Bulletin 100-G IEC Contactors

Click to enlarge - 100-G_GS


Bulletin 100-G — IEC Contactors


Your order must include: cat. no. of the contactor selected, coil voltage code, overload relay suffix code, and, if required, cat. no. of any accessories.

The Bulletin 100-G contactor product family provides reliable switching of motor loads up to 1200 A. A complete range of accessories including auxiliary contacts, mechanical latches, horizontal and vertical interlocks, and 4th add-on neutral switching poles provides maximum flexibility to meet a wide variety of application requirements.

Standards Compliance and Certifications

Standards Compliance

EN/IEC 60947-4-1
IEC 60947 Type “1” Coordination
CSA C22.2 No. 14
UL 508


Certifications

CE Marked
cULus Listed (File No. E 3125, Guide NLDX, NLDX7)


Product Selection

AC and DC Control

AC-1 Switching of 3-phase motors—AC-2, AC-3 Auxiliary Contacts Cat. No.
Ie [A] kW (50 Hz)§  Hp (60 Hz) kW (50 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
40 °C 230V 400V 500V 690V 200V 230V 460V 575V 400V N.O. N.C.
760 160 315 400 500 150 150 350 350 315 2 2 100-G550Ä22
1000 220 400 500 630 200 250 500 500 400 2 2 100-G700Ä22
1100 280 500 630 710 250 300 600 600 500 2 2 100-G860Ä22
1200 315 560 750 850 560 2⋆  2 ‡  100-G1000Ä12
1350 375 710 900 1000 450 450 900 900 710 2⋆  2 100-G1200Ä12
  
‡ No UL/cUL
§ Preferred value according to IEC 60072-1.

Ä Coil Voltage Code

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 50/60Hz:
Cat. No. 100-G550Ä22 becomes Cat. No.100-G550KD22.


For Use With: [V] 100…110 110…120 200…220 220…240 345…380 380…415 400…440 440…480
100-G550...100-G860 50/60 Hz KD KF KN KB
DC KD KF KN KB
  

For Use With: [V] 110…115 110 220…230 220 240 380…400 440 480V
100-G1000...100-G1200 50/60 Hz KD KF KA KN KB KU
DC ZD♣  ZA♣ 
  
♣ Consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Price Adder For Type Available Control Voltages No Surcharge
Special control voltages 100-G550…100-G860 24…600V 50/60 Hz, 24…440V DC >25 pieces
100-G1000…100-G1200 48…600V 50/60 Hz, 48…440V DC
  

Bulletin 100-G Accessories

Control Modules

  Description For Use With Cat. No.
Click to enlarge - 100-EF22_GS Auxiliary Contact Block
  • For mounting between T1 & T2 or between T2 & T3

  • Adjustable; provides normal, delayed, or overlapping contacts

  • Max. two blocks/contactor

  • Alternate terminal marking tags included

  • 2 N.O. and 2 N.C. contacts
  • Click to enlarge - 100G-94-2 100-G550…100-G860 100-EF22
    Standard Terminal marking for mounting between T1 & T2
    Click to enlarge - 100G-94-3
    Alternate terminal marking for mounting between T2 & T3
    4-Pole
    Click to enlarge - 100-EB_GS Auxiliary Contact Block
  • For side mounting on either side of the contactor

  • Max. four blocks/contactor

  • Alternate terminal marking tags included

  • 1 N.O. and 1 N.C. contact
  • Click to enlarge - 100G-94-5 100-G1000…100-G1200 100-EB11
    Standard terminal marking
    Click to enlarge - 100G-94-6 Click to enlarge - 100G-94-7
    Alternate terminal markings
    2-Pole
    Click to enlarge - 100-NP_GS Fourth Add-On Neutral Switching Pole
  • Left- or right-side mountable

  • Note: no UL/cUL
  • Ith AC-1 500 A 100-G550 100-NP800-5
    100-G700, 100-G860 100-NP500-6
    Ith AC-1 1000A 100-G700, 100-G860 100-NP1000-6
    100-G1000, 100-G1200 100-NP1000-7
    Click to enlarge - 100-FLAM_GS Mechanical Latch
  • Mechanical life: 0.5 million operations

  • Direct and Impulse Control
  • Direct and Impulse Contact control 100-G550 100-FLAM5Ä
    Direct and Impulse Contact control 100-G700, 100-G860 100-FLAM6Ä
    Click to enlarge - 100-MCH00_GS Mechanical Interlock — Horizontal 100-G550 to 100-G550 100-MC00-5H
    100-G550 to 100-G700 or 100-G860 100-MC00-56H
    100-G700 or 100-G860 to 100-G700 or 100-G860 100-MC00-6H
    100-G700 or 100-G860 to 100-G1000 or 100-G1200 100-MC00-67H
    100-G1000 or 100-G1200 to 100-G1000 or 100-G1200 100-MC00-7H
    Click to enlarge - 100-MCV00_GS Mechanical Interlock — Vertical 100-G550 to 100-G550 100-MC00-5V
    100-G550 to 100-G700 or 100-G860 100-MC00-56V
    100-G700 or 100-G860 to 100-G700 or 100-G860 100-MC00-6V
    100-G700 or 100-G860 to 100-G1000 or 100-G1200 100-MC00-67V
    100-G1000 or 100-G1200 to 100-G1000 or 100-G1200 100-MC00-7V
      
    Package Quantity = 1

    Ä Coil Voltage Codes⋆ 

    The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 100-FLAM5Ä becomes Cat. No.100-FLAM5KD.

    For use with [V] 110...120 220...240 380...415 440...480
    100-G550... 100-G860 50-60 Hz KD KF KN KB
      
    ⋆ For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

    Bulletin 100-G Specifications

    Electrical Data

    Cat. No. 100-G550... 100-G700... 100-G860... 100-G1000 100-G1200
    AC-1, Three-phase Switching - IEC
    Ambient temperature: 40 °C
             
            Ie £ 690V [A] 760 1000 1100 1200 1350
    230V [kW] 303 398 438 478 538
    240V [kW] 316 416 457 499 561
    400V [kW] 527 693 762 831 935
    415V [kW] 546 719 791 863 970
    500V [kW] 658 866 953 1039 1169
    690V [kW] 908 1195 1315 1434 1613
    Ambient temperature: 60 °C          
            Ie £ 690V [A] 605 800 870 960 1,085
    230V [kW] 241 319 347 382 432
    240V [kW] 251 333 362 399 451
    400V [kW] 419 554 603 665 752
    415V [kW] 435 575 625 690 780
    500V [kW] 524 693 753 831 940
    690V [kW] 723 956 1040 1147 1297
    Continuous Current - UL/CSA
    General Purpose Rating 40 °C
    [A] 520 700 810 1215
    Switching of 3-phase Motors - IEC          
    AC-2, AC-3   230/240V [A] 550 700 860 1000 1200
    50 Hz/60 °C 400/415V [A] 550 700 860 1000 1200
    500V [A] 550 700 860 1000 1200
    690V [A] 500 630 700 860 1000
    230V [kW] 179 228 280 326 391
    240V [kW] 187 238 293 340 408
    400V [kW] 312 414 509 592 710
    415V [kW] 324 430 528 628 737
    500V [kW] 407 518 636 756 888
    690V [kW] 510 657 730 897 1043
    AC-4 at 200000 operations          
    50 Hz   230/240V [A] 140 180 210 260 300
    400/415V [A] 140 180 210 260 300
    230V [kW] 45 57 67 83 97
    240V [kW] 47 60 70 87 101
    400V [kW] 78 101 118 146 170
    415V [kW] 81 105 122 151 176
    AC-4, Squirrel-cage motors with reversing and
    jogging at 20,000 (25,000), operations
             
        230/240V [A] 360 430 520 (630) (700)
    400/415V⋆  [A] 350 420 520 (630) (700)
    230V [kW] 116 139 170 (205) (228)
    240V [kW] 120 151 177 (214) (245)
    400V [kW] 198 238 295 (357) (414)
    415V [kW] 206 247 300 (359) (424)
      
    ⋆ At rated Voltage 415V and rated current: Life span - 25%.

    Cat. No. 100-G550 100-G700 100-G860 100-G1000... 100-G1200...
    Switching of 3-phase Motors - UL/CSA          
    60 Hz/60 °C 200V [A] 414 552 692 1185
    230V [A] 360 602 722 1130
    460V [A] 414 590 708 1062
    575V [A] 336 472 576 864
    200V [Hp] 150 200 250 450
    230V [Hp] 150 250 300 450
    460V [Hp] 350 500 600 900
    575V [Hp] 350 500 600 900
    Rated making capacity          
    AC-3 Ie £ 415V [A] 5500 7000 8600 10000 12000
    500V [A] 5500 7000 8600 10000 12000
    690V [A] 5500 7000 8600 10000 12000
    Rated Breaking capacity          
    AC-3 Ie £ 240V [A] 4400 5600 6900 8000 9600
    400V [A] 4400 5600 6900 8000 9600
    415V [A] 4400 5600 6900 8000 9600
    500V [A] 4400 5600 6900 8000 9600
    690V [A] 4000 5100 5600 6900 8000
    Star-Delta Starting          
    50 Hz 230V [A] 953 1212 1490 1732 2078
    240V [A] 953 1212 1490 1732 2078
    400V [A] 953 1212 1490 1732 2078
    415V [A] 953 1212 1490 1732 2078
    500V [A] 953 1212 1490 1732 2078
    690V [A] 831 1091 1195 1490 1732
    230V [kW] 310 395 485 565 677
    240V [kW] 324 412 507 589 707
    400V [kW] 540 717 882 1025 1250
    415V [kW] 561 745 915 1088 1278
    500V [kW] 705 897 1102 1309 1538
    690V [kW] 883 1138 1247 1554 2078
    Wye-Delta Starting          
    60 Hz 230V [Hp] 250 400 500 650 750
    460V [Hp] 600 800 1000 1300 1500
    575V [Hp] 600 800 1000 1500 1500
    Short-circuit Protection of Contactors without
    Overload Relay
             
    Fuse gG (aM) Type 1 coordination
    (per IEC 60947-4-1)
      500V [A] (630) 800 1000 1000 1250
    690V [A] (630) 800 1000 1000 1000
    Switching of Three-phase Capacitor
    Inductivity of dispatching between parallel switched capacitor: min. 6 pH
    Single capacitors 40 °C   230V [kVar] 180 220 250 290 330
    240V [kVar] 200 250 300 325 360
    400V [kVar] 320 400 450 500 575
    415V [kVar] 350 430 500 550 630
    500V [kVar] 450 520 600 660 750
    690V [kVar] 580 700 800 875 1000
    55 °C 230V [kVar] 150 180 220 275 325
    240V [kVar] 170 200 260 300 350
    400V [kVar] 280 330 400 460 550
    415V [kVar] 300 360 450 500 600
    500V [kVar] 360 420 540 600 720
    690V [kVar] 500 580 720 800 950
      

    Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
    Capacitor Banks




    40 °C




    230V [kVar] 180 220 250 290 330
    240V [kVar] 200 250 300 325 360
    400V [kVar] 320 400 450 500 575
    415V [kVar] 350 430 500 550 430
    500V [kVar] 450 520 600 660 750
    690V [kVar] 580 700 800 875 1000
    55 °C




    230V [kVar] 150 180 220 275 325
    240V [kVar] 170 200 260 300 350
    400V [kVar] 280 330 400 460 550
    415V [kVar] 300 360 450 500 600
    500V [kVar] 360 420 540 600 720
    690V [kVar] 500 580 720 800 950
    DC Switching
    Switching of non- or slightly inductive loads, resistance furnaces
    DC-1 at 60 °C
             
        1 Pole 24/48V [A] 645 760 930 1020 1150
        2 Poles in series 24/48V [A] 645 760 930 1020 1150
        3 Poles in series

    24/48V [A] 645 760 930 1020 1150
    110V [A] 480 560 630 800 900
    220V [A] 315 400 450 500 600
    Shunt-Wound Motors
    Starting, plugging, reversing, plugging
    DC-3 at 60 °C
             
        3 Poles in series 24/48V [A] 605 800 870 960 1085
    Series-Wound Motors
    Starting, plugging, reversing, plugging
    DC-5 at 60 °C
             
        3 Poles in series 24/48V [A] 605 800 870 960 1085
    Lighting Loads
    Elec. Discharge. Lamps - AC - 5a,
             
        Non-Compensated [A] 450 570 700 850 1000
        Compensated [A] 360 460 550 660 800
    Incandescent Lamps - AC - 5b,
    Electrical Endurance @ 100 000 ops

    [A]

    315

    440

    500

    560

    630
    Switching Power Transformers AC - 6a          
    Inrush = n · Ie [A] 7440 9450 11700 13500 16200
    Ie Rated transformer current [A] 248 315 390 450 540
      n = 30 400V AC [kVA] 172 218 270 312 374
    500V AC [kVA] 215 273 338 390 468
    690V AC [kVA] 269 339 376 538 645
    n = 20   [A] 371 472 580 675 810
    n = 15 [A] 435 630 774 900 1080
    Rated Short-Time Withstand ICW, 60 °C          
        1 s [A] 5500 7000 8000 10000 12000
    4 s [A] 5500 7000 8000 10000 12000
    10 s [A] 4400 5600 6900 8000 9600
    15 s [A] 3800 5000 6000 7400 8500
    60 s [A] 2300 2800 3400 4000 4800
    240 s [A] 1300 1800 2000 2300 2700
    900 s [A] 850 1150 1350 1600 1900
    Minimum cooling time at zero current [Min.] 60 60 60 60 60
    Resistance and Energy Dissipation          
    Main circuit resistance [mW] 0.11 0.1 0.08 0.06 0.05
    Total energy dissipation at Ie AC-3 [W] 99 147 177 180 216
    Excess energy dissipation at Ie AC-3          
      AC Control [W] 110 172 202 250 286
    DC Control [W] 109 169 199 240 276
      

    Mechanical Data

    Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
    Life Span in Millions of Operations          
    Mechanical
    AC Control [Mil.] 5 5 5 1 1
    DC Control [Mil.] 5 5 5 1 1
    Shipping Weights AC Control [kg] 13.8 26.4 28.4 50.3 53.4
      [lb] 30.4 58.1 62.5 110.8 117.6
    DC Control [kg] 13.8 26.4 28.4 50.3 53.4
      [lb] 30.4 58.1 62.5 110.8 117.6
    Terminals⋆           
    Terminal Dimensions [mm] 6 x 40 8 x 50 8 x 50 10 x 50 10 x 60
    Terminal screw hole size [mm] (1) x Æ 13 (1) x Æ 13 (1) x Æ 15 (2) x Æ 13 (2) x Æ 13
    Terminations - Power
    Type
    Hexagonal Bolt
    Direct Connection        
    Click to enlarge - Contactors_2-30-9 b max. [mm] 50 60 60 60 60
    c max. [mm] 20 20 25 25 25
    s max. [mm] 2 x 5 2 x 5 2 x 6 2 x 6 2 x 8
    Æ min. [mm] 12.5 13 15 2 x 13 2 x 13
    Recommended Torque [N•m] 50 60 75 60 60
    [ft.-lb] 37 44 55 44 44
    Conductor/Wire Terminations⋆           
    Bus bar (Width) [mm] 40 50 50 50 60
    Hex screw [in] 1/2 3/8 3/8 3/8 3/8
    Recommended Torque [N•m] 42 62 62 56 56
    [lb•in] 375 550 550 500 500
    Auxiliary Contact [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
    Coils [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
      
    ⋆ Quantity indicated in ( ).

    Coil Data

    Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
    Operating Limits  
    AC- 50 Hz Pick-up [x Us] 0.85…1.1
    Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
    AC- 60 Hz Pick-up [x Us] 0.85…1.1
    Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
    DC Control Pick-up [x Us] 0.85…1.1
    Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
    Pickup and Holding Power      
    AC- 50 Hz Pick-up [VA] 800…950 1350…1600 2400
    Hold-in [VA] 9…11 21…25 70
    AC- 60 Hz Pick-up [VA] 800…950 1350…1600 2400
    Hold-in [VA] 9…11 21…25 70
    DC Control Pick-up [W] 700…850 1300…1550 2100
    Hold-in [W] 8…10 18…22 60
    Operating Times: Switching Delay    
    AC Making delay [ms] 50…100 50…100
    Breaking delay [ms] 20…50‡ /150…200/500…1000§  25…50
    DC Making delay [ms] 50…100 50…100
    Breaking delay [ms] 20…50‡ /150…200/500…1000§  25…50
      
    ‡ Accelerates
    § Delays

    Auxiliary Contacts

    Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
    AC Switching    
    AC-1 Ith at 40 °C [A] 16 16
    at 60 °C [A] 12 12
    AC- 15 at rated voltage 120V [A] 6 6
    230V [A] 3 3
    240V [A] 3 3
    400V [A] 2 2
    415V [A] 2 2
    500V [A] 1.5 1.5
    690V [A] 1 1
    DC Switching
    DC-13 control of electromagnets
    24V DC [A] 6 6
    48V DC [A] 3 3
    110V DC [A] 1 1
    220V DC [A] 0.5 0.5
    Back-up Fuse
    Short-circuit protection without contact welding
    per IEC 60947-5
       
    Fuse gG [A] 10 16
      

    General Data

    Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000…⋆  100-G1200…
    Rated Isolation Voltage Ui    
    IEC, AS, BS, SEV, VDE, 0660
    UL/CSA
    [V]
    1,000V
    600V
    690V
    600V
    Impulse Voltage Uimp    
    1 minute per IEC 947-4 [KV] 8 kV 2,5 kV
    Rated Voltage - Main Control Ue    
    AC 50/60 Hz [V] 230, 240, 400, 415, 460, 500, 575, 690V 230, 240, 400, 415, 460, 500, 575, 690V
    DC [V] 24, 48, 110, 220, 440V
    Operating Frequency for AC Loads
    50/60 Hz
    [Hz] 180/hr. for 0.25s start time - 42/hr. for 1s start time
    Insulation Class of the Magnetic Coil Class B per VDE 0660, table 22
    Rated frequency of the Coil AC 50/60 Hz, DC
    Ambient Temperature  
    Storage -40 °C…+80 °C
    Operation at rated current -25 °C…+70 °C
    Climatic Withstand Damp alternating conditions cyclical, per DIN 50 016 and 40 046, part 38, IEC 60068
    Altitude 2000 m above sea level, per IEC 60947-1
    Type of Protection IP00 IEC 60529/DIN 40 050
    Standards Compliance IEC 60947, UL 508, CSA C22.2, No. 14
    Certifications cULus, CE
      
    ⋆ Cat. No. 100-G1000… is not cULus certified.

    Life-Load Curves

    100-G550…100-G1200

    AC-3 Switching of Running Three-phase Motors, Ue = 380…460V AC
    AC-1 Non or Slightly Inductive Loads, Resistance Furnaces


    Click to enlarge - 100G-119-1


    AC-4 Jogging of Squirrel-cage Motors, Ue = 380…460V AC

    Click to enlarge - 100G-119-2


    Life-Load Curves

    100-G550…100-G1200

    AC-3 90% Switching of Running Motors, Ue = 380…460V AC
    AC-4 10% Jogging


    Click to enlarge - 100G-120-1


    Permissable Switching Rate

    100-G550…100-G1200

    Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
    Starting Time ts = 0.25 s, Relative Running Time 40%


    Click to enlarge - 100G-120-2


    Permissable Switching Rate, Continued

    100-G550…100-G1200

    Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
    Starting Time ts = 1 s, Relative Running Time 40%


    Click to enlarge - 100G-121-1


    100-G550…100-G1200

    Switching of Starting Motors (AC-2, and AC4) Uz = 380…460V AC
    Starting Time ted = 1 s, (<ts)


    Click to enlarge - 100G-121-2

    Bulletin 100-G Approximate Dimensions

    Bulletin 100-G Contactors and Accessories

    Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

    Click to enlarge - 100G_D12


    Mounting Position

    Click to enlarge - 100G_D13


    Cat. No. a b b1 c c1 Æd d1 d2 Æe e1 e2 e3
    100-G550 220 258 228 225 164 9
    220 110 12.5 40 79
    100-G700 280 307 277 291 203 11
    280 175 13 50 101
    100-G860 280 361 325 291 203 11 280 175 15 50 101
    100-G1000 334 490 434 345 231
    13.5
    380 120 2x13 50 100 40
    100-G1200 334
    490 434 345 231 13.5 380 120 2x13 60 100
    40
      

    Contactor with mm
    Auxiliary contact block   a
    Mechanical Interlock side by side 100-G550/100-G550
    100-G700, -860/100-G700, -860
    100-G1000, -1200/100-G1000, -1200
    100-G550/100-G700, -860
    100-G700, -860/100-G1000, -1200
    a+42+a
    a+32+a
    a+46+a
    a+37+a
    a+73+a
    stacked vertically 100-G550/100-G550
    100-G700, -860/100-G700, -860
    100-G1000, -1200/100-G1000, -1200
    100-G550/100-G700, -860
    100-G700, -860/100-G1000, -1200
    b+56 + b
    b/2+380…480+b/2
    b+120…170+b
    b/2+400+b/2
    b/2+570+b/2
    4th add-on neutral switching pole 100-G550
    100-G700, -860
    100-G1000, -1200
    a+74
    a+68
    a+76
    Mechanical latch 100-G550
    100-G700
    100-G860
    b+59
    b+64
    b+37
      

    Renewal Parts

    Bulletin 100-M Replacement Coils⋆ 

    Click to enlarge - 100Line-M-Coil Description Pkg. Qty. Cat. No.
    24V 50/60 Hz 10 MA014
    48V 50/60 Hz 10 MA024
    220V 50/60 Hz 10 MA050
    240V 50/60 Hz 10 MA052
    440V 50 Hz/480V 60 Hz 10 MA082
    12V DC 10 MB708
    24V DC 10 MB714
    60V DC 10 MB734
    125V DC 10 MB746
    24V DC with Diode Suppressor 10 MD714
      
    ⋆ AC and DC coils are not interchangeable.

    Bulletin 100-C Replacement Coils

    Click to enlarge - 100-C_104-C-277-1


    AC Standard Control Voltages [V] AC Coil Code 100-C09…100-C16 100-C23…100-C37, 100L-C20 100-C40, -C43 100-C60…100-C85 100-C90…100-C97
    50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
    12 Q TA006 TC006 TD006 TE006 TF006
    12 R TA404 TC404 TD404 TE404 TF404
    24 J TA013 TC013 TD013 TE013 TF013
    24 K TA407 TC407 TD407 TE407 TF407
    24 KJ TA855 TC855 TD855 TE855 TF855
    32 36 V TA481 TC481 TD481 TE481 TF481
    36 42 W TA410 TC410 TD410 TE410 TF410
    42 48 X TA482 TC482 TD482 TE482 TF482
    48 Y TA414 TC414 TD414 TE414 TF414
    48 KY TA860 TC860 TD860 TE860 TF860
    100 100…110 100 KP TA861 TC861 TD861 TE861 TF861
    110 120 D TA473 TC473 TD473 TE473 TF473
    110 KD TA856 TC856 TD856 TE856 TF856
    120 P TA425 TC425 TD425 TE425 TF425
    127 S TA428 TC428 TD428 TE428 TF428
    200 200…220 200 KG TA862 TC862 TD862 TE862 TF862
    208 H TA049 TC049 TD049 TE049 TF049
    200…220 208…240 L TA296 TC296 TD296 TE296 TF296
    200…230 KL TA864 TC864 TD864 TE864
    220 240 A TA474 TC474 TD474 TE474 TF474
    220…230 260 F TA441 TC441 TD441 TE441 TF441
    230 KF TA851 TC851 TD851 TE851 TF851
    230…240 VA TA440 TC440 TD440 TE440 TF440
    240 277 T TA480 TC480 TD480 TE480 TF480
    240 KA TA858 TC858 TD858 TE858 TF858
    347 I TA065 TC065 TD065 TE065 TF065
    380 E TA067 TC067 TD067 TE067 TF067
    380…400 440 N TA071 TC071 TD071 TE071 TF071
    400 KN TA863 TC863 TD863 TE863 TF863
    400…415 G TA457 TC457 TD457 TE457 TF457
    440 480 B TA475 TC475 TD475 TE475 TF475
    440 KB TA859 TC859 TD859 TE859 TF859
    500 M TA479 TC479 TD479 TE479 TF479
    550 600 C TA476 TC476 TD476 TE476 TF476
      

    Coils, Continued

    Click to enlarge - 100-C_104-C-277-1


    DC Standard Control Voltage [V] DC Coil Code 100-C09…100-C16 100-C23…100-C37, 100L-C20 100-C40, -C43 100-C60…100-C85 100-C90…100-C97
    Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
    9⋆  ZR TA766 TC766 TD766
    9V Diode⋆  DR TE766M TF766M
    12 ZQ TA708 TC708 TD708
    12V Diode DQ TE708M TF708M
    24‡  ZJ TA714 TC714 TD714
    24 Diode‡  DJ TA714M TC714M TD714M TE714M TF714M
    36 ZW TA719 TC719 TD719
    36V Diode DW TE719M TF719M
    48 ZY TA724 TC724 TD724
    48V Diode DY TE724M TF724M
    60 ZZ TA774 TC774 TD774
    60V Diode DZ TE774M TF774M
    64 ZB TA727 TC727 TD727
    64V Diode DB TE727M TF727M
    72 ZG TA728 TC728 TD728
    72V Diode DG TE728M TF728M
    80 ZE TA729 TC729 TD729
    80V Diode DE TE729M TF729M
    110 ZD TA733 TC733 TD733
    110V Diode DD TE733M TF733M
    115 ZP TA734 TC734 TD734
    115V Diode DP TE734M TF734M
    125 ZS TA737 TC737 TD737
    125V Diode DS TE737M TF737M
    220 ZA TA747 TC747 TD747
    220V Diode DA TE747M TF747M
    230 ZF TA749 TC749 TD749
    230V Diode DF TE749F TF749F
    250 ZT TA751 TC751 TD751
    250V Diode DT TE751F TF751F
      
    ⋆ Voltage operating range: 0.65…1.3 x Us.
    ‡ Voltage operating range: 0.7…1.25 x Us.

      Description Coil Type For Use With Cat. No.
    Click to enlarge - 100D-279-1 Arc Chambers for Contactors
    For 3-pole 100-D Contactors
    Conventional 100-D115 100-DA-115
    100-D180 100-DA-180
    Electronic 100-D115 100-DAE-115
    100-D140 100-DAE-140
    100-D180 100-DAE-180
    100-D210 100-DAE-210
    100-D250 100-DAE-250
    100-D300 100-DAE-300
    100-D420 100-DAE-420
    Click to enlarge - 100D-279-2 Main Contacts for Contactors
    3 complete sets for 3-pole 100-D Contactors
    Conventional 100-D115 100-DC-115
    100-D140 100-DC-140
    100-D180 100-DC-180
    Electronic 100-D115 100-DCE-115
    100-D140 100-DCE-140
    100-D180 100-DCE-180
    100-D210 100-DCE-210
    100-D250 100-DCE-250
    100-D300 100-DCE-300
    100-D420 100-DCE-420
    100-D630 100-DCE-630
    100-D860 100-DCE-860
      Terminal Hardware
    Set of 6
    Conventional 100-D115…D180 100-DHF180
    Electronic 100-D115E…D180 100-DHF180
    100-D210…D420 100-DHF420
    100-D630…D860 100-DHF860
      

    Bulletin 100-D Replacement coils

    Click to enlarge - 100D-280-1


    Conventional AC Conventional DC
    AC Standard
    Control Voltages
    AC
    Coil
    Code
    100-D95…D180 100-D210…D420 100-D630…D860 DC Standard
    Control Voltages
    DC
    Coil
    Code
    100-D95…D180 100-D210…D420 100-D630…D860
    50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
    24V K TG407 24V ZJ TG714
    24V J TG013 48V ZY TG724
    48V Y TG414 110V ZD TG733
    42V 48V X TG482 125V ZS TG737
    100V⋆  KP TG861 220V ZA TG761
    110V 120V D TG473  
    110V⋆  KN TG856
    208V H TG049
    200V⋆  KG TG862
    220V⋆  KL TG857
    220…230V 240V A TG441
    240V 277V T TG480
    277V⋆  KT TG060
    230V⋆  KF TG851
    240V⋆  KA TG858
    380…400V 440V N TG071
    415V 480V B TG475
    440V G TG478
    500V M TG479
    550V 600V C TG476
    Electronic AC Electronic DC
    AC Standard
    Control Voltages
    AC
    Coil
    Code
    100-D95…D300 100-D420 100-D630…D860 DC Standard Control Voltage DC
    Coil
    Code
    100-D95…D300 100-D420 100-D630…D860
    50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
    24V EJ‡  TGE855 24V EZJ TGE708
    42…64V EY TGE864 48…72V EZY TGE779
    100V EP TGE861 THE861 TJE861 110…130V EZD TGE780 THE780
    110…130V ED TGE865 THE865 TJE865 ED TJE865
    200V EG TGE862 THE862 200…255V EZA TGE781 THE781
    208…277V EA TGE866 THE866 EA TJE879
    200…220V EG TJE878  
    230…250V EA TJE879
    277V ET TJE880
    380…500V EN TGE867 THE867
    380…415V EN TJE867
    440…480V EB TJE868
    500V EM TJE869
      
    ⋆ Applies to 100-D95…-D115 contactors only. Not available with 100-D140…-D180 contactors.
    ‡ Not available on 100/104-D300.

    Bulletin 100-G Renewal Parts

      Description For Use With Cat. No.
    Click to enlarge - 100G-95-1 Arcing Chamber
    For 3 poles
    100-G550 100-AC550
    100-G700, 100-G860 100-AC860
    Click to enlarge - 100G-95-3 Main Contact Set
    Set for 1 pole
    100-G550 100-CP550
    100-G700 100-CP700
    100-G860 100-CP860
    100-G1000 100-CP1000
    100-G1200 100-CP1200
    Click to enlarge - 100G-95-4 Auxiliary Contact Block
    Special 2-pole design: 1 N.O. delayed make, 1 N.C. contact
    N.O. delayed make contact used for operation of the Feeder/Group Coil mechanism
    One contact block supplied standard with contactor
    Click to enlarge - 100G-95-5 100-G1000, 100-G1200 100-EB11DC
      

    Coils and Supply Modules

    Click to enlarge - 100G-95-6 Click to enlarge - 100G-95-7

    AC Standard
    Control
    Voltages
    DC Standard Control Voltage Coil Code 100-G550 100-G700...100-G860
    50/60 Hz
    110…120V 100…110V KD TX734 TXS734 TY734 TYS734
    220…240V 200…220V KF TX747 TXS747 TY747 TYS747
    380…415V 345…380V KN TX779 TXS779 TY779 TYS779
    440…480V 400…440V KB TX780 TXS780 TY780 TYS780
      
    ⋆ Coils sold in pairs.

    AC Standard
    Control
    Voltages
    Coil Code 100-G1000...100-G1200
    Coil Cat. No.⋆  Supply Module Cat. No.
    50/60 Hz
    110…115V KD TZ734 TZS734
    220…230V KF TZ747 TZS747
    380…400V KN TZ779 TZS779
    440V KB TZ780 TZS780