Bulletin 100-G IEC Contactors
|
Bulletin 100-G — IEC Contactors
- 315...710 kW, 400V
- 350…900 Hp, 460/575V
- 3-Pole contactors
- 4th add-on neutral switching pole
- AC and DC control
- Horizontal and vertical interlocking
- Mechanical latching
- Meets IEC, CE, and cULus Standards and Certifications
Your order must include: cat. no. of the contactor selected, coil voltage code, overload relay suffix code, and, if required, cat. no. of any accessories.
The Bulletin 100-G contactor product family provides reliable switching of motor loads up to 1200 A. A complete range of accessories including auxiliary contacts, mechanical latches, horizontal and vertical interlocks, and 4th add-on neutral switching poles provides maximum flexibility to meet a wide variety of application requirements.
Standards Compliance and Certifications
Standards Compliance
EN/IEC 60947-4-1
IEC 60947 Type 1 Coordination
CSA C22.2 No. 14
UL 508
Certifications
CE Marked
cULus Listed (File No. E 3125, Guide NLDX, NLDX7)
Product Selection
AC and DC Control
Ä Coil Voltage Code
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 50/60Hz:
Cat. No. 100-G550Ä22 becomes Cat. No.100-G550KD22.
| For Use With: | [V] | 100…110 | 110…120 | 200…220 | 220…240 | 345…380 | 380…415 | 400…440 | 440…480 |
| 100-G550...100-G860 | 50/60 Hz | — | KD | — | KF | — | KN | — | KB |
| DC | KD | — | KF | — | KN | — | KB | — | |
| For Use With: | [V] | 110…115 | 110 | 220…230 | 220 | 240 | 380…400 | 440 | 480V |
| 100-G1000...100-G1200 | 50/60 Hz | KD | — | KF | — | KA | KN | KB | KU |
| DC | — | ZD♣ | — | ZA♣ | — | — | — | — | |
| ♣ Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||
| Price Adder For | Type | Available Control Voltages | No Surcharge |
| Special control voltages | 100-G550…100-G860 | 24…600V 50/60 Hz, 24…440V DC | >25 pieces |
| 100-G1000…100-G1200 | 48…600V 50/60 Hz, 48…440V DC | ||
Bulletin 100-G Accessories
Control Modules
Ä Coil Voltage Codes⋆
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 100-FLAM5Ä becomes Cat. No.100-FLAM5KD.
| For use with | [V] | 110...120 | 220...240 | 380...415 | 440...480 |
| 100-G550... 100-G860 | 50-60 Hz | KD | KF | KN | KB |
| ⋆ For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||
Bulletin 100-G Specifications
Electrical Data
| Cat. No. | 100-G550... | 100-G700... | 100-G860... | 100-G1000 | 100-G1200 | |||
| AC-1, Three-phase Switching - IEC Ambient temperature: 40 °C |
||||||||
| Ie | £ | 690V | [A] | 760 | 1000 | 1100 | 1200 | 1350 |
| 230V | [kW] | 303 | 398 | 438 | 478 | 538 | ||
| 240V | [kW] | 316 | 416 | 457 | 499 | 561 | ||
| 400V | [kW] | 527 | 693 | 762 | 831 | 935 | ||
| 415V | [kW] | 546 | 719 | 791 | 863 | 970 | ||
| 500V | [kW] | 658 | 866 | 953 | 1039 | 1169 | ||
| 690V | [kW] | 908 | 1195 | 1315 | 1434 | 1613 | ||
| Ambient temperature: 60 °C | ||||||||
| Ie | £ | 690V | [A] | 605 | 800 | 870 | 960 | 1,085 |
| 230V | [kW] | 241 | 319 | 347 | 382 | 432 | ||
| 240V | [kW] | 251 | 333 | 362 | 399 | 451 | ||
| 400V | [kW] | 419 | 554 | 603 | 665 | 752 | ||
| 415V | [kW] | 435 | 575 | 625 | 690 | 780 | ||
| 500V | [kW] | 524 | 693 | 753 | 831 | 940 | ||
| 690V | [kW] | 723 | 956 | 1040 | 1147 | 1297 | ||
| Continuous Current - UL/CSA General Purpose Rating 40 °C |
[A] | 520 | 700 | 810 | — | 1215 | ||
| Switching of 3-phase Motors - IEC | ||||||||
| AC-2, AC-3 | 230/240V | [A] | 550 | 700 | 860 | 1000 | 1200 | |
| 50 Hz/60 °C | 400/415V | [A] | 550 | 700 | 860 | 1000 | 1200 | |
| 500V | [A] | 550 | 700 | 860 | 1000 | 1200 | ||
| 690V | [A] | 500 | 630 | 700 | 860 | 1000 | ||
| 230V | [kW] | 179 | 228 | 280 | 326 | 391 | ||
| 240V | [kW] | 187 | 238 | 293 | 340 | 408 | ||
| 400V | [kW] | 312 | 414 | 509 | 592 | 710 | ||
| 415V | [kW] | 324 | 430 | 528 | 628 | 737 | ||
| 500V | [kW] | 407 | 518 | 636 | 756 | 888 | ||
| 690V | [kW] | 510 | 657 | 730 | 897 | 1043 | ||
| AC-4 at 200000 operations | ||||||||
| 50 Hz | 230/240V | [A] | 140 | 180 | 210 | 260 | 300 | |
| 400/415V | [A] | 140 | 180 | 210 | 260 | 300 | ||
| 230V | [kW] | 45 | 57 | 67 | 83 | 97 | ||
| 240V | [kW] | 47 | 60 | 70 | 87 | 101 | ||
| 400V | [kW] | 78 | 101 | 118 | 146 | 170 | ||
| 415V | [kW] | 81 | 105 | 122 | 151 | 176 | ||
| AC-4, Squirrel-cage motors with reversing and jogging at 20,000 (25,000), operations |
||||||||
| 230/240V | [A] | 360 | 430 | 520 | (630) | (700) | ||
| 400/415V⋆ | [A] | 350 | 420 | 520 | (630) | (700) | ||
| 230V | [kW] | 116 | 139 | 170 | (205) | (228) | ||
| 240V | [kW] | 120 | 151 | 177 | (214) | (245) | ||
| 400V | [kW] | 198 | 238 | 295 | (357) | (414) | ||
| 415V | [kW] | 206 | 247 | 300 | (359) | (424) | ||
| ⋆ At rated Voltage 415V and rated current: Life span - 25%. | ||||||||
| Cat. No. | 100-G550 | 100-G700 | 100-G860 | 100-G1000... | 100-G1200... | ||||
| Switching of 3-phase Motors - UL/CSA | |||||||||
| 60 Hz/60 °C | 200V | [A] | 414 | 552 | 692 | — | 1185 | ||
| 230V | [A] | 360 | 602 | 722 | — | 1130 | |||
| 460V | [A] | 414 | 590 | 708 | — | 1062 | |||
| 575V | [A] | 336 | 472 | 576 | — | 864 | |||
| 200V | [Hp] | 150 | 200 | 250 | — | 450 | |||
| 230V | [Hp] | 150 | 250 | 300 | — | 450 | |||
| 460V | [Hp] | 350 | 500 | 600 | — | 900 | |||
| 575V | [Hp] | 350 | 500 | 600 | — | 900 | |||
| Rated making capacity | |||||||||
| AC-3 Ie | £ | 415V | [A] | 5500 | 7000 | 8600 | 10000 | 12000 | |
| 500V | [A] | 5500 | 7000 | 8600 | 10000 | 12000 | |||
| 690V | [A] | 5500 | 7000 | 8600 | 10000 | 12000 | |||
| Rated Breaking capacity | |||||||||
| AC-3 Ie | £ | 240V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |
| 400V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |||
| 415V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |||
| 500V | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | |||
| 690V | [A] | 4000 | 5100 | 5600 | 6900 | 8000 | |||
| Star-Delta Starting | |||||||||
| 50 Hz | 230V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | ||
| 240V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 400V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 415V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 500V | [A] | 953 | 1212 | 1490 | 1732 | 2078 | |||
| 690V | [A] | 831 | 1091 | 1195 | 1490 | 1732 | |||
| 230V | [kW] | 310 | 395 | 485 | 565 | 677 | |||
| 240V | [kW] | 324 | 412 | 507 | 589 | 707 | |||
| 400V | [kW] | 540 | 717 | 882 | 1025 | 1250 | |||
| 415V | [kW] | 561 | 745 | 915 | 1088 | 1278 | |||
| 500V | [kW] | 705 | 897 | 1102 | 1309 | 1538 | |||
| 690V | [kW] | 883 | 1138 | 1247 | 1554 | 2078 | |||
| Wye-Delta Starting | |||||||||
| 60 Hz | 230V | [Hp] | 250 | 400 | 500 | 650 | 750 | ||
| 460V | [Hp] | 600 | 800 | 1000 | 1300 | 1500 | |||
| 575V | [Hp] | 600 | 800 | 1000 | 1500 | 1500 | |||
| Short-circuit Protection of Contactors without Overload Relay |
|||||||||
| Fuse gG (aM) Type 1 coordination (per IEC 60947-4-1) |
500V | [A] | (630) | 800 | 1000 | 1000 | 1250 | ||
| 690V | [A] | (630) | 800 | 1000 | 1000 | 1000 | |||
| Switching of Three-phase Capacitor Inductivity of dispatching between parallel switched capacitor: min. 6 pH |
|||||||||
| Single capacitors | 40 °C | 230V | [kVar] | 180 | 220 | 250 | 290 | 330 | |
| 240V | [kVar] | 200 | 250 | 300 | 325 | 360 | |||
| 400V | [kVar] | 320 | 400 | 450 | 500 | 575 | |||
| 415V | [kVar] | 350 | 430 | 500 | 550 | 630 | |||
| 500V | [kVar] | 450 | 520 | 600 | 660 | 750 | |||
| 690V | [kVar] | 580 | 700 | 800 | 875 | 1000 | |||
| 55 °C | 230V | [kVar] | 150 | 180 | 220 | 275 | 325 | ||
| 240V | [kVar] | 170 | 200 | 260 | 300 | 350 | |||
| 400V | [kVar] | 280 | 330 | 400 | 460 | 550 | |||
| 415V | [kVar] | 300 | 360 | 450 | 500 | 600 | |||
| 500V | [kVar] | 360 | 420 | 540 | 600 | 720 | |||
| 690V | [kVar] | 500 | 580 | 720 | 800 | 950 | |||
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000… | 100-G1200… | |||
| Capacitor Banks |
40 °C |
230V | [kVar] | 180 | 220 | 250 | 290 | 330 |
| 240V | [kVar] | 200 | 250 | 300 | 325 | 360 | ||
| 400V | [kVar] | 320 | 400 | 450 | 500 | 575 | ||
| 415V | [kVar] | 350 | 430 | 500 | 550 | 430 | ||
| 500V | [kVar] | 450 | 520 | 600 | 660 | 750 | ||
| 690V | [kVar] | 580 | 700 | 800 | 875 | 1000 | ||
| 55 °C |
230V | [kVar] | 150 | 180 | 220 | 275 | 325 | |
| 240V | [kVar] | 170 | 200 | 260 | 300 | 350 | ||
| 400V | [kVar] | 280 | 330 | 400 | 460 | 550 | ||
| 415V | [kVar] | 300 | 360 | 450 | 500 | 600 | ||
| 500V | [kVar] | 360 | 420 | 540 | 600 | 720 | ||
| 690V | [kVar] | 500 | 580 | 720 | 800 | 950 | ||
| DC Switching Switching of non- or slightly inductive loads, resistance furnaces DC-1 at 60 °C |
||||||||
| 1 Pole | 24/48V | [A] | 645 | 760 | 930 | 1020 | 1150 | |
| 2 Poles in series | 24/48V | [A] | 645 | 760 | 930 | 1020 | 1150 | |
| 3 Poles in series |
24/48V | [A] | 645 | 760 | 930 | 1020 | 1150 | |
| 110V | [A] | 480 | 560 | 630 | 800 | 900 | ||
| 220V | [A] | 315 | 400 | 450 | 500 | 600 | ||
| Shunt-Wound Motors Starting, plugging, reversing, plugging DC-3 at 60 °C |
||||||||
| 3 Poles in series | 24/48V | [A] | 605 | 800 | 870 | 960 | 1085 | |
| Series-Wound Motors Starting, plugging, reversing, plugging DC-5 at 60 °C |
||||||||
| 3 Poles in series | 24/48V | [A] | 605 | 800 | 870 | 960 | 1085 | |
| Lighting Loads Elec. Discharge. Lamps - AC - 5a, |
||||||||
| Non-Compensated | [A] | 450 | 570 | 700 | 850 | 1000 | ||
| Compensated | [A] | 360 | 460 | 550 | 660 | 800 | ||
| Incandescent Lamps - AC - 5b, Electrical Endurance @ 100 000 ops |
[A] |
315 |
440 |
500 |
560 |
630 |
||
| Switching Power Transformers AC - 6a | ||||||||
| Inrush = n · Ie | [A] | 7440 | 9450 | 11700 | 13500 | 16200 | ||
| Ie Rated transformer current | [A] | 248 | 315 | 390 | 450 | 540 | ||
| n = 30 | 400V AC | [kVA] | 172 | 218 | 270 | 312 | 374 | |
| 500V AC | [kVA] | 215 | 273 | 338 | 390 | 468 | ||
| 690V AC | [kVA] | 269 | 339 | 376 | 538 | 645 | ||
| n = 20 | [A] | 371 | 472 | 580 | 675 | 810 | ||
| n = 15 | [A] | 435 | 630 | 774 | 900 | 1080 | ||
| Rated Short-Time Withstand ICW, 60 °C | ||||||||
| 1 s | [A] | 5500 | 7000 | 8000 | 10000 | 12000 | ||
| 4 s | [A] | 5500 | 7000 | 8000 | 10000 | 12000 | ||
| 10 s | [A] | 4400 | 5600 | 6900 | 8000 | 9600 | ||
| 15 s | [A] | 3800 | 5000 | 6000 | 7400 | 8500 | ||
| 60 s | [A] | 2300 | 2800 | 3400 | 4000 | 4800 | ||
| 240 s | [A] | 1300 | 1800 | 2000 | 2300 | 2700 | ||
| 900 s | [A] | 850 | 1150 | 1350 | 1600 | 1900 | ||
| Minimum cooling time at zero current | [Min.] | 60 | 60 | 60 | 60 | 60 | ||
| Resistance and Energy Dissipation | ||||||||
| Main circuit resistance | [mW] | 0.11 | 0.1 | 0.08 | 0.06 | 0.05 | ||
| Total energy dissipation at Ie AC-3 | [W] | 99 | 147 | 177 | 180 | 216 | ||
| Excess energy dissipation at Ie AC-3 | ||||||||
| AC Control | [W] | 110 | 172 | 202 | 250 | 286 | ||
| DC Control | [W] | 109 | 169 | 199 | 240 | 276 | ||
Mechanical Data
Coil Data
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000… | 100-G1200… | ||
| Operating Limits | |||||||
| AC- 50 Hz | Pick-up | [x Us] | 0.85…1.1 | ||||
| Drop-out | [x Us] | 0.2…0.5 | 0.2…0.75 | 0.1…0.6 | |||
| AC- 60 Hz | Pick-up | [x Us] | 0.85…1.1 | ||||
| Drop-out | [x Us] | 0.2…0.5 | 0.2…0.75 | 0.1…0.6 | |||
| DC Control | Pick-up | [x Us] | 0.85…1.1 | ||||
| Drop-out | [x Us] | 0.2…0.5 | 0.2…0.75 | 0.1…0.6 | |||
| Pickup and Holding Power | |||||||
| AC- 50 Hz | Pick-up | [VA] | 800…950 | 1350…1600 | 2400 | ||
| Hold-in | [VA] | 9…11 | 21…25 | 70 | |||
| AC- 60 Hz | Pick-up | [VA] | 800…950 | 1350…1600 | 2400 | ||
| Hold-in | [VA] | 9…11 | 21…25 | 70 | |||
| DC Control | Pick-up | [W] | 700…850 | 1300…1550 | 2100 | ||
| Hold-in | [W] | 8…10 | 18…22 | 60 | |||
| Operating Times: Switching Delay | |||||||
| AC | Making delay | [ms] | 50…100 | 50…100 | |||
| Breaking delay | [ms] | 20…50 /150…200/500…1000§ | 25…50 | ||||
| DC | Making delay | [ms] | 50…100 | 50…100 | |||
| Breaking delay | [ms] | 20…50 /150…200/500…1000§ | 25…50 | ||||
| Accelerates | |||||||
| § Delays | |||||||
Auxiliary Contacts
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000… | 100-G1200… | |||
| AC Switching | ||||||||
| AC-1 | Ith | at 40 °C | [A] | 16 | 16 | |||
| at 60 °C | [A] | 12 | 12 | |||||
| AC- 15 at rated voltage | 120V | [A] | 6 | 6 | ||||
| 230V | [A] | 3 | 3 | |||||
| 240V | [A] | 3 | 3 | |||||
| 400V | [A] | 2 | 2 | |||||
| 415V | [A] | 2 | 2 | |||||
| 500V | [A] | 1.5 | 1.5 | |||||
| 690V | [A] | 1 | 1 | |||||
| DC Switching DC-13 control of electromagnets |
24V DC | [A] | 6 | 6 | ||||
| 48V DC | [A] | 3 | 3 | |||||
| 110V DC | [A] | 1 | 1 | |||||
| 220V DC | [A] | 0.5 | 0.5 | |||||
| Back-up Fuse Short-circuit protection without contact welding per IEC 60947-5 |
||||||||
| Fuse gG | [A] | 10 | 16 | |||||
General Data
| Cat. No. | 100-G550… | 100-G700… | 100-G860… | 100-G1000…⋆ | 100-G1200… | ||
| Rated Isolation Voltage Ui | |||||||
| IEC, AS, BS, SEV, VDE, 0660 UL/CSA |
[V] |
1,000V 600V |
690V 600V |
||||
| Impulse Voltage Uimp | |||||||
| 1 minute per IEC 947-4 | [KV] | 8 kV | 2,5 kV | ||||
| Rated Voltage - Main Control Ue | |||||||
| AC | 50/60 Hz | [V] | 230, 240, 400, 415, 460, 500, 575, 690V | 230, 240, 400, 415, 460, 500, 575, 690V | |||
| DC | [V] | 24, 48, 110, 220, 440V | |||||
| Operating Frequency for AC Loads 50/60 Hz |
[Hz] | 180/hr. for 0.25s start time - 42/hr. for 1s start time | |||||
| Insulation Class of the Magnetic Coil | Class B per VDE 0660, table 22 | ||||||
| Rated frequency of the Coil | AC 50/60 Hz, DC | ||||||
| Ambient Temperature | |||||||
| Storage | -40 °C…+80 °C | ||||||
| Operation at rated current | -25 °C…+70 °C | ||||||
| Climatic Withstand | Damp alternating conditions cyclical, per DIN 50 016 and 40 046, part 38, IEC 60068 | ||||||
| Altitude | 2000 m above sea level, per IEC 60947-1 | ||||||
| Type of Protection | IP00 IEC 60529/DIN 40 050 | ||||||
| Standards Compliance | IEC 60947, UL 508, CSA C22.2, No. 14 | ||||||
| Certifications | cULus, CE | ||||||
| ⋆ Cat. No. 100-G1000… is not cULus certified. | |||||||
Life-Load Curves
100-G550…100-G1200
AC-3 Switching of Running Three-phase Motors, Ue = 380…460V AC
AC-1 Non or Slightly Inductive Loads, Resistance Furnaces
|
AC-4 Jogging of Squirrel-cage Motors, Ue = 380…460V AC
|
Life-Load Curves
100-G550…100-G1200
AC-3 90% Switching of Running Motors, Ue = 380…460V AC
AC-4 10% Jogging
|
Permissable Switching Rate
100-G550…100-G1200
Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 0.25 s, Relative Running Time 40%
|
Permissable Switching Rate, Continued
100-G550…100-G1200
Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 1 s, Relative Running Time 40%
|
100-G550…100-G1200
Switching of Starting Motors (AC-2, and AC4) Uz = 380…460V AC
Starting Time ted = 1 s, (<ts)
|
Bulletin 100-G Approximate Dimensions
Bulletin 100-G Contactors and Accessories
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
|
Mounting Position
|
| Cat. No. | a | b | b1 | c | c1 | Æd | d1 | d2 | Æe | e1 | e2 | e3 |
| 100-G550 | 220 | 258 | 228 | 225 | 164 | 9 |
220 | 110 | 12.5 | 40 | 79 | — |
| 100-G700 | 280 | 307 | 277 | 291 | 203 | 11 |
280 | 175 | 13 | 50 | 101 | — |
| 100-G860 | 280 | 361 | 325 | 291 | 203 | 11 | 280 | 175 | 15 | 50 | 101 | — |
| 100-G1000 | 334 | 490 | 434 | 345 | 231 |
13.5 |
380 | 120 | 2x13 | 50 | 100 | 40 |
| 100-G1200 | 334 |
490 | 434 | 345 | 231 | 13.5 | 380 | 120 | 2x13 | 60 | 100 |
40 |
| Contactor with | mm | |||
| Auxiliary contact block | a |
|||
| Mechanical Interlock | side by side | 100-G550/100-G550 100-G700, -860/100-G700, -860 100-G1000, -1200/100-G1000, -1200 100-G550/100-G700, -860 100-G700, -860/100-G1000, -1200 |
a+42+a a+32+a a+46+a a+37+a a+73+a |
|
| stacked vertically | 100-G550/100-G550 100-G700, -860/100-G700, -860 100-G1000, -1200/100-G1000, -1200 100-G550/100-G700, -860 100-G700, -860/100-G1000, -1200 |
b+56 + b b/2+380…480+b/2 b+120…170+b b/2+400+b/2 b/2+570+b/2 |
||
| 4th add-on neutral switching pole | 100-G550 100-G700, -860 100-G1000, -1200 |
a+74 a+68 a+76 |
||
| Mechanical latch | 100-G550 100-G700 100-G860 |
b+59 b+64 b+37 |
||
Renewal Parts
Bulletin 100-M Replacement Coils⋆
Bulletin 100-C Replacement Coils
|
| AC Standard Control Voltages [V] | AC Coil Code | 100-C09…100-C16 | 100-C23…100-C37, 100L-C20 | 100-C40, -C43 | 100-C60…100-C85 | 100-C90…100-C97 | ||
| 50 Hz | 60 Hz | 50/60 Hz | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| — | 12 | — | Q | TA006 | TC006 | TD006 | TE006 | TF006 |
| 12 | — | — | R | TA404 | TC404 | TD404 | TE404 | TF404 |
| — | 24 | — | J | TA013 | TC013 | TD013 | TE013 | TF013 |
| 24 | — | — | K | TA407 | TC407 | TD407 | TE407 | TF407 |
| — | — | 24 | KJ | TA855 | TC855 | TD855 | TE855 | TF855 |
| 32 | 36 | — | V | TA481 | TC481 | TD481 | TE481 | TF481 |
| 36 | 42 | — | W | TA410 | TC410 | TD410 | TE410 | TF410 |
| 42 | 48 | — | X | TA482 | TC482 | TD482 | TE482 | TF482 |
| 48 | — | — | Y | TA414 | TC414 | TD414 | TE414 | TF414 |
| — | — | 48 | KY | TA860 | TC860 | TD860 | TE860 | TF860 |
| 100 | 100…110 | 100 | KP | TA861 | TC861 | TD861 | TE861 | TF861 |
| 110 | 120 | — | D | TA473 | TC473 | TD473 | TE473 | TF473 |
| — | — | 110 | KD | TA856 | TC856 | TD856 | TE856 | TF856 |
| 120 | — | — | P | TA425 | TC425 | TD425 | TE425 | TF425 |
| 127 | — | — | S | TA428 | TC428 | TD428 | TE428 | TF428 |
| 200 | 200…220 | 200 | KG | TA862 | TC862 | TD862 | TE862 | TF862 |
| — | 208 | — | H | TA049 | TC049 | TD049 | TE049 | TF049 |
| 200…220 | 208…240 | — | L | TA296 | TC296 | TD296 | TE296 | TF296 |
| — | — | 200…230 | KL | TA864 | TC864 | TD864 | TE864 | — |
| 220 | 240 | — | A | TA474 | TC474 | TD474 | TE474 | TF474 |
| 220…230 | 260 | — | F | TA441 | TC441 | TD441 | TE441 | TF441 |
| — | — | 230 | KF | TA851 | TC851 | TD851 | TE851 | TF851 |
| 230…240 | — | — | VA | TA440 | TC440 | TD440 | TE440 | TF440 |
| 240 | 277 | — | T | TA480 | TC480 | TD480 | TE480 | TF480 |
| — | — | 240 | KA | TA858 | TC858 | TD858 | TE858 | TF858 |
| — | 347 | — | I | TA065 | TC065 | TD065 | TE065 | TF065 |
| — | 380 | — | E | TA067 | TC067 | TD067 | TE067 | TF067 |
| 380…400 | 440 | — | N | TA071 | TC071 | TD071 | TE071 | TF071 |
| — | — | 400 | KN | TA863 | TC863 | TD863 | TE863 | TF863 |
| 400…415 | — | — | G | TA457 | TC457 | TD457 | TE457 | TF457 |
| 440 | 480 | — | B | TA475 | TC475 | TD475 | TE475 | TF475 |
| — | — | 440 | KB | TA859 | TC859 | TD859 | TE859 | TF859 |
| 500 | — | — | M | TA479 | TC479 | TD479 | TE479 | TF479 |
| 550 | 600 | — | C | TA476 | TC476 | TD476 | TE476 | TF476 |
Coils, Continued
|
| DC Standard Control Voltage [V] | DC Coil Code | 100-C09…100-C16 | 100-C23…100-C37, 100L-C20 | 100-C40, -C43 | 100-C60…100-C85 | 100-C90…100-C97 |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||
| 9⋆ | ZR | TA766 | TC766 | TD766 | — | — |
| 9V Diode⋆ | DR | — | — | — | TE766M | TF766M |
| 12 | ZQ | TA708 | TC708 | TD708 | — | — |
| 12V Diode | DQ | — | — | — | TE708M | TF708M |
| 24 | ZJ | TA714 | TC714 | TD714 | — | — |
| 24 Diode | DJ | TA714M | TC714M | TD714M | TE714M | TF714M |
| 36 | ZW | TA719 | TC719 | TD719 | — | — |
| 36V Diode | DW | — | — | — | TE719M | TF719M |
| 48 | ZY | TA724 | TC724 | TD724 | — | — |
| 48V Diode | DY | — | — | — | TE724M | TF724M |
| 60 | ZZ | TA774 | TC774 | TD774 | — | — |
| 60V Diode | DZ | — | — | — | TE774M | TF774M |
| 64 | ZB | TA727 | TC727 | TD727 | — | — |
| 64V Diode | DB | — | — | — | TE727M | TF727M |
| 72 | ZG | TA728 | TC728 | TD728 | — | — |
| 72V Diode | DG | — | — | — | TE728M | TF728M |
| 80 | ZE | TA729 | TC729 | TD729 | — | — |
| 80V Diode | DE | — | — | — | TE729M | TF729M |
| 110 | ZD | TA733 | TC733 | TD733 | — | — |
| 110V Diode | DD | — | — | — | TE733M | TF733M |
| 115 | ZP | TA734 | TC734 | TD734 | — | — |
| 115V Diode | DP | — | — | — | TE734M | TF734M |
| 125 | ZS | TA737 | TC737 | TD737 | — | — |
| 125V Diode | DS | — | — | — | TE737M | TF737M |
| 220 | ZA | TA747 | TC747 | TD747 | — | — |
| 220V Diode | DA | — | — | — | TE747M | TF747M |
| 230 | ZF | TA749 | TC749 | TD749 | — | — |
| 230V Diode | DF | — | — | — | TE749F | TF749F |
| 250 | ZT | TA751 | TC751 | TD751 | — | — |
| 250V Diode | DT | — | — | — | TE751F | TF751F |
| ⋆ Voltage operating range: 0.65…1.3 x Us. | ||||||
| Voltage operating range: 0.7…1.25 x Us. | ||||||
Bulletin 100-D Replacement coils
|
| Conventional AC | Conventional DC | ||||||||||
| AC Standard Control Voltages |
AC Coil Code |
100-D95…D180 | 100-D210…D420 | 100-D630…D860 | DC Standard Control Voltages |
DC Coil Code |
100-D95…D180 | 100-D210…D420 | 100-D630…D860 | ||
| 50 Hz | 60 Hz | 50/60 Hz | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |||
| 24V | — | — | K | TG407 | — | — | 24V | ZJ | TG714 | — | — |
| — | 24V | — | J | TG013 | — | — | 48V | ZY | TG724 | — | — |
| 48V | — | — | Y | TG414 | — | — | 110V | ZD | TG733 | — | — |
| 42V | 48V | — | X | TG482 | — | — | 125V | ZS | TG737 | — | — |
| — | — | 100V⋆ | KP | TG861 | — | — | 220V | ZA | TG761 | — | — |
| 110V | 120V | — | D | TG473 | — | — | |||||
| — | — | 110V⋆ | KN | TG856 | — | — | |||||
| — | 208V | — | H | TG049 | — | — | |||||
| — | — | 200V⋆ | KG | TG862 | — | — | |||||
| — | — | 220V⋆ | KL | TG857 | — | — | |||||
| 220…230V | 240V | — | A | TG441 | — | — | |||||
| 240V | 277V | — | T | TG480 | — | — | |||||
| — | — | 277V⋆ | KT | TG060 | — | — | |||||
| — | — | 230V⋆ | KF | TG851 | — | — | |||||
| — | — | 240V⋆ | KA | TG858 | — | — | |||||
| 380…400V | 440V | — | N | TG071 | — | — | |||||
| 415V | 480V | — | B | TG475 | — | — | |||||
| 440V | — | — | G | TG478 | — | — | |||||
| 500V | — | — | M | TG479 | — | — | |||||
| 550V | 600V | — | C | TG476 | — | — | |||||
| Electronic AC | Electronic DC | ||||||||||
| AC Standard Control Voltages |
AC Coil Code |
100-D95…D300 | 100-D420 | 100-D630…D860 | DC Standard Control Voltage | DC Coil Code |
100-D95…D300 | 100-D420 | 100-D630…D860 | ||
| 50 Hz | 60 Hz | 50/60 Hz | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |||
| — | — | 24V | EJ | TGE855 | — | — | 24V | EZJ | TGE708 | — | — |
| — | — | 42…64V | EY | TGE864 | — | — | 48…72V | EZY | TGE779 | — | — |
| — | — | 100V | EP | TGE861 | THE861 | TJE861 | 110…130V | EZD | TGE780 | THE780 | — |
| — | — | 110…130V | ED | TGE865 | THE865 | TJE865 | ED | — | — | TJE865 | |
| — | — | 200V | EG | TGE862 | THE862 | — | 200…255V | EZA | TGE781 | THE781 | — |
| — | — | 208…277V | EA | TGE866 | THE866 | — | EA | — | — | TJE879 | |
| — | — | 200…220V | EG | — | — | TJE878 | |||||
| — | — | 230…250V | EA | — | — | TJE879 | |||||
| — | — | 277V | ET | — | — | TJE880 | |||||
| — | — | 380…500V | EN | TGE867 | THE867 | — | |||||
| — | — | 380…415V | EN | — | — | TJE867 | |||||
| — | — | 440…480V | EB | — | — | TJE868 | |||||
| — | — | 500V | EM | — | — | TJE869 | |||||
| ⋆ Applies to 100-D95…-D115 contactors only. Not available with 100-D140…-D180 contactors. | |||||||||||
| Not available on 100/104-D300. | |||||||||||
Bulletin 100-G Renewal Parts
Coils and Supply Modules
|
|
| AC Standard Control Voltages |
DC Standard Control Voltage | Coil Code | 100-G550 | 100-G700...100-G860 | ||
| 50/60 Hz | ||||||
| 110…120V | 100…110V | KD | TX734 | TXS734 | TY734 | TYS734 |
| 220…240V | 200…220V | KF | TX747 | TXS747 | TY747 | TYS747 |
| 380…415V | 345…380V | KN | TX779 | TXS779 | TY779 | TYS779 |
| 440…480V | 400…440V | KB | TX780 | TXS780 | TY780 | TYS780 |
| ⋆ Coils sold in pairs. | ||||||
| AC Standard Control Voltages |
Coil Code | 100-G1000...100-G1200 | |
| Coil Cat. No.⋆ | Supply Module Cat. No. | ||
| 50/60 Hz | |||
| 110…115V | KD | TZ734 | TZS734 |
| 220…230V | KF | TZ747 | TZS747 |
| 380…400V | KN | TZ779 | TZS779 |
| 440V | KB | TZ780 | TZS780 |