Contactors

Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Bulletin 100-G IEC Contactors

Bulletin 100-G IEC Contactors

Introduction Standards Compliance and Certifications Product Selection Bulletin 100-G Accessories Bulletin 100-G Specifications Bulletin 100-G Approximate Dimensions Renewal Parts
Bulletin 100-G Accessories

Control Modules

  Description For Use With Cat. No.
Click to enlarge - 100-EF22_GS Auxiliary Contact Block
  • For mounting between T1 & T2 or between T2 & T3

  • Adjustable; provides normal, delayed, or overlapping contacts

  • Max. two blocks/contactor

  • Alternate terminal marking tags included

  • 2 N.O. and 2 N.C. contacts
  • Click to enlarge - 100G-94-2 100-G550…100-G860 100-EF22
    Standard Terminal marking for mounting between T1 & T2
    Click to enlarge - 100G-94-3
    Alternate terminal marking for mounting between T2 & T3
    4-Pole
    Click to enlarge - 100-EB_GS Auxiliary Contact Block
  • For side mounting on either side of the contactor

  • Max. four blocks/contactor

  • Alternate terminal marking tags included

  • 1 N.O. and 1 N.C. contact
  • Click to enlarge - 100G-94-5 100-G1000…100-G1200 100-EB11
    Standard terminal marking
    Click to enlarge - 100G-94-6 Click to enlarge - 100G-94-7
    Alternate terminal markings
    2-Pole
    Click to enlarge - 100-NP_GS Fourth Add-On Neutral Switching Pole
  • Left- or right-side mountable

  • Note: no UL/cUL
  • Ith AC-1 500 A 100-G550 100-NP800-5
    100-G700, 100-G860 100-NP500-6
    Ith AC-1 1000A 100-G700, 100-G860 100-NP1000-6
    100-G1000, 100-G1200 100-NP1000-7
    Click to enlarge - 100-FLAM_GS Mechanical Latch
  • Mechanical life: 0.5 million operations

  • Direct and Impulse Control
  • Direct and Impulse Contact control 100-G550 100-FLAM5Ä
    Direct and Impulse Contact control 100-G700, 100-G860 100-FLAM6Ä
    Click to enlarge - 100-MCH00_GS Mechanical Interlock — Horizontal 100-G550 to 100-G550 100-MC00-5H
    100-G550 to 100-G700 or 100-G860 100-MC00-56H
    100-G700 or 100-G860 to 100-G700 or 100-G860 100-MC00-6H
    100-G700 or 100-G860 to 100-G1000 or 100-G1200 100-MC00-67H
    100-G1000 or 100-G1200 to 100-G1000 or 100-G1200 100-MC00-7H
    Click to enlarge - 100-MCV00_GS Mechanical Interlock — Vertical 100-G550 to 100-G550 100-MC00-5V
    100-G550 to 100-G700 or 100-G860 100-MC00-56V
    100-G700 or 100-G860 to 100-G700 or 100-G860 100-MC00-6V
    100-G700 or 100-G860 to 100-G1000 or 100-G1200 100-MC00-67V
    100-G1000 or 100-G1200 to 100-G1000 or 100-G1200 100-MC00-7V
      
    Package Quantity = 1

    Ä Coil Voltage Codes⋆ 

    The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 100-FLAM5Ä becomes Cat. No.100-FLAM5KD.

    For use with [V] 110...120 220...240 380...415 440...480
    100-G550... 100-G860 50-60 Hz KD KF KN KB
      
    ⋆ For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.