Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Bulletin 100Q-C Capacitor-Switching Contactors
Bulletin 100Q-C Capacitor-Switching Contactors
Product SelectionFor Applications per IEC 60947-4 (AC-6b)
| Ratings for Switching Capacitor Banks @ 40 °C | ||||||||||||||
| 1-Phase 50 Hz (kVar) | 3-Phase 50 Hz (kVar) | Aux. Contacts | Cat. No. | |||||||||||
| 230V | 240V | 400V | 415V | 500V | 690V | 230V | 240V | 400V | 415V | 500V | 690V | N.O. | N.C. | |
| 5 | 5 | 8.5 | 9 | 10.5 | 15 | 8.5 | 8.5 | 15 | 15.5 | 18.5 | 25 | 1 | 1 | 100Q-C16Ä11 |
| 2 | 0 | 100Q-C16Ä20 | ||||||||||||
| 8 | 8.5 | 14 | 14.5 | 17.5 | 24 | 14 | 14 | 25 | 25 | 30 | 40 | 1 | 1 | 100Q-C37Ä11 |
| 2 | 0 | 100Q-C37Ä20 | ||||||||||||
| Ratings for Switching Capacitor Banks @ 60 °C | ||||||||||||||
| 1-Phase 50 Hz (kVar) | 3-Phase 50 Hz (kVar) | Aux. Contacts | Cat. No. | |||||||||||
| 230V | 240V | 400V | 415V | 500V | 690V | 230V | 240V | 400V | 415V | 500V | 690V | N.O. | N.C. | |
| 5 | 5 | 8.5 | 9 | 10.5 | 15 | 8.5 | 8.5 | 15 | 15.5 | 18.5 | 25 | 1 | 1 | 100Q-C16Ä11 |
| 2 | 0 | 100Q-C16Ä20 | ||||||||||||
| 8 | 8.5 | 14 | 14.5 | 17.5 | 24 | 14 | 14 | 25 | 25 | 30 | 40 | 1 | 1 | 100Q-C37Ä11 |
| 2 | 0 | 100Q-C37Ä20 | ||||||||||||
For Applications per UL/CSA
| Ratings for Switching Capacitor Banks | ||||||||
| 1-Phase 60 Hz (kVar) | 3-Phase 60 Hz (kVar) | Aux. Contacts | Cat. No. | |||||
| 115V | 230V | 200V | 230V | 460V | 600V | N.O. | N.C. | |
| 2.2 | 4.5 | 6.5 | 7.5 | 15 | 18.5 | 1 | 1 | 100Q-C16Ä11 |
| 2 | 0 | 100Q-C16Ä20 | ||||||
| 3.6 | 7.5 | 11 | 12.5 | 20 | 25 | 1 | 1 | 100Q-C37Ä11 |
| 2 | 0 | 100Q-C37Ä20 | ||||||
Ä Coil Voltage Code
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 100Q-C16Ä11 becomes Cat. No.100Q-C16D11.
| [V] | 12 | 24 | 32 | 36 | 42 | 48 | 100 | 100-110 | 110 | 120 | 127 | 200 | 200-220 | 208 | 208-240 | 220-230 | 230 | 230-240 | 240 | 277 | 347 | 380 | 380-400 | 400 | 400-415 | 440 | 480 | 500 | 550 | 600 |
| Hz | ||||||||||||||||||||||||||||||
| 50 Hz | R | K | V | W | X | Y | KP | — | D | P | S | KG | L | — | — | F | — | VA | T | — | — | — | N | — | G | B | — | M | C | — |
| 60 Hz | Q | J | — | V | — | X | — | KP | — | D | — | — | KG | H | L | — | — | — | A | T | I | E | — | — | — | N | B | — | — | C |
| 50/60 Hz | — | KJ | — | — | — | KY | KP | — | KD | — | — | KG | KL | — | — | KL | KF | — | KA | — | — | — | — | KN | — | KB | — | — | — | — |
| DC Voltages [V] | 9 | 12 | 24 | 36 | 48 | 60 | 64 | 72 | 80 | 110 | 110-125 | 115 | 125 | 220 | 220-250 | 230 | 250 |
| Standard | ZR | ZQ | ZJ | ZW | ZY | ZZ | ZB | ZG | ZE | ZD | — | ZP | ZS | ZA | — | ZF | ZT |
| with Integrated Diode | — | — | DJ | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Electronic with Integrated Diode | — | EQ | EJ | — | — | — | — | — | — | — | ED | — | — | — | EA | — | — |
Maximum Operational Rates
100Q-C16 200 operations/hour
100Q-C37 100 operations/hour