Bulletin 100Q-C Capacitor-Switching Contactors

Click to enlarge - 100Q-75-1
Cat. No. 100Q-C37A11


Bulletin 100Q-C — Capacitor-Switching Contactors


Your order must include: cat. no. of the contactor specified with coil voltage code and, if required, cat. no. of any accessories.

The Bulletin 100Q-C Capacitor-Switching contactors are designed for switching banks of capacitors. The unique design uses front-mounted resistor elements that limit the severely high inrush currents seen in these applications. This reduces stress to the contactors and the capacitors, as well as allowing a more compact and economical design without the use of air-core reactors.

Standards Compliance and Certifications

Standards Compliance

IEC 60947-4
CSA C22.2 No. 14
UL 508
Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS


Certifications

CE Marked
cULus Listed (File No. E 41850, Guide NLDX, NLDX7)


Product Selection

For Applications per IEC 60947-4 (AC-6b)

Ratings for Switching Capacitor Banks @ 40 °C
1-Phase 50 Hz (kVar) 3-Phase 50 Hz (kVar) Aux. Contacts Cat. No.
230V 240V 400V 415V 500V 690V 230V 240V 400V 415V 500V 690V N.O. N.C.
5 5 8.5 9 10.5 15 8.5 8.5 15 15.5 18.5 25 1 1 100Q-C16Ä11
2 0 100Q-C16Ä20
8 8.5 14 14.5 17.5 24 14 14 25 25 30 40 1 1 100Q-C37Ä11
2 0 100Q-C37Ä20
  

Ratings for Switching Capacitor Banks @ 60 °C
1-Phase 50 Hz (kVar) 3-Phase 50 Hz (kVar) Aux. Contacts Cat. No.
230V 240V 400V 415V 500V 690V 230V 240V 400V 415V 500V 690V N.O. N.C.
5 5 8.5 9 10.5 15 8.5 8.5 15 15.5 18.5 25 1 1 100Q-C16Ä11
2 0 100Q-C16Ä20
8 8.5 14 14.5 17.5 24 14 14 25 25 30 40 1 1 100Q-C37Ä11
2 0 100Q-C37Ä20
  

For Applications per UL/CSA

Ratings for Switching Capacitor Banks
1-Phase 60 Hz (kVar) 3-Phase 60 Hz (kVar) Aux. Contacts Cat. No.
115V 230V 200V 230V 460V 600V N.O. N.C.
2.2 4.5 6.5 7.5 15 18.5 1 1 100Q-C16Ä11
2 0 100Q-C16Ä20
3.6 7.5 11 12.5 20 25 1 1 100Q-C37Ä11
2 0 100Q-C37Ä20
  

Ä Coil Voltage Code

The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 100Q-C16Ä11 becomes Cat. No.100Q-C16D11.


[V] 12 24 32 36 42 48 100 100-110 110 120 127 200 200-220 208 208-240 220-230 230 230-240 240 277 347 380 380-400 400 400-415 440 480 500 550 600
Hz
50 Hz R K V W X Y KP D P S KG L F VA T N G B M C
60 Hz Q J V X KP D KG H L A T I E N B C
50/60 Hz KJ KY KP KD KG KL KL KF KA KN KB
  

DC Voltages [V] 9 12 24 36 48 60 64 72 80 110 110-125 115 125 220 220-250 230 250
Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
with Integrated Diode DJ
Electronic with Integrated Diode EQ EJ ED EA
  

Maximum Operational Rates

100Q-C16        200 operations/hour
100Q-C37        100 operations/hour


Approximate Dimensions

Bulletin 100Q-C Contactors

Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - mcsc_t


AC Contactors and DC Contactors with 12V or 24V Electronic Coils

Cat. No. a b c c1 c2 Æd d1 d2
100Q-C16 45 (1-25/32) 81 (3-3/16) 119.5 (4-3/4) 114.5 (4-43/64) 6 (15/64) 2 - 4.5 (2 -3/16) 60 (2-23/64) 35 (1-3/8)
100Q-C37 45 (1-25/32) 81 (3-3/16) 136.5 (5-37/64) 131.6 (5-11/32) 6.5 (1/4) 2 - 4.5 (2 -3/16) 60 (2-23/64) 35 (1-3/8)
  

DC Contactors with Conventional Coils

Cat. No. a b c c1 c2 Æd d1 d2
100Q-C16Z 45 (1-25/32) 81 (3-3/16) 145.5 (5-49/64) 140.5 (5-37/64) 6 (15/64) 2 - 4.5 (2 -3/16) 60 (2-23/64) 35 (1-3/8)
100Q-C37Z 45 (1-25/32) 81 (3-3/16) 180.5 (7-5/32) 175.5 (6-61/64) 6.5 (1/4) 2 - 4.5 (2 -3/16) 60 (2-23/64) 35 (1-3/8)
  

DC Contactors with 110V or 220V DC Electronic Coils

Cat. No. a b c c1 c2 Æd d1 d2
100Q-C16EA, 100Q-C16ED 45 (1-25/32) 105 (4-1/8) 119.5 (4-3/4) 114.5 (4-43/64) 6 (15/64) 2 - 4.5 (2 -3/16) 60 (2-23/64) 35 (1-3/8)
100Q-C37EA, 100Q-C37ED 45 (1-25/32) 105 (4-1/8) 136.5 (5-37/64) 131.6 (5-11/32) 6.5 (1/4) 2 - 4.5 (2 -3/16) 60 (2-23/64) 35 (1-3/8)