Bulletin 100-G IEC Contactors

Click to enlarge - 100-G_GS


Bulletin 100-G IEC Contactors


Your order must include: cat. no. of the contactor selected, coil voltage code, overload relay suffix code, and, if required, cat. no. of any accessories.

The Bulletin 100-G contactor product family provides reliable switching of motor loads up to 1200 A. A complete range of accessories including auxiliary contacts, mechanical latches, horizontal and vertical interlocks, and 4th add-on neutral switching poles provides maximum flexibility to meet a wide variety of application requirements.

Standards Compliance and Certifications

Standards Compliance

EN/IEC 60947-4-1
IEC 60947 Type “1” Coordination
CSA C22.2 No. 14
UL 508


Certifications

CE Marked
cULus Listed (File No. E 3125, Guide NLDX, NLDX7)


Product Selection

AC and DC Control

AC-1 Switching of 3-phase motors—AC-2, AC-3 3-Phase AC-2, AC-3 kW Rating (50 Hz), 400V Auxiliary Contacts   Cat. No.
Ie [A] kW (50 Hz)‡  Hp (60 Hz) kW (50 Hz) Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a  
40 °C 230V 400V 500V 690V 200V 230V 460V 575V 400V N.O. N.C.  
760 160 315 400 500 150 150 350 350 315 2 2   100-G550Ä22
1000 220 400 500 630 200 250 500 500 400 2 2   100-G700Ä22
1100 280 500 630 710 250 300 600 600 500 2 2   100-G860Ä22
1200 315 560 750 850 560 2¬  2 T  T  100-G1000Ä12
1350 375 710 850 1000 450 450 900 900 710 2¬  2   100-G1200Ä12
  
Package Quantity = 1
Discount Group PRO
¬ 1 N.O. contact used in control circuit.
T No UL/cUL
‡ Preferred value according to IEC 60072-1.

Ä Coil Voltage Code

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 50/60Hz:
Cat. No. 100-G550Ä22 becomes Cat. No.100-G550KD22.


For Use With: [V] 100…110 110…120 200…220 220…240 345…380 380…415 400…440 440…480
100-G550...100-G860 50/60 Hz KD KF KN KB
DC KD KF KN KB
  

For Use With: [V] 110…115 110 220…230 220 240 380…400 440 480V
100-G1000...100-G1200 50/60 Hz KD KF KA KN KB KU
DC ZD ZA
  

Price Adder For Type Available Control Voltages No Surcharge
Special control voltages 100-G550…100-G860 24…600V 50/60 Hz, 24…440V DC >25 pieces
100-G1000…100-G1200 48…600V 50/60 Hz, 48…440V DC
  

Bulletin 100-G Accessories

Control Modules

  Description For Use With Cat. No.
Click to enlarge - 100-EF22_GS Auxiliary Contact Block
For mounting between T1 & T2 or between T2 & T3
Adjustable; provides normal, delayed, or overlapping contacts
Max. two blocks/contactor
Alternate terminal marking tags included
2 N.O. and 2 N.C. contacts
Click to enlarge - 100G-94-2 100-G550…100-G860 100-EF22
Standard Terminal marking for mounting between T1 & T2
Click to enlarge - 100G-94-3
Alternate terminal marking for mounting between T2 & T3
4-Pole
Click to enlarge - 100-EB_GS Auxiliary Contact Block
For side mounting on either side of the contactor
Max. four blocks/contactor
Alternate terminal marking tags included
1 N.O. and 1 N.C. contact
Click to enlarge - 100G-94-5 100-G1000…100-G1200 100-EB11
Standard terminal marking
Click to enlarge - 100G-94-6 Click to enlarge - 100G-94-7
Alternate terminal markings
2-Pole
Click to enlarge - 100-NP_GS Fourth Add-On Neutral Switching Pole
Left- or right-side mountable
Note: no UL/cUL
Ith AC-1 500 A 100-G550 100-NP500-5
100-G700, 100-G860 100-NP500-6
Ith AC-1 1000A 100-G700, 100-G860 100-NP1000-6
100-G1000, 100-G1200 100-NP1000-7
Click to enlarge - 100-FLAM_GS Mechanical Latch
Mechanical life: 0.5 million operations
Direct and Impulse Control
Direct and Impulse Contact control 100-G550 100-FLAM5Ä
Direct and Impulse Contact control 100-G700, 100-G860 100-FLAM6Ä
Click to enlarge - 100-MCH00_GS Mechanical Interlock — Horizontal 100-G550 to 100-G550 100-MC00-5H
100-G550 to 100-G700 or 100-G860 100-MC00-56H
100-G700 or 100-G860 to 100-G700 or 100-G860 100-MC00-6H
100-G700 or 100-G860 to 100-G1000 or 100-G1200 100-MC00-67H
100-G1000 or 100-G1200 to 100-G1000 or 100-G1200 100-MC00-7H
Click to enlarge - 100-MCV00_GS Mechanical Interlock — Vertical 100-G550 to 100-G550 100-MC00-5V
100-G550 to 100-G700 or 100-G860 100-MC00-56V
100-G700 or 100-G860 to 100-G700 or 100-G860 100-MC00-6V
100-G700 or 100-G860 to 100-G1000 or 100-G1200 100-MC00-67V
100-G1000 or 100-G1200 to 100-G1000 or 100-G1200 100-MC00-7V
  
Package Quantity = 1

Ä Coil Voltage Codes¬ 

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 100-FLAM5Ä becomes Cat. No.100-FLAM5KD.

For use with [V] 110...120 220...240 380...415 440...480
100-G550... 100-G860 50-60 Hz KD KF KN KB
  
¬ For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Bulletin 100-G Specifications

Electrical Data

Cat. No. 100-G550... 100-G700... 100-G860... 100-G1000 100-G1200
AC-1, Three-phase Switching - IEC
Ambient temperature: 40 °C
         
        Ie £ 690V [A] 760 1000 1100 1200 1350
230V [kW] 303 398 438 478 538
240V [kW] 316 416 457 499 561
400V [kW] 527 693 762 831 935
415V [kW] 546 719 791 863 970
500V [kW] 658 866 953 1039 1169
690V [kW] 908 1195 1315 1434 1613
Ambient temperature: 60 °C          
        Ie £ 690V [A] 605 800 870 960 1,085
230V [kW] 241 319 347 382 432
240V [kW] 251 333 362 399 451
400V [kW] 419 554 603 665 752
415V [kW] 435 575 625 690 780
500V [kW] 524 693 753 831 940
690V [kW] 723 956 1040 1147 1297
Continuous Current - UL/CSA
General Purpose Rating 40 °C
[A] 520 700 810 1215
Switching of 3-phase Motors - IEC          
AC-2, AC-3   230/240V [A] 550 700 860 1000 1200
50 Hz/60 °C 400/415V [A] 550 700 860 1000 1200
500V [A] 550 700 860 1000 1200
690V [A] 500 630 700 860 1000
230V [kW] 179 228 280 326 391
240V [kW] 187 238 293 340 408
400V [kW] 312 414 509 592 710
415V [kW] 324 430 528 628 737
500V [kW] 407 518 636 756 888
690V [kW] 510 657 730 897 1043
AC-4 at 200000 operations          
50 Hz   230/240V [A] 140 180 210 260 300
400/415V [A] 140 180 210 260 300
230V [kW] 45 57 67 83 97
240V [kW] 47 60 70 87 101
400V [kW] 78 101 118 146 170
415V [kW] 81 105 122 151 176
AC-4, Squirrel-cage motors with reversing and
jogging at 20,000 (25,000), operations
         
    230/240V [A] 360 430 520 (630) (700)
400/415V¬  [A] 350 420 520 (630) (700)
230V [kW] 116 139 170 (205) (228)
240V [kW] 120 151 177 (214) (245)
400V [kW] 198 238 295 (357) (414)
415V [kW] 206 247 300 (359) (424)
  
¬ At rated Voltage 415V and rated current: Life span - 25%.

Cat. No. 100-G550 100-G700 100-G860 100-G1000... 100-G1200...
Switching of 3-phase Motors - UL/CSA          
60 Hz/60 °C 200V [A] 414 552 692 1185
230V [A] 360 602 722 1130
460V [A] 414 590 708 1062
575V [A] 336 472 576 864
200V [Hp] 150 200 250 450
230V [Hp] 150 250 300 450
460V [Hp] 350 500 600 900
575V [Hp] 350 500 600 900
Rated making capacity          
AC-3 Ie £ 415V [A] 5500 7000 8600 10000 12000
500V [A] 5500 7000 8600 10000 12000
690V [A] 5500 7000 8600 10000 12000
Rated Breaking capacity          
AC-3 Ie £ 240V [A] 4400 5600 6900 8000 9600
400V [A] 4400 5600 6900 8000 9600
415V [A] 4400 5600 6900 8000 9600
500V [A] 4400 5600 6900 8000 9600
690V [A] 4000 5100 5600 6900 8000
Star-Delta Staring          
50 Hz 230V [A] 953 1212 1490 1732 2078
240V [A] 953 1212 1490 1732 2078
400V [A] 953 1212 1490 1732 2078
415V [A] 953 1212 1490 1732 2078
500V [A] 953 1212 1490 1732 2078
690V [A] 831 1091 1195 1490 1732
230V [kW] 310 395 485 565 677
240V [kW] 324 412 507 589 707
400V [kW] 540 717 882 1025 1250
415V [kW] 561 745 915 1088 1278
500V [kW] 705 897 1102 1309 1538
690V [kW] 883 1138 1247 1554 2078
Wye-Delta Starting          
60 Hz 230V [Hp] 250 400 500 650 750
460V [Hp] 600 800 1000 1300 1500
575V [Hp] 600 800 1000 1500 1500
Short-circuit Protection of Contactors without
Overload Relay
         
Fuse gG (aM) Type 1 coordination
(per IEC 60947-4-1)
  500V [A] (630) 800 1000 1000 1250
690V [A] (630) 800 1000 1000 1000
Switching of Three-phase Capacitor
Inductivity of dispatching between parallel switched capacitor: min. 6 pH
Single capacitors 40 °C   230V [kVar] 180 220 250 290 330
240V [kVar] 200 250 300 325 360
400V [kVar] 320 400 450 500 575
415V [kVar] 350 430 500 550 630
500V [kVar] 450 520 600 660 750
690V [kVar] 580 700 800 875 1000
55 °C 230V [kVar] 150 180 220 275 325
240V [kVar] 170 200 260 300 350
400V [kVar] 280 330 400 460 550
415V [kVar] 300 360 450 500 600
500V [kVar] 360 420 540 600 720
690V [kVar] 500 580 720 800 950
  

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Capacitor Banks




40 °C




230V [kVar] 180 220 250 290 330
240V [kVar] 200 250 300 325 360
400V [kVar] 320 400 450 500 575
415V [kVar] 350 430 500 550 430
500V [kVar] 450 520 600 660 750
690V [kVar] 580 700 800 875 1000
55 °C




230V [kVar] 150 180 220 275 325
240V [kVar] 170 200 260 300 350
400V [kVar] 280 330 400 460 550
415V [kVar] 300 360 450 500 600
500V [kVar] 360 420 540 600 720
690V [kVar] 500 580 720 800 950
DC Switching
Switching of non- or slightly inductive loads, resistance furnaces
DC-1 at 60 °C
         
    1 Pole 24/48V [A] 645 760 930 1020 1150
    2 Poles in series 24/48V [A] 645 760 930 1020 1150
    3 Poles in series

24/48V [A] 645 760 930 1020 1150
110V [A] 480 560 630 800 900
220V [A] 315 400 450 500 600
Shunt-Wound Motors
Starting, plugging, reversing, plugging
DC-3 at 60 °C
         
    3 Poles in series 24/48V [A] 605 800 870 960 1085
Series-Wound Motors
Starting, plugging, reversing, plugging
DC-5 at 60 °C
         
    3 Poles in series 24/48V [A] 605 800 870 960 1085
Lighting Loads
Elec. Discharge. Lamps - AC - 5a,
         
    Non-Compensated [A] 450 570 700 850 1000
    Compensated [A] 360 460 550 660 800
Incandescent Lamps - AC - 5b,
Electrical Endurance @ 100 000 ops

[A]

315

440

500

560

630
Switching Power Transformers AC - 6a          
Inrush = n · Ie [A] 7440 9450 11700 13500 16200
Ie Rated transformer current [A] 248 315 390 450 540
  n = 30 400V AC [kVA] 172 218 270 312 374
500V AC [kVA] 215 273 338 390 468
690V AC [kVA] 269 339 376 538 645
n = 20   [A] 371 472 580 675 810
n = 15 [A] 435 630 774 900 1080
Rated Short-Time Withstand ICW, 60 °C          
    1 s [A] 5500 7000 8000 10000 12000
4 s [A] 5500 7000 8000 10000 12000
10 s [A] 4400 5600 6900 8000 9600
15 s [A] 3800 5000 6000 7400 8500
60 s [A] 2300 2800 3400 4000 4800
240 s [A] 1300 1800 2000 2300 2700
900 s [A] 850 1150 1350 1600 1900
Minimum cooling time at zero current [Min.] 60 60 60 60 60
Resistance and Energy Dissipation          
Main circuit resistance [mW] 0.11 0.1 0.08 0.06 0.05
Total energy dissipation at Ie AC-3 [W] 99 147 177 180 216
Excess energy dissipation at Ie AC-3          
  AC Control [W] 110 172 202 250 286
DC Control [W] 109 169 199 240 276
  

Mechanical Data

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Life Span in Millions of Operations          
Mechanical
AC Control [Mil.] 5 5 5 1 1
DC Control [Mil.] 5 5 5 1 1
Shipping Weights AC Control [kg] 13.8 26.4 28.4 50.3 53.4
  [lb] 30.4 58.1 62.5 110.8 117.6
DC Control [kg] 13.8 26.4 28.4 50.3 53.4
  [lb] 30.4 58.1 62.5 110.8 117.6
Terminals¬           
Terminal Dimensions [mm] 6 x 40 8 x 50 8 x 50 10 x 50 10 x 60
Terminal screw hole size [mm] (1) x Æ 13 (1) x Æ 13 (1) x Æ 15 (2) x Æ 13 (2) x Æ 13
Terminations - Power
Type
Hexagonal Bolt
Direct Connection        
Click to enlarge - Contactors_2-30-9 b max. [mm] 50 60 60 60 60
c max. [mm] 20 20 25 25 25
s max. [mm] 2 x 5 2 x 5 2 x 6 2 x 6 2 x 8
Æ min. [mm] 12.5 13 15 2 x 13 2 x 13
Recommended Torque [N•m] 50 60 75 60 60
[ft.-lb] 37 44 55 44 44
Conductor/Wire Terminations¬           
Bus bar (Width) [mm] 40 50 50 50 60
Hex screw [in] 1/2 3/8 3/8 3/8 3/8
Recommended Torque [N•m] 42 62 62 56 56
[lb•in] 375 550 550 500 500
Auxiliary Contact [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
Coils [mm2] (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5 (2) x 2.5
  
¬ Quantity indicated in ( ).

Coil Data

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
Operating Limits  
AC- 50 Hz Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
AC- 60 Hz Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
DC Control Pick-up [x Us] 0.85…1.1
Drop-out [x Us] 0.2…0.5 0.2…0.75 0.1…0.6
Pickup and Holding Power      
AC- 50 Hz Pick-up [VA] 800…950 1350…1600 2400
Hold-in [VA] 9…11 21…25 70
AC- 60 Hz Pick-up [VA] 800…950 1350…1600 2400
Hold-in [VA] 9…11 21…25 70
DC Control Pick-up [W] 700…850 1300…1550 2100
Hold-in [W] 8…10 18…22 60
Operating Times: Switching Delay    
AC Making delay [ms] 50…100 50…100
Breaking delay [ms] 20…50T /150…200/500…1000‡  25…50
DC Making delay [ms] 50…100 50…100
Breaking delay [ms] 20…50T /150…200/500…1000‡  25…50
  
T Accelerates
‡ Delays

Auxiliary Contacts

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000… 100-G1200…
AC Switching    
AC-1 Ith at 40 °C [A] 16 16
at 60 °C [A] 12 12
AC- 15 at rated voltage 120V [A] 6 6
230V [A] 3 3
240V [A] 3 3
400V [A] 2 2
415V [A] 2 2
500V [A] 1.5 1.5
690V [A] 1 1
DC Switching
DC-13 control of electromagnets
24V DC [A] 6 6
48V DC [A] 3 3
110V DC [A] 1 1
220V DC [A] 0.5 0.5
Back-up Fuse
Short-circuit protection without contact welding
per IEC 60947-5
   
Fuse gG [A] 10 16
  

General Data

Cat. No. 100-G550… 100-G700… 100-G860… 100-G1000…¬  100-G1200…
Rated Isolation Voltage Ui    
IEC, AS, BS, SEV, VDE, 0660
UL/CSA
[V]
1,000V
600V
690V
600V
Impulse Voltage Uimp    
1 minute per IEC 947-4 [KV] 8 kV 2,5 kV
Rated Voltage - Main Control Ue    
AC 50/60 Hz [V] 230, 240, 400, 415, 460, 500, 575, 690V 230, 240, 400, 415, 460, 500, 575, 690V
DC [V] 24, 48, 110, 220, 440V
Operating Frequency for AC Loads
50/60 Hz
[Hz] 180/hr. for 0.25s start time - 42/hr. for 1s start time
Insulation Class of the Magnetic Coil Class B per VDE 0660, table 22
Rated frequency of the Coil AC 50/60 Hz, DC
Ambient Temperature  
Storage -40 °C…+80 °C
Operation at rated current -25 °C…+70 °C
Climatic Withstand Damp alternating conditions cyclical, per DIN 50 016 and 40 046, part 38, IEC 60068
Altitude 2000 m above sea level, per IEC 60947-1
Type of Protection IP00 IEC 60529/DIN 40 050
Standards Compliance IEC 60947, UL 508, CSA C22.2, No. 14
Certifications cULus, CE
  
¬ Cat. No. 100-G1000… is not cULus certified.

Life-Load Curves

100-G550…100-G1200

AC-3 Switching of Running Three-phase Motors, Ue = 380…460V AC
AC-1 Non or Slightly Inductive Loads, Resistance Furnaces


Click to enlarge - 100G-119-1


AC-4 Jogging of Squirrel-cage Motors, Ue = 380…460V AC

Click to enlarge - 100G-119-2


Life-Load Curves, Continued

100-G550…100-G1200

AC-3 90% Switching of Running Motors, Ue = 380…460V AC
AC-4 10% Jogging


Click to enlarge - 100G-120-1


Permissable Switching Rate

100-G550…100-G1200

Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 0.25 s, Relative Running Time 40%


Click to enlarge - 100G-120-2


Permissable Switching Rate, Continued

100-G550…100-G1200

Switching of Running Squirrel-cage Motors AC-3, Ue = 380…460V AC
Starting Time ts = 1 s, Relative Running Time 40%


Click to enlarge - 100G-121-1


100-G550…100-G1200

Switching of Starting Motors (AC-2, and AC4) Uz = 380…460V AC
Starting Time ted = 1 s, (<ts)


Click to enlarge - 100G-121-2

Bulletin 100-G Approximate Dimensions

Bulletin 100-G Contactors and Accessories

Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Click to enlarge - 100G_D12


Mounting Position

Click to enlarge - 100G_D13


Cat. No. a b b1 c c1 Æd d1 d2 Æe e1 e2 e3
100-G550 220 258 228 225 164 9
220 110 12.5 40 79
100-G700 280 307 277 291 203 11
280 175 13 50 101
100-G860 280 361 325 291 203 11 280 175 15 50 101
100-G1000 334 490 434 345 231
13.5
380 120 2x13 50 100 40
100-G1200 334
490 434 345 231 13.5 380 120 2x13 60 100
40
  

Contactor with mm
Auxiliary contact block   a
Mechanical Interlock side by side 100-G550/100-G550
100-G700, -860/100-G700, -860
100-G1000, -1200/100-G1000, -1200
100-G550/100-G700, -860
100-G700, -860/100-G1000, -1200
a+42+a
a+32+a
a+46+a
a+37+a
a+73+a
stacked vertically 100-G550/100-G550
100-G700, -860/100-G700, -860
100-G1000, -1200/100-G1000, -1200
100-G550/100-G700, -860
100-G700, -860/100-G1000, -1200
b+56 + b
b/2+380…480+b/2
b+120…170+b
b/2+400+b/2
b/2+570+b/2
4th add-on neutral switching pole 100-G550
100-G700, -860
100-G1000, -1200
a+74
a+68
a+76
Mechanical latch 100-G550
100-G700
100-G860
b+59
b+64
b+37
  

Renewal Parts

Bulletin 100-M Replacement Coils¬ 

Click to enlarge - 100Line-M-Coil Description Pkg. Qty. Cat. No.
24V 50/60 Hz 10 MA014
48V 50/60 Hz 10 MA024
110V 50 Hz/110…120V 60 Hz 10 MA034
220V 50/60 Hz 10 MA050
240V 50/60 Hz 10 MA052
380V 50/60 Hz 10 MA062
440V 50 Hz/480V 60 Hz 10 MA082
12V DC 10 MB708
18V DC 10 MB710
24V DC 10 MB714
48V DC 10 MB724
60V DC 10 MB734
110V DC 10 MB744
125V DC 10 MB746
220V DC 10 MB766
24V DC with Diode Suppressor 10 MD714
  
¬ AC and DC coils are not interchangeable.

Bulletin 100-C Replacement Coils

Click to enlarge - 100-C_104-C-277-1


AC Standard Control Voltages [V] AC Coil Code 100-C09…100-C16 100-C23…100-C37, 100L-C20 100-C40, -C43 100-C60…100-C85 100-C90
50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
12 Q TA006 TC006 TD006 TE006 TF006
12 R TA404 TC404 TD404 TE404 TF404
24 J TA013 TC013 TD013 TE013 TF013
24 K TA407 TC407 TD407 TE407 TF407
24 KJ TA855 TC855 TD855 TE855 TF855
32 36 V TA481 TC481 TD481 TE481 TF481
36 W TA410 TC410 TD410 TE410 TF410
42 48 X TA482 TC482 TD482 TE482 TF482
48 Y TA414 TC414 TD414 TE414 TF414
48 KY TA860 TC860 TD860 TE860 TF860
100 100…110 100 KP TA861 TC861 TD861 TE861 TF861
110 120 D TA473 TC473 TD473 TE473 TF473
110 KD TA856 TC856 TD856 TE856 TF856
120 P TA425 TC425 TD425 TE425 TF425
127 S TA428 TC428 TD428 TE428 TF428
200 200…220 200 KG TA862 TC862 TD862 TE862 TF862
208 H TA049 TC049 TD049 TE049 TF049
200…220 208…240 L TA296 TC296 TD296 TE296 TF296
200…230 KL TA864 TC864 TD864 TE864
220 240 A TA474 TC474 TD474 TE474 TF474
220…230 260 F TA441 TC441 TD441 TE441 TF441
230 KF TA851 TC851 TD851 TE851 TF851
230…240 VA TA440 TC440 TD440 TE440 TF440
240 277 T TA480 TC480 TD480 TE480 TF480
240 KA TA858 TC858 TD858 TE858 TF858
347 I TA065 TC065 TD065 TE065 TF065
380 E TA067 TC067 TD067 TE067 TF067
380…400 440 N TA071 TC071 TD071 TE071 TF071
400 KN TA863 TC863 TD863 TE863 TF863
400…415 G TA457 TC457 TD457 TE457 TF457
440 480 B TA475 TC475 TD475 TE475 TF475
440 KB TA859 TC859 TD859 TE859 TF859
500 M TA479 TC479 TD479 TE479 TF479
550 600 C TA476 TC476 TD476 TE476 TF476
  

Coils, Continued

Click to enlarge - 100-C_104-C-277-1


DC Standard Control Voltage [V] DC Coil Code 100-C09…100-C16 100-C23…100-C37, 100L-C20 100-C40, -C43 100-C60…100-C85 100-C90
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
9¬  ZR TA766 TC766 TD766
9V Diode¬  DR TE766M TF766M
12 ZQ TA708 TC708 TD708
12V Diode DQ TE708M TF708M
24T  ZJ TA714 TC714 TD714
24 DiodeT  DJ TA714M TC714M TD714M TE714M TF714M
36 ZW TA719 TC719 TD719
36V Diode DW TE719M TF719M
48 ZY TA724 TC724 TD724
48V Diode DY TE724M TF724M
60 ZZ TA774 TC774 TD774
60V Diode DZ TE774M TF774M
64 ZB TA727 TC727 TD727
64V Diode DB TE727M TF727M
72 ZG TA728 TC728 TD728
72V Diode DG TE728M TF728M
80 ZE TA729 TC729 TD729
80V Diode DE TE729M TF729M
110 ZD TA733 TC733 TD733
110V Diode DD TE733M TF733M
115 ZP TA734 TC734 TD734
115V Diode DP TE734M TF734M
125 ZS TA737 TC737 TD737
125V Diode DS TE737M TF737M
220 ZA TA747 TC747 TD747
220V Diode DA TE747M TF747M
230 ZF TA749 TC749 TD749
230V Diode DF TE749F TF749F
250 ZT TA751 TC751 TD751
250V Diode DT TE751F TF751F
  
¬ Voltage operating range: 0.65…1.3 x Us.
T Voltage operating range: 0.7…1.25 x Us.

Bulletin 190 IEC Modular Starter System

AC Operating Coils
Used with Cat. Nos. 190-A40, 190-CPS40, and 190R-CPS40
Voltage [V] Frequency [Hz] Cat. No.
24 50 JB407
24 60 JB013
110 50 JB473
120 60 JB473
208 60 JB049
220 50 JB474
240 60 JB474
380 50 JB454
415 50 JB457
440 50 JB475
480 60 JB475
550 50 JB476
600 60 JB476
  

Bulletin 193 Overload Relays with Current Transformers

For Use
With
Panel Adapter Assembly
Cat. No.
Overload Relay Only
Cat. No.
193-HPD110 40781-607-01 193-NX23
193-DPC88 40781-607-01 193-NX24
193-DPD120 40781-607-01 193-NX25
193-DPD200 40781-607-01 193-NX26
193-EPD180 40781-607-01 193-NX27
193-EPD300 40781-607-01 193-NX28
193-FPD240 40781-607-01 193-NX29
193-FPD40 40781-607-01 193-NX30
193-GPD378¬  40781-607-01 193-NX32
193-GPD630¬  40781-607-01 193-NX33
  
¬ Contact kits for Cat. Nos. 100-A09…100-A30 are not available as replacement parts.

AC Operating Coils
Used with 193-GPD Devices
Voltage Frequency [Hz] Cat. No.
24V AC 50 HA407
24V AC 60 HA013
110V AC 50 HA473
110 V AC 60
120 V AC 50
120V AC 60 HA473
208 V AC 50
208V AC 60 HA049
220V AC 50 HA474
220V AC 60 HA051
240V AC 50 HA442
240V AC 60 HA474
277V AC 60 HA060
380V AC 50 HA454
380 V AC 60
415V AC 50 HA457
440V AC 50 HA475
440V AC 60 HA071
480 V AC 50
480V AC 60 HA475
500V AC 50 HA464
500 V AC 60
600V AC 60 HA476
  

  Description Coil Type For Use With Cat. No.
Click to enlarge - 100D-279-1 Arc Chambers for Contactors
For 3-pole 100-D Contactors
Conventional 100-D95 100-DA-95
100-D110 100-DA-110
100-D140 100-DA-140
100-D180 100-DA-180
Electronic 100-D95 100-DAE-95
100-D110 100-DAE-110
100-D140 100-DAE-140
100-D180 100-DAE-180
100-D210 100-DAE-210
100-D250 100-DAE-250
100-D300 100-DAE-300
100-D420 100-DAE-420
Click to enlarge - 100D-279-2 Main Contacts for Contactors
3 complete sets for 3-pole 100-D Contactors
Conventional 100-D95 100-DC-95
100-D110 100-DC-110
100-D140 100-DC-140
100-D180 100-DC-180
Electronic 100-D95 100-DCE-95
100-D110 100-DCE-110
100-D140 100-DCE-140
100-D180 100-DCE-180
100-D210 100-DCE-210
100-D250 100-DCE-250
100-D300 100-DCE-300
100-D420 100-DCE-420
100-D630 100-DCE-630
100-D860 100-DCE-860
  Terminal Hardware
Set of 6
Conventional 100-D95…D110 100-DHF110
100-D140…D180 100-DHF180
Electronic 100-D95…D180 100-DHF180
100-D210…D420 100-DHF420
100-D630…D860 100-DHF860
  

Bulletin 100-D Replacement coils

Click to enlarge - 100D-280-1


Conventional AC Conventional DC
AC Standard
Control Voltages
AC
Coil
Code
100-D95…D180 100-D210…D420 100-D630…D860 DC Standard
Control Voltages
DC
Coil
Code
100-D95…D180 100-D210…D420 100-D630…D860
50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
24V K TG407 12V ZQ TG708
24V J TG013 24V ZJ TG714
32V 36V V TG481 36V ZW TG719
36V 42V W TG410 48V ZY TG724
48V Y TG414 60V ZZ TG774
42V 48V X TG482 110V ZD TG733
100V¬  KP TG861 125V ZS TG737
110V 120V D TG473 130V ZF TG738
110V¬  KN TG856 220V ZA TG761
208V H TG049 240V ZL TG750
200V¬  KG TG862 250V ZT TG751
220V¬  KL TG857  
220…230V 240V A TG441
240V 277V T TG480
277V¬  KT TG060
230V¬  KF TG851
240V¬  KA TG858
380…400V 440V N TG071
415V 480V B TG475
440V G TG478
500V M TG479
550V 600V C TG476
Electronic AC Electronic DC
AC Standard
Control Voltages
AC
Coil
Code
100-D95…D300 100-D420 100-D630…D860 DC Standard Control Voltage DC
Coil
Code
100-D95…D300 100-D420 100-D630…D860
50 Hz 60 Hz 50/60 Hz Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
24V EJT  TGE855 24V EZJ TGE708
42…64V EY TGE864 48…72V EZY TGE779
100V EP TGE861 THE861 TJE861 110…130V EZD TGE780 THE780
110…130V ED TGE865 THE865 TJE865 ED TJE865
200V EG TGE862 THE862 200…255V EZA TGE781 THE781
208…277V EA TGE866 THE866 EA TJE879
200…220V EG TJE878  
230…250V EA TJE879
277V ET TJE880
380…500V EN TGE867 THE867
380…415V EN TJE867
440…480V EB TJE868
500V EM TJE869
  
¬ Applies to 100-D95…-D110 contactors only. Not available with 100-D140…-D180 contactors.
T Not available on 100/104-D300.

Bulletin 100-G Renewal Parts

  Description For Use With Cat. No.
Click to enlarge - 100G-95-1 Arcing Chamber
For 3 poles
100-G550 100-AC550
100-G700, 100-G860 100-AC860
Click to enlarge - 100G-95-2 Arcing Chamber
For 1 pole
100-G1000, 100-G1200 100-AC1200
Click to enlarge - 100G-95-3 Main Contact Set
Set for 1 pole
100-G550 100-CP550
100-G700 100-CP700
100-G860 100-CP860
100-G1000 100-CP1000
100-G1200 100-CP1200
Click to enlarge - 100G-95-4 Auxiliary Contact Block
Special 2-pole design: 1 N.O. delayed make, 1 N.C. contact
N.O. delayed make contact used for operation of the Feeder/Group Coil mechanism
One contact block supplied standard with contactor
Click to enlarge - 100G-95-5 100-G1000, 100-G1200 100-EB11DC
  

Coils and Supply Modules

Click to enlarge - 100G-95-6 Click to enlarge - 100G-95-7

AC Standard
Control
Voltages
DC Standard Control Voltage Coil Code 100-G550 100-G700...100-G860
50/60 Hz
110…120V 100…110V KD TX734 TXS734 TY734 TYS734
220…240V 200…220V KF TX747 TXS747 TY747 TYS747
380…415V 345…380V KN TX779 TXS779 TY779 TYS779
440…480V 400…440V KB TX780 TXS780 TY780 TYS780
  
¬ Coils sold in pairs.

AC Standard
Control
Voltages
Coil Code 100-G1000...100-G1200
Coil Cat. No.¬  Supply Module Cat. No.
50/60 Hz
110…115V KD TZ734 TZS734
220…230V KF TZ747 TZS747
380…400V KN TZ779 TZS779
440V KB TZ780 TZS780