Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Contactor Accessories, Modifications, Specifications, and Approximate Dimensions > Specifications
Specifications
Electrical Data
| Cat. No. | 100-G550... | 100-G700... | 100-G860... | 100-G1000 | 100-G1200 | |||
| AC-1, Three-phase Switching - IEC Ambient temperature: 40 °C |
||||||||
| Ie | £ | 690V | [A] | 760 | 1000 | 1100 | 1200 | 1350 |
| 230V | [kW] | 303 | 398 | 438 | 478 | 538 | ||
| 240V | [kW] | 316 | 416 | 457 | 499 | 561 | ||
| 400V | [kW] | 527 | 693 | 762 | 831 | 935 | ||
| 415V | [kW] | 546 | 719 | 791 | 863 | 970 | ||
| 500V | [kW] | 658 | 866 | 953 | 1039 | 1169 | ||
| 690V | [kW] | 908 | 1195 | 1315 | 1434 | 1613 | ||
| Ambient temperature: 60 °C | ||||||||
| Ie | £ | 690V | [A] | 605 | 800 | 870 | 960 | 1,085 |
| 230V | [kW] | 241 | 319 | 347 | 382 | 432 | ||
| 240V | [kW] | 251 | 333 | 362 | 399 | 451 | ||
| 400V | [kW] | 419 | 554 | 603 | 665 | 752 | ||
| 415V | [kW] | 435 | 575 | 625 | 690 | 780 | ||
| 500V | [kW] | 524 | 693 | 753 | 831 | 940 | ||
| 690V | [kW] | 723 | 956 | 1040 | 1147 | 1297 | ||
| Continuous Current - UL/CSA General Purpose Rating 40 °C |
[A] | 520 | 700 | 810 | — | 1215 | ||
| Switching of 3-phase Motors - IEC | ||||||||
| AC-2, AC-3 | 230/240V | [A] | 550 | 700 | 860 | 1000 | 1200 | |
| 50 Hz/60 °C | 400/415V | [A] | 550 | 700 | 860 | 1000 | 1200 | |
| 500V | [A] | 550 | 700 | 860 | 1000 | 1200 | ||
| 690V | [A] | 500 | 630 | 700 | 860 | 1000 | ||
| 230V | [kW] | 179 | 228 | 280 | 326 | 391 | ||
| 240V | [kW] | 187 | 238 | 293 | 340 | 408 | ||
| 400V | [kW] | 312 | 414 | 509 | 592 | 710 | ||
| 415V | [kW] | 324 | 430 | 528 | 628 | 737 | ||
| 500V | [kW] | 407 | 518 | 636 | 756 | 888 | ||
| 690V | [kW] | 510 | 657 | 730 | 897 | 1043 | ||
| AC-4 at 200000 operations | ||||||||
| 50 Hz | 230/240V | [A] | 140 | 180 | 210 | 260 | 300 | |
| 400/415V | [A] | 140 | 180 | 210 | 260 | 300 | ||
| 230V | [kW] | 45 | 57 | 67 | 83 | 97 | ||
| 240V | [kW] | 47 | 60 | 70 | 87 | 101 | ||
| 400V | [kW] | 78 | 101 | 118 | 146 | 170 | ||
| 415V | [kW] | 81 | 105 | 122 | 151 | 176 | ||
| AC-4, Squirrel-cage motors with reversing and jogging at 20,000 (25,000), operations |
||||||||
| 230/240V | [A] | 360 | 430 | 520 | (630) | (700) | ||
| 400/415V⋆ | [A] | 350 | 420 | 520 | (630) | (700) | ||
| 230V | [kW] | 116 | 139 | 170 | (205) | (228) | ||
| 240V | [kW] | 120 | 151 | 177 | (214) | (245) | ||
| 400V | [kW] | 198 | 238 | 295 | (357) | (414) | ||
| 415V | [kW] | 206 | 247 | 300 | (359) | (424) | ||
| ⋆ At rated Voltage 415V and rated current: Life span - 25%. | ||||||||
| Cat. No. | 100-G550 | 100-G700 | 100-G860 | 100-G1000... | 100-G1200... | ||||
| Switching of 3-phase Motors - UL/CSA | |||||||||
| 60 Hz/60 °C | 200V | [A] | 414 | 552 | 692 | — | 1185 | ||
| 230V | [A] | 360 | 602 | 722 | — | 1130 | |||
| 460V | [A] | 414 | 590 | 708 | — | 1062 | |||
| 575V | [A] | 336 | 472 | 576 | — | 864 | |||
| 200V | [Hp] | 150 | 200 | 250 | — | 450 | |||
| 230V | [Hp] | 150 | 250 | 300 | — | 450 | |||
| 460V | [Hp] | 350 | 500 | 600 | — | 900 | |||
| 575V | [Hp] | 350 | 500 | 600 | — | 900 | |||
| Rated making capacity | |||||||||
| AC-3 Ie | £ | 415V | [A] | 5500 | 7000 | 8600 | 10000 | 12000 | |
| 500V | [A] | 5500 | 7000 | 8600 | 10000 | 12000 | |||
| 690V | [A] | 5500 | 7000 | 8600 | 10000 | 12000 | |||
| Rated Breaking capacity | |||||||||
| AC-3 Ie | £ | 240V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |
| 400V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |||
| 415V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |||
| 500V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |||
| 690V | [A] | 4000 | 5100 | 5600 | 6900 | 8000 | |||
| Star-Delta Starting | |||||||||
| 50 Hz | 230V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | ||
| 240V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 400V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 415V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 500V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 690V | [A] | 831 | 1091 | 1195 | 1490 | 1732 | |||
| 230V | [kW] | 310 | 395 | 485 | 565 | 677 | |||
| 240V | [kW] | 324 | 412 | 507 | 589 | 707 | |||
| 400V | [kW] | 540 | 717 | 882 | 1025 | 1250 | |||
| 415V | [kW] | 561 | 745 | 915 | 1088 | 1278 | |||
| 500V | [kW] | 705 | 897 | 1102 | 1309 | 1538 | |||
| 690V | [kW] | 883 | 1138 | 1247 | 1554 | 2078 | |||
| Wye-Delta Starting | |||||||||
| 60 Hz | 230V | [Hp] | 250 | 400 | 500 | 650 | 750 | ||
| 460V | [Hp] | 600 | 800 | 1000 | 1300 | 1500 | |||
| 575V | [Hp] | 600 | 800 | 1000 | 1500 | 1500 | |||
| Short-circuit Protection of Contactors without Overload Relay |
|||||||||
| Fuse gG (aM) Type 1 coordination (per IEC 60947-4-1) |
500V | [A] | (630) | 800 | 1000 | 1000 | 1250 | ||
| 690V | [A] | (630) | 800 | 1000 | 1000 | 1000 | |||
| Switching of Three-phase Capacitor Inductivity of dispatching between parallel switched capacitor: min. 6 pH |
|||||||||
| Single capacitors | 40 °C | 230V | [kVar] | 180 | 220 | 250 | 290 | 330 | |
| 240V | [kVar] | 200 | 250 | 300 | 325 | 360 | |||
| 400V | [kVar] | 320 | 400 | 450 | 500 | 575 | |||
| 415V | [kVar] | 350 | 430 | 500 | 550 | 630 | |||
| 500V | [kVar] | 450 | 520 | 600 | 660 | 750 | |||
| 690V | [kVar] | 580 | 700 | 800 | 875 | 1000 | |||
| 55 °C | 230V | [kVar] | 150 | 180 | 220 | 275 | 325 | ||
| 240V | [kVar] | 170 | 200 | 260 | 300 | 350 | |||
| 400V | [kVar] | 280 | 330 | 400 | 460 | 550 | |||
| 415V | [kVar] | 300 | 360 | 450 | 500 | 600 | |||
| 500V | [kVar] | 360 | 420 | 540 | 600 | 720 | |||
| 690V | [kVar] | 500 | 580 | 720 | 800 | 950 | |||
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000… | 100-G1200… | |||
| Capacitor Banks |
40 °C |
230V | [kVar] | 180 | 220 | 250 | 290 | 330 |
| 240V | [kVar] | 200 | 250 | 300 | 325 | 360 | ||
| 400V | [kVar] | 320 | 400 | 450 | 500 | 575 | ||
| 415V | [kVar] | 350 | 430 | 500 | 550 | 430 | ||
| 500V | [kVar] | 450 | 520 | 600 | 660 | 750 | ||
| 690V | [kVar] | 580 | 700 | 800 | 875 | 1000 | ||
| 55 °C |
230V | [kVar] | 150 | 180 | 220 | 275 | 325 | |
| 240V | [kVar] | 170 | 200 | 260 | 300 | 350 | ||
| 400V | [kVar] | 280 | 330 | 400 | 460 | 550 | ||
| 415V | [kVar] | 300 | 360 | 450 | 500 | 600 | ||
| 500V | [kVar] | 360 | 420 | 540 | 600 | 720 | ||
| 690V | [kVar] | 500 | 580 | 720 | 800 | 950 | ||
| DC Switching Switching of non- or slightly inductive loads, resistance furnaces DC-1 at 60 °C |
||||||||
| 1 Pole | 24/48V | [A] | 645 | 760 | 930 | 1020 | 1150 | |
| 2 Poles in series | 24/48V | [A] | 645 | 760 | 930 | 1020 | 1150 | |
| 3 Poles in series |
24/48V | [A] | 645 | 760 | 930 | 1020 | 1150 | |
| 110V | [A] | 480 | 560 | 630 | 800 | 900 | ||
| 220V | [A] | 315 | 400 | 450 | 500 | 600 | ||
| Shunt-Wound Motors Starting, plugging, reversing, plugging DC-3 at 60 °C |
||||||||
| 3 Poles in series | 24/48V | [A] | 605 | 800 | 870 | 960 | 1085 | |
| Series-Wound Motors Starting, plugging, reversing, plugging DC-5 at 60 °C |
||||||||
| 3 Poles in series | 24/48V | [A] | 605 | 800 | 870 | 960 | 1085 | |
| Lighting Loads Elec. Discharge. Lamps - AC - 5a, |
||||||||
| Non-Compensated | [A] | 450 | 570 | 700 | 850 | 1000 | ||
| Compensated | [A] | 360 | 460 | 550 | 660 | 800 | ||
| Incandescent Lamps - AC - 5b, Electrical Endurance @ 100 000 ops |
[A] |
315 |
440 |
500 |
560 |
630 |
||
| Switching Power Transformers AC - 6a | ||||||||
| Inrush = n ยท Ie | [A] | 7440 | 9450 | 11700 | 13500 | 16200 | ||
| Ie Rated transformer current | [A] | 248 | 315 | 390 | 450 | 540 | ||
| n = 30 | 400V AC | [kVA] | 172 | 218 | 270 | 312 | 374 | |
| 500V AC | [kVA] | 215 | 273 | 338 | 390 | 468 | ||
| 690V AC | [kVA] | 269 | 339 | 376 | 538 | 645 | ||
| n = 20 | [A] | 371 | 472 | 580 | 675 | 810 | ||
| n = 15 | [A] | 435 | 630 | 774 | 900 | 1080 | ||
| Rated Short-Time Withstand ICW, 60 °C | ||||||||
| 1 s | [A] | 5500 | 7000 | 8000 | 10000 | 12000 | ||
| 4 s | [A] | 5500 | 7000 | 8000 | 10000 | 12000 | ||
| 10 s | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | ||
| 15 s | [A] | 3800 | 5000 | 6000 | 7400 | 8500 | ||
| 60 s | [A] | 2300 | 2800 | 3400 | 4000 | 4800 | ||
| 240 s | [A] | 1300 | 1800 | 2000 | 2300 | 2700 | ||
| 900 s | [A] | 850 | 1150 | 1350 | 1600 | 1900 | ||
| Minimum cooling time at zero current | [Min.] | 60 | 60 | 60 | 60 | 60 | ||
| Resistance and Energy Dissipation | ||||||||
| Main circuit resistance | [mW] | 0.11 | 0.1 | 0.08 | 0.06 | 0.05 | ||
| Total energy dissipation at Ie AC-3 | [W] | 99 | 147 | 177 | 180 | 216 | ||
| Excess energy dissipation at Ie AC-3 | ||||||||
| AC Control | [W] | 110 | 172 | 202 | 250 | 286 | ||
| DC Control | [W] | 109 | 169 | 199 | 240 | 276 | ||
Mechanical Data
Coil Data
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000… | 100-G1200… | ||
| Operating Limits | |||||||
| AC- 50 Hz | Pick-up | [x Us] | 0.85…1.1 | ||||
| Drop-out | [x Us] | 0.2…0.5 | 0.2…0.75 | 0.1…0.6 | |||
| AC- 60 Hz | Pick-up | [x Us] | 0.85…1.1 | ||||
| Drop-out | [x Us] | 0.2…0.5 | 0.2…0.75 | 0.1…0.6 | |||
| DC Control | Pick-up | [x Us] | 0.85…1.1 | ||||
| Drop-out | [x Us] | 0.2…0.5 | 0.2…0.75 | 0.1…0.6 | |||
| Pickup and Holding Power | |||||||
| AC- 50 Hz | Pick-up | [VA] | 800…950 | 1350…1600 | 2400 | ||
| Hold-in | [VA] | 9…11 | 21…25 | 70 | |||
| AC- 60 Hz | Pick-up | [VA] | 800…950 | 1350…1600 | 2400 | ||
| Hold-in | [VA] | 9…11 | 21…25 | 70 | |||
| DC Control | Pick-up | [W] | 700…850 | 1300…1550 | 2100 | ||
| Hold-in | [W] | 8…10 | 18…22 | 60 | |||
| Operating Times: Switching Delay | |||||||
| AC | Making delay | [ms] | 50…100 | 50…100 | |||
| Breaking delay | [ms] | 20…50 /150…200/500…1000§ | 25…50 | ||||
| DC | Making delay | [ms] | 50…100 | 50…100 | |||
| Breaking delay | [ms] | 20…50 /150…200/500…1000§ | 25…50 | ||||
| Accelerates | |||||||
| § Delays | |||||||
Auxiliary Contacts
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000… | 100-G1200… | |||
| AC Switching | ||||||||
| AC-1 | Ith | at 40 °C | [A] | 16 | 16 | |||
| at 60 °C | [A] | 12 | 12 | |||||
| AC- 15 at rated voltage | 120V | [A] | 6 | 6 | ||||
| 230V | [A] | 3 | 3 | |||||
| 240V | [A] | 3 | 3 | |||||
| 400V | [A] | 2 | 2 | |||||
| 415V | [A] | 2 | 2 | |||||
| 500V | [A] | 1.5 | 1.5 | |||||
| 690V | [A] | 1 | 1 | |||||
| DC Switching DC-13 control of electromagnets |
24V DC | [A] | 6 | 6 | ||||
| 48V DC | [A] | 3 | 3 | |||||
| 110V DC | [A] | 1 | 1 | |||||
| 220V DC | [A] | 0.5 | 0.5 | |||||
| Back-up Fuse Short-circuit protection without contact welding per IEC 60947-5 |
||||||||
| Fuse gG | [A] | 10 | 16 | |||||
General Data
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000…⋆ | 100-G1200… | ||
| Rated Isolation Voltage Ui | |||||||
| IEC, AS, BS, SEV, VDE, 0660 UL/CSA |
[V] |
1,000V 600V |
690V 600V |
||||
| Impulse Voltage Uimp | |||||||
| 1 minute per IEC 947-4 | [KV] | 8 kV | 2,5 kV | ||||
| Rated Voltage - Main Control Ue | |||||||
| AC | 50/60 Hz | [V] | 230, 240, 400, 415, 460, 500, 575, 690V | 230, 240, 400, 415, 460, 500, 575, 690V | |||
| DC | [V] | 24, 48, 110, 220, 440V | |||||
| Operating Frequency for AC Loads 50/60 Hz |
[Hz] | 180/hr. for 0.25s start time - 42/hr. for 1s start time | |||||
| Insulation Class of the Magnetic Coil | Class B per VDE 0660, table 22 | ||||||
| Rated frequency of the Coil | AC 50/60 Hz, DC | ||||||
| Ambient Temperature | |||||||
| Storage | -40 °C…+80 °C | ||||||
| Operation at rated current | -25 °C…+70 °C | ||||||
| Climatic Withstand | Damp alternating conditions cyclical, per DIN 50 016 and 40 046, part 38, IEC 60068 | ||||||
| Altitude | 2000 m above sea level, per IEC 60947-1 | ||||||
| Type of Protection | IP00 IEC 60529/DIN 40 050 | ||||||
| Standards Compliance | IEC 60947, UL 508, CSA C22.2, No. 14 | ||||||
| Certifications | cULus, CE | ||||||
| ⋆ Cat. No. 100-G1000… is not cULus certified. | |||||||
Life-Load Curves
100-G550…100-G1200
AC-3 Switching of Running Three-phase Motors, Ue = 380…460V AC
AC-1 Non or Slightly Inductive Loads, Resistance Furnaces
|
AC-4 Jogging of Squirrel-cage Motors, Ue = 380…460V AC
|
100-G550…100-G1200
AC-3 90% Switching of Running Motors, Ue = 380…460V AC
AC-4 10% Jogging
|
Permissable Switching Rate
100-G550…100-G1200
Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 0.25 s, Relative Running Time 40%
|
100-G550…100-G1200
Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 1 s, Relative Running Time 40%
|
100-G550…100-G1200
Switching of Starting Motors (AC-2, and AC4) Uz = 380…460V AC
Starting Time ted = 1 s, (<ts)
|