3-Pole AC-Operated Contactors


Click to enlarge - 100D-70-2 Click to enlarge - 100D-70-3

Ie [A] Ie [A] Switching of 3-phase motors — AC-2, AC-3 Auxiliary contacts Non-Reversing
Contactor
Cat. No.
Reversing
Contactor
Cat. No.
60 °C 40 °C kW (50 Hz) Hp (60 Hz) N.O. N.C.
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
95 160 30 50 55 63 90 45 25 30 60 75 0 0 100-D95Ä00
1 1 100-D95Ä11
2 4 104-D95Ä24
110 160 32 55 63 75 100 55 40 40 75 100 0 0 100-D110Ä00
1 1 100-D110Ä11
2 4 104-D110Ä24
140 250 45 75 80 80 110 75 40 50 100 125 0 0 100-D140Ä00
1 1 100-D140Ä11
2 4 104-D140Ä24
180 250 55 90 100 90 132 90 50 60 150 150 0 0 100-D180Ä00
1 1 100-D180Ä11
2 4 104-D180Ä24
210 350 63 110 125 150 200 110 60 75 150 200 0 0 100-D210Ä00
1 1 100-D210Ä11
2 4 104-D210Ä24
250 350 80 132 150 160 250 132 75 100 200 250 0 0 100-D250Ä00
1 1 100-D250Ä11
2 4 104-D250Ä24
300 450 90 160 160 200 300 160 100 125 250 300 0 0 100-D300Ä00
1 1 100-D300Ä11
2 4 104-D300Ä24
420 540 132 220 250 300 425 220 150 175 350 400 0 0 100-D420Ä00
1 1 100-D420Ä11
2 4 104-D420Ä24
630 800 200 355 355 450 500 200 250 500 600 0 0 100-D630Ä00
1 1 100-D630Ä11
2 4 104-D630Ä24
860 1000 250 500 500 560 600 250 300 600 700 0 0 100-D860Ä00
1 1 100-D860Ä11
2 4 104-D860Ä24
     

Ä Coil Voltage Codes for AC Control

Conventional Coil [V] 24 48 100 110 120 200 208 220…230 230 240 277 380…400 415 440 480 500 550 600
100-D95...100-D180 50 Hz K Y D A T N B G M C
60 Hz J X D H A T N B C
100-D95…100-D110 50/60 Hz KP KN KG KL KF KA KT
  

Electronic Coil
w/ EI. Interface § 
[V] 24 42…64 100 110…130 200 208…277 200…220 230…250 277 380…415 380…500 440…480 500
100-D95...100-D300 50/60 Hz EJ§  EY EP ED EG EA EN
100-D420 50/60 Hz EP ED EG EA EN
100-D630…100-D860 50/60 Hz EP ED EG EG EA ET EN EB EM
  

§ Signal voltage of the Cat. No. 100-D… electronic interface: nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC...30.2V DC
Dropout Voltage: –3.0V DC...+5.0V DC.
§ Not available with 100/104-D300.


3-Pole DC-Operated Contactors


Click to enlarge - 100D-70-2 Click to enlarge - 100D-70-3

Ie [A] Switching of 3-phase motors AC-2, AC-3 Auxiliary contacts Non-Reversing
Contactor
Cat. No.
Reversing
Contactor
Cat. No.
60 °C 40 °C kW (50 Hz) Hp (60 Hz) N.O. N.C.
AC-3 AC-1 230V 400V 415V 500V 690V 1000V 200V 230V 460V 575V Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
95 160 30 50 55 63 90 45 25 30 60 75 0 0 100-D95Ä00
1 1 100-D95Ä11
2 1/1L 100-D95Ä22LT 
2 4 104-D95Ä24
2 2/2L 104-D95Ä24LT 
110 160 32 55 63 75 100 55 40 40 75 100 0 0 100-D110Ä00
1 1 100-D110Ä11
2 1/1L 100-D110Ä22LT 
2 4 104-D110Ä24
2 2/2L 104-D110Ä24LT 
140 250 45 75 80 80 110 75 40 50 100 125 0 0 100-D140Ä00
1 1 100-D140Ä11
2 1/1L 100-D140Ä22LT 
2 4 104-D140Ä24
2 2/2L 104-D140Ä24LT 
180 250 55 90 100 90 132 90 50 60 150 150 0 0 100-D180Ä00
1 1 100-D180Ä11
100-D180Ä22LT 
2 4 104-D180Ä24
2 2/2L 104-D180Ä24LT 
210 350 63 110 125 150 200 110 60 75 150 200 0 0 100-D210Ä00
1 1 100-D210Ä11
2 4 104-D210Ä24
250 350 80 132 150 160 250 132 75 100 200 250 0 0 100-D250Ä00
1 1 100-D250Ä11
2 4 104-D250Ä24
300 450 90 160 160 200 300 160 100 125 250 300 0 0 100-D300Ä00
1 1 100-D300Ä11
2 4 104-D300Ä24
420 540 132 220 250 300 425 220 150 175 350 400 0 0 100-D420Ä00
1 1 100-D420Ä11
2 4 104-D420Ä24
630 800 200 355 355 450 500 200 250 500 600 0 0 100-D630Ä00
1 1 100-D630Ä11
2 4 104-D630Ä24
860 1000 250 500 500 560 600 250 300 600 700 0 0 100-D860Ä00
1 1 100-D630Ä11
2 4 104-D860Ä24
  

Ä Coil Voltage Codes for DC Control

Conventional Coil [V] 24 48 110 125 220
100-D95...100-D180T  DC ZJ ZY ZD ZS ZA
  

Electronic Coil
w/ EI Interface § 
[V] 24 48…72 110…130 200…255
100-D95...100-D300 DC EZJ EZY EZD EZA
100-D420 DC EZD EZA
100-D630…100-D860 DC ED EA
  

T For conventional DC coils, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contact(s).
§ Signal voltage of the Cat. No. 100-D… electronic interface: nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC...30.2V DC , Dropout Voltage: –3.0V DC...+5.0V DC.


Auxiliary contacts with sequence numbering.

Cat. Nos. 100-D95…D420 — Electronic and Conventional AC Coils, Electronic DC Coils

Click to enlarge - 100D-73-1


Contact Configuration Auxiliary contact configurations
    Left Side Mounting   Right Side Mounting
N.O. N.C. Outside Cat. No. Inside Cat. No. For Use With Inside Cat. No. Outside Cat. No.
8 0 100-DS2-20 100-DS1-20 100-D…00 100-DS1-20 100-DS2-20
Sequence starts with… 7/8 3/4 1/2 5/6
7 1 100-DS2-20 100-DS1-20 100-D…00 100-DS1-11 100-DS2-20
Sequence starts with… 7/8 3/4 1/2 5/6
6 2 100-DS2-20 100-DS1-11 100-D…00 100-DS1-11 100-DS2-20
Sequence starts with… 7/8 3/4 1/2 5/6
5 3 100-DS2-20 100-DS1-11 100-D…00 100-DS1-11 100-DS2-11
Sequence starts with… 7/8 3/4 1/2 5/6
4 4 100-DS2-11 100-DS1-11 100-D…00 100-DS1-11 100-DS2-11
Sequence starts with… 7/8 3/4 1/2 5/6
  

Cat. Nos. 100-D95…D420 — Electronic and Conventional AC Coils, Electronic DC coils

Click to enlarge - 100D-73-2


Contact Configuration Auxiliary contact configurations
    Left Side Mounting   Right Side Mounting
N.O. N.C. Outside Cat. No. Inside Cat. No. For Use With Inside Cat. No. Outside Cat. No.
8 0 100-D…11
Sequence starts with…
7 1 100-DS2-20 100-DS1-20 100-D…11 100-DS1-11 100-DS2-20
Sequence starts with… 7/8 3/4 1/2 5/6
6 2 100-DS2-20 100-DS1-11 100-D…11 100-DS1-11 100-DS2-20
Sequence starts with… 7/8 3/4 1/2 5/6
5 3 100-DS2-20 100-DS1-11 100-D…11 100-DS1-11 100-DS2-11
Sequence starts with… 7/8 3/4 1/2 5/6
4 4 100-DS2-11 100-DS1-11 100-D…11 100-DS1-11 100-DS2-11
Sequence starts with… 7/8 3/4 1/2 5/6
  

Contactor cat. nos. 100-D95…D180 — Conventional DC coils

Click to enlarge - 100D-73-3


Contact Configuration Auxiliary contact configurations
    Left Side Mounting   Right Side Mounting
N.O. N.C. Outside Cat. No. Inside Cat. No. For Use With Inside Cat. No. Outside Cat. No.
8 0 100-D…22L
Sequence starts with…
7 1 100-D…22L
Sequence starts with…
6 2 100-DS2-20 100-DS1-11 100-D…22L 100-DS1-L11¬  100-DS2-20
Sequence starts with… 7/8 3/4 1/2 5/6
5 3 100-DS2-20 100-DS1-11 100-D…22L 100-DS1-L11¬  100-DS2-11
Sequence starts with… 7/8 3/4 1/2 5/6
4 4 100-DS2-11 100-DS1-11 100-D…22L 100-DS1-L11¬  100-DS2-11
Sequence starts with… 7/8 3/4 1/2 5/6
  
¬ With conventional DC control, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts.