)
  
⋆ At rated Voltage 415V and rated current: Life span - 25%.

Cat. No. 100-G550 100-G700 100-G860 100-G1000... 100-G1200...
Switching of 3-phase Motors - UL/CSA          
60 Hz/60 °C 200V [A] 414 552 692 1185
230V [A] 360 602 722 1130
460V [A] 414 590 708 1062
575V [A] 336 472 576 864
200V [Hp] 150 200 250 450
230V [Hp] 150 250 300 450
460V [Hp] 350 500 600 900
575V [Hp] 350 500 600 900
Rated making capacity          
AC-3 Ie £ 415V [A] 5500 7000 8600 10000 12000
500V [A] 5500 7000 8600 10000 12000
690V [A] 5500 7000 8600 10000 12000
Rated Breaking capacity          
AC-3 Ie £ 240V [A] 4400 5600 6900 8000 9600
400V [A] 4400 5600 6900 8000 9600
415V [A] 4400 5600 6900 8000 9600
500V [A] 4400 5600 6900 8000 9600
690V [A] 4000 5100 5600 6900 8000
Star-Delta Starting          
50 Hz 230V [A] 953 1212 1490 1732 2078
240V [A] 953 1212 1490 1732 2078
400V [A] 953 1212 1490 1732 2078
415V [A] 953 1212 1490 1732 2078
500V [A] 953 1212 1490 1732 2078
690V [A] 831 1091 1195 1490 1732
230V [kW] 310 395 485 565 677
240V [kW] 324 412 507 589 707
400V [kW] 540 717 882 1025 1250
415V [kW] 561 745 915 1088 1278
500V [kW] 705 897 1102 1309 1538
690V [kW] 883 1138 1247 1554 2078
Wye-Delta Starting          
60 Hz 230V [Hp] 250 400 500 650 750
460V [Hp] 600 800 1000 1300 1500
575V [Hp] 600 800 1000 1500 1500
Short-circuit Protection of Contactors without
Overload Relay
         
Fuse gG (aM) Type 1 coordination
(per IEC 60947-4-1)
  500V [A] (630) 800 1000 1000 1250
690V [A] (630) 800 1000 1000 1000
Switching of Three-phase Capacitor
Inductivity of dispatching between parallel switched capacitor: min. 6 pH
Single capacitors 40 °C   230V [kVar] 180 220 250 290 330
240V [kVar] 200 250 300 325 360
400V [kVar] 320 400 450 500 575
415V [kVar] 350 430 500 550 630
500V [kVar] 450 520 600 660 750
690V [kVar] 580 700 800 875 1000
55 °C 230V [kVar] 150 180 220 275 325
240V [kVar] 170 200 260 300 350
400V [kVar] 280 330 400 460 550
415V [kVar] 300 360 450 500 600
500V [kVar] 360 420 540 600 720
690V [kVar] 500 580 720 800 950
  

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Capacitor Banks




40 °C




230V [kVar] 180 220 250 290 330
240V [kVar] 200 250 300 325 360
400V [kVar] 320 400 450 500 575
415V [kVar] 350 430 500 550 430
500V [kVar] 450 520 600 660 750
690V [kVar] 580 700 800 875 1000
55 °C




230V [kVar] 150 180 220 275 325
240V [kVar] 170 200 260 300 350
400V [kVar] 280 330 400 460 550
415V [kVar] 300 360 450 500 600
500V [kVar] 360 420 540 600 720
690V [kVar] 500 580 720 800 950
DC Switching
Switching of non- or slightly inductive loads, resistance furnaces
DC-1 at 60 °C
         
    1 Pole 24/48V [A] 645 760 930 1020 1150
    2 Poles in series 24/48V [A] 645 760 930 1020 1150
    3 Poles in series

24/48V [A] 645 760 930 1020 1150
110V [A] 480 560 630 800 900
220V [A] 315 400 450 500 600
Shunt-Wound Motors
Starting, plugging, reversing, plugging
DC-3 at 60 °C
         
    3 Poles in series 24/48V [A] 605 800 870 960 1085
Series-Wound Motors
Starting, plugging, reversing, plugging
DC-5 at 60 °C
         
    3 Poles in series 24/48V [A] 605 800 870 960 1085
Lighting Loads
Elec. Discharge. Lamps - AC - 5a,
         
    Non-Compensated [A] 450 570 700 850 1000
    Compensated [A] 360 460 550 660 800
Incandescent Lamps - AC - 5b,
Electrical Endurance @ 100 000 ops

[A]

315

440

500

560

630
Switching Power Transformers AC - 6a          
Inrush = n ยท Ie [A] 7440 9450 11700 13500 16200
Ie Rated transformer current [A] 248 315 390 450 540
  n = 30 400V AC [kVA] 172 218 270 312 374
500V AC [kVA] 215 273 338 390 468
690V AC [kVA] 269 339 376 538 645
n = 20   [A] 371 472 580 675 810
n = 15 [A] 435 630 774 900 1080
Rated Short-Time Withstand ICW, 60 °C          
    1 s [A] 5500 7000 8000 10000 12000
4 s [A] 5500 7000 8000 10000 12000
10 s [A] 4400 5600 6900 8000 9600
15 s [A] 3800 5000 6000 7400 8500
60 s [A] 2300 2800 3400 4000 4800
240 s [A] 1300 1800 2000 2300 2700
900 s [A] 850 1150 1350 1600 1900
Minimum cooling time at zero current [Min.] 60 60 60 60 60
Resistance and Energy Dissipation          
Main circuit resistance [mW] 0.11 0.1 0.08 0.06 0.05
Total energy dissipation at Ie AC-3 [W] 99 147 177 180 216
Excess energy dissipation at Ie AC-3          
  AC Control [W] 110 172 202 250 286
DC Control [W] 109 169 199 240 276
  

Mechanical Data

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Life Span in Millions of Operations          
Mechanical
AC Control [Mil.] 5 5 5 1 1
DC Control [Mil.] 5 5 5 1 1
Shipping Weights AC Control [kg] 13.8 26.4 28.4 50.3 53.4
  [lb] 30.4 58.1 62.5 110.8 117.6
DC Control [kg] 13.8 26.4 28.4 50.3 53.4
  [lb] 30.4 58.1 62.5 110.8 117.6
Terminals⋆           
Terminal Dimensions [mm] 6 x 40 8 x 50 8 x 50 10 x 50 10 x 60
Terminal screw hole size [mm] (1) x Æ 13 (1) x Æ 13 (1) x Æ 15 (2) x Æ 13 (2) x Æ 13
Terminations - Power
Type
Hexagonal Bolt
Direct Connection        
Click to enlarge - Contactors_2-30-9 b max. [mm] 50 60 60 60 60
c max. [mm] 20 20 25 25 25
s max. [mm] 2 x 5 2 x 5 2 x 6 2 x 6 2 x 8
Æ min. [mm] 12.5 13 15 2 x 13 2 x 13
Recommended Torque [N•m] 50 60 75 60 60
[ft.-lb] 37 44 55 44 44
Conductor/Wire Terminations⋆           
Bus bar (Width) [mm] 40 50 50 50 60
Hex screw [in] 1/2 3/8 3/8 3/8 3/8
Recommended Torque [N•m] 42 62 62 56 56
[lb•in] 375 550 550 500 500
Auxiliary Contact [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
Coils [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
  
⋆ Quantity indicated in ( ).

Coil Data

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Operating Limits  
AC- 50 Hz Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
AC- 60 Hz Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
DC Control Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
Pickup and Holding Power      
AC- 50 Hz Pick-up [VA] 800…950 1350…1600 2400
Hold-in [VA] 9…11 21…25 70
AC- 60 Hz Pick-up [VA] 800…950 1350…1600 2400
Hold-in [VA] 9…11 21…25 70
DC Control Pick-up [W] 700…850 1300…1550 2100
Hold-in [W] 8…10 18…22 60
Operating Times: Switching Delay    
AC Making delay [ms] 50…100 50…100
Breaking delay [ms] 20…50‡ /150…200/500…1000§  25…50
DC Making delay [ms] 50…100 50…100
Breaking delay [ms] 20…50‡ /150…200/500…1000§  25…50
  
‡ Accelerates
§ Delays

Auxiliary Contacts

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
AC Switching    
AC-1 Ith at 40 °C [A] 16 16
at 60 °C [A] 12 12
AC- 15 at rated voltage 120V [A] 6 6
230V [A] 3 3
240V [A] 3 3
400V [A] 2 2
415V [A] 2 2
500V [A] 1.5 1.5
690V [A] 1 1
DC Switching
DC-13 control of electromagnets
24V DC [A] 6 6
48V DC [A] 3 3
110V DC [A] 1 1
220V DC [A] 0.5 0.5
Back-up Fuse
Short-circuit protection without contact welding
per IEC 60947-5
   
Fuse gG [A] 10 16
  

General Data

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000…⋆  100-G1200…
Rated Isolation Voltage Ui    
IEC, AS, BS, SEV, VDE, 0660
UL/CSA
[V]
1,000V
600V
690V
600V
Impulse Voltage Uimp    
1 minute per IEC 947-4 [KV] 8 kV 2,5 kV
Rated Voltage - Main Control Ue    
AC 50/60 Hz [V] 230, 240, 400, 415, 460, 500, 575, 690V 230, 240, 400, 415, 460, 500, 575, 690V
DC [V] 24, 48, 110, 220, 440V
Operating Frequency for AC Loads
50/60 Hz
[Hz] 180/hr. for 0.25s start time - 42/hr. for 1s start time
Insulation Class of the Magnetic Coil Class B per VDE 0660, table 22
Rated frequency of the Coil AC 50/60 Hz, DC
Ambient Temperature  
Storage -40 °C…+80 °C
Operation at rated current -25 °C…+70 °C
Climatic Withstand Damp alternating conditions cyclical, per DIN 50 016 and 40 046, part 38, IEC 60068
Altitude 2000 m above sea level, per IEC 60947-1
Type of Protection IP00 IEC 60529/DIN 40 050
Standards Compliance IEC 60947, UL 508, CSA C22.2, No. 14
Certifications cULus, CE
  
⋆ Cat. No. 100-G1000… is not cULus certified.

Life-Load Curves

100-G550…100-G1200

AC-3 Switching of Running Three-phase Motors, Ue = 380…460V AC
AC-1 Non or Slightly Inductive Loads, Resistance Furnaces


Click to enlarge - 100G-119-1


AC-4 Jogging of Squirrel-cage Motors, Ue = 380…460V AC

Click to enlarge - 100G-119-2


100-G550…100-G1200

AC-3 90% Switching of Running Motors, Ue = 380…460V AC
AC-4 10% Jogging


Click to enlarge - 100G-120-1


Permissable Switching Rate

100-G550…100-G1200

Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 0.25 s, Relative Running Time 40%


Click to enlarge - 100G-120-2


100-G550…100-G1200

Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 1 s, Relative Running Time 40%


Click to enlarge - 100G-121-1


100-G550…100-G1200

Switching of Starting Motors (AC-2, and AC4) Uz = 380…460V AC
Starting Time ted = 1 s, (<ts)


Click to enlarge - 100G-121-2