Catalogs > Industrial Controls Catalog > Motor Control, IEC > Contactors > Bulletin 100-D IEC Contactors
Bulletin 100-D IEC Contactors
| Introduction | Standards Compliance and Certifications | Product Selection | Bulletin 100-D/104-D Accessories |
| Bulletin 100/104-K, 100/104-C, 100/104-D, 100S/104S-C, 100S-D Specifications | Bulletin 100-D/104-D Life-Load Curves | Bulletin 100-D Approximate Dimensions | Renewal Parts |
3-Pole AC-Operated Contactors
- Conventional and Electronic AC Coils
- 3 Main Contacts
- Non-Reversing or Reversing
|
|
Ä Coil Voltage Codes for AC Control
| Conventional Coil | [V] | 24 | 48 | 100 | 110 | 120 | 200 | 208 | 220…230 | 230 | 240 | 277 | 380…400 | 415 | 440 | 480 | 500 | 550 | 600 |
| 100-D95...100-D180 | 50 Hz | K | Y | — | D | — | — | — | A | — | T | — | N | B | G | — | M | C | — |
| 60 Hz | J | X | — | — | D | — | H | — | — | A | T | — | — | N | B | — | — | C | |
| 100-D95…100-D110 | 50/60 Hz | — | — | KP | KN | — | KG | — | KL | KF | KA | KT | — | — | — | — | — | — | — |
| Electronic Coil w/ EI. Interface § |
[V] | 24 | 42…64 | 100 | 110…130 | 200 | 208…277 | 200…220 | 230…250 | 277 | 380…415 | 380…500 | 440…480 | 500 |
| 100-D95...100-D300 | 50/60 Hz | EJ§ | EY | EP | ED | EG | EA | — | — | — | — | EN | — | — |
| 100-D420 | 50/60 Hz | — | — | EP | ED | EG | EA | — | — | — | — | EN | — | — |
| 100-D630…100-D860 | 50/60 Hz | — | — | EP | ED | EG | — | EG | EA | ET | EN | — | EB | EM |
§ Signal voltage of the Cat. No. 100-D… electronic interface: nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC...30.2V DC
Dropout Voltage: 3.0V DC...+5.0V DC.
§ Not available with 100/104-D300.
3-Pole DC-Operated Contactors
- Conventional and Electronic DC Coils
- 3 Main Contacts
- Non-Reversing or Reversing
|
|
Ä Coil Voltage Codes for DC Control
| Conventional Coil | [V] | 24 | 48 | 110 | 125 | 220 |
| 100-D95...100-D180T | DC | ZJ | ZY | ZD | ZS | ZA |
| Electronic Coil w/ EI Interface § |
[V] | 24 | 48…72 | 110…130 | 200…255 |
| 100-D95...100-D300 | DC | EZJ | EZY | EZD | EZA |
| 100-D420 | DC | — | — | EZD | EZA |
| 100-D630…100-D860 | DC | — | — | ED | EA |
T For conventional DC coils, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contact(s).
§ Signal voltage of the Cat. No. 100-D… electronic interface: nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC...30.2V DC , Dropout Voltage: 3.0V DC...+5.0V DC.
Auxiliary contacts with sequence numbering.
Cat. Nos. 100-D95…D420 — Electronic and Conventional AC Coils, Electronic DC Coils
|
| Contact Configuration | Auxiliary contact configurations | |||||
| Left Side Mounting | Right Side Mounting | |||||
| N.O. | N.C. | Outside Cat. No. | Inside Cat. No. | For Use With | Inside Cat. No. | Outside Cat. No. |
| 8 | 0 | 100-DS2-20 | 100-DS1-20 | 100-D…00 | 100-DS1-20 | 100-DS2-20 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 7 | 1 | 100-DS2-20 | 100-DS1-20 | 100-D…00 | 100-DS1-11 | 100-DS2-20 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 6 | 2 | 100-DS2-20 | 100-DS1-11 | 100-D…00 | 100-DS1-11 | 100-DS2-20 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 5 | 3 | 100-DS2-20 | 100-DS1-11 | 100-D…00 | 100-DS1-11 | 100-DS2-11 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 4 | 4 | 100-DS2-11 | 100-DS1-11 | 100-D…00 | 100-DS1-11 | 100-DS2-11 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
Cat. Nos. 100-D95…D420 — Electronic and Conventional AC Coils, Electronic DC coils
|
| Contact Configuration | Auxiliary contact configurations | |||||
| Left Side Mounting | Right Side Mounting | |||||
| N.O. | N.C. | Outside Cat. No. | Inside Cat. No. | For Use With | Inside Cat. No. | Outside Cat. No. |
| 8 | 0 | — | — | 100-D…11 | — | — |
| Sequence starts with… | — | — | — | — | ||
| 7 | 1 | 100-DS2-20 | 100-DS1-20 | 100-D…11 | 100-DS1-11 | 100-DS2-20 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 6 | 2 | 100-DS2-20 | 100-DS1-11 | 100-D…11 | 100-DS1-11 | 100-DS2-20 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 5 | 3 | 100-DS2-20 | 100-DS1-11 | 100-D…11 | 100-DS1-11 | 100-DS2-11 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 4 | 4 | 100-DS2-11 | 100-DS1-11 | 100-D…11 | 100-DS1-11 | 100-DS2-11 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
Contactor cat. nos. 100-D95…D180 — Conventional DC coils
|
| Contact Configuration | Auxiliary contact configurations | |||||
| Left Side Mounting | Right Side Mounting | |||||
| N.O. | N.C. | Outside Cat. No. | Inside Cat. No. | For Use With | Inside Cat. No. | Outside Cat. No. |
| 8 | 0 | — | — | 100-D…22L | — | — |
| Sequence starts with… | — | — | — | — | ||
| 7 | 1 | — | — | 100-D…22L | — | — |
| Sequence starts with… | — | — | — | — | ||
| 6 | 2 | 100-DS2-20 | 100-DS1-11 | 100-D…22L | 100-DS1-L11¬ | 100-DS2-20 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 5 | 3 | 100-DS2-20 | 100-DS1-11 | 100-D…22L | 100-DS1-L11¬ | 100-DS2-11 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| 4 | 4 | 100-DS2-11 | 100-DS1-11 | 100-D…22L | 100-DS1-L11¬ | 100-DS2-11 |
| Sequence starts with… | 7/8 | 3/4 | 1/2 | 5/6 | ||
| ¬ With conventional DC control, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contacts. | ||||||